VENTIS VB00014 Wood Insert Owner’s Manual
- June 12, 2024
- Ventis
Table of Contents
Wood Insert
Owner’s Manual
INSTALLATION AND
OPERATION REQUIREMENTS
HEI170
(VB00014 Model)
VB00014 Wood Insert
Safety tested according to CAN/ULC 628, UL 1482 and UL 737 by an accredited
laboratory.
US Environmental Protection Agency phase II certified wood insert compliant
with 2020 cord wood standard.
EPA
2.5 g/h <≤
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION
INSPECTION REQUIREMENTS IN THE AREA.
READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS WOOD INSERT.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN PROPERTY DAMAGE, BODILY
INJURY OR EVEN DEATH.
READ AND KEEP THIS MANUAL FOR REFERENCE
ONLINE WARRANTY REGISTRATION
If the unit requires repairs during the warranty period, proof of purchase
must be provided. The purchase invoice must be kept. The date indicated on it
establishes the warranty period. If it can not be provided, the warranty
period will be determined by the date of manufacture of the product.
It is also highly recommended to register the warranty online at
http://www.occanada.com/en/service-support/warranty/warranty-registration
Registering the warranty will help to quickly find the information needed on the unit.
Dealer:
Installer:
Phone Number:____
Serial Number:_____
General Information
2.1 Performances
Values are as measured per test method, except for the recommended heating
area, firebox volume, maximum burn time and maximum heat output.
Model | Hal 70 (VB00014) |
---|---|
Type of combustion | Non-catalytic |
Fuel Type | Dry Cordwood |
Recommended heating area (sq. ft. .)1 | 500 to 1,800 ft2 (46 to 167 m2) |
Overall firebox volume2 | 1.86 ft3 (0.053 m3) |
EPA loading volume | 1.44 ft3 (0.041 m3) |
Maximum burn time’ | 7 hours |
Maximum heat output (dry cordwood)3 | 65,000 BTU/h (19 kW) |
Overall heat output rate (min. to max.)22 | 9,800 BTU/h to 52,200 BTU/h (2.87 |
kW to 15.3 kW)
Average overall efficiency3 (Dry cordwood)| 68 % (HHV)5| 73 % (LHV)6
Optimum overall efficiency’| 76%
Optimum heat transfer efficiency8| 75%
Average particulate emissions rate9| 2.4 g/h (EPA / CSA B415.1-10)70
Average CO”| 103 g/h
- Recommended heating area and maximum burn time may vary subject to location in home, chimney draft,heat loss factors, climate, fuel type and other variables. The recommended heated area for a given appliance is defined by the manufacturer as its capacity to maintain a minimum acceptable temperature in the designated area in case of a power failure.
- The overall firebox calculation is an approximation and is not intended to be used for loading. This volume includes a buffer zone to allow an easier fuel insertion, prevent ash spillage and allow the air wash to work properly.
- The maximum heat output (dry cordwood) is based on a loading density varying between 15 lb/ft and 20 lb/ft
- Other performances are based on a fuel load prescribed by the standard. The specified loading density varies between 7 lb/ft³ and 12 lb/ft3. The moisture content is between 19% and 25%.
- As measured per CSA B415.1-10 stack loss method.
- Higher Heating Value of the fuel.
- Lower Heating Value of the fuel.
- Optimum overall efficiency at a specific burn rate (LHV).
- The optimum heat transfer efficiency is for the low burn rate and represents the appliance’s ability to convert the energy contained in the wood logs into energy transferred to the room in the form of heat and does not take into account the chemical losses during combustion.
- This appliance is officially tested and certified by an independent agency.
- Tested and certified in compliance with CFR 40 part 60, subpart AAA, section 60.534(a)(1(ii) and ASTM E3053-17. Based on EPA letter dated November 1, 2022.11 Carbon monoxide.
2.2 Specifications
Recommended log length | 16 in (406 mm) east-west |
---|---|
Maximum log length’ | 18 in (457 mm) east-west |
Flue outlet diameter | 6 in (150 mm) |
Recommended connector pipe diameter | 6 in (150 mm) |
Type of chimney | ULC S635, CAN/ULC-S640, UL 1777 |
Minimum liner height | 12 feet |
Baffle material | Vermiculite |
Approved for alcove installation | Not applicable |
Approved for mobile home installation2 | No |
Type of door | Simple, glass with cast iron frame |
Type of glass | Ceramic glass |
Blower | Included (up to 144 CFM) |
Particulate emission standard3 | EPA / CSA B415.1-10 |
USA Standard (Safety) | UL 1482, UL 737 |
Canada Standard (Safety) | CAN/ULC-628 |
2.3 Dimensions
1.1 EPA Loading Procedure
The best loading method for efficient and clean combustion with this fireplace
is the EPA loading method. The images below show the space in the firebox
where the logs are to be placed. It is important to always respect this space
and not to put logs in the grid area marked with an X.
The marked area is defined by the space between the glass and primary air
channel. Leave enough space between the logs for good air circulation. Using
more than the usable firebox volume for loading wood will result in poor
combustion. The Usable firebox volume of 1.44 ft³ shown below is the one used
during EPA emissions certification. The log length recommended for this stove
is 16 inches and the EPA testing were done with log length of 16 in. The fuel
specie used for the EPA certification was beech.
1.1.1 Air control
The air control is located underneath the ash shelf. To open the air control,
pull the air control handle completely toward you (High). This will increase
the burn rate. To close the air control, push the air control handle
completely. This will permit to achieve the lowest possible burn rate.
1.1.2 High burn rate (primary air control open )
For Kindling and Start-up fuel configuration refer to the pictures below.
Split the start-up fuellog into 6 pieces. Crisscross at 45 degrees the 6
pieces on the brick on 3 rows (From thebottom, first row 2 smallest-second row
2 biggest- third row 2 medium) and leaving some spacebetween each wood pieces.
Crisscross at 45 degrees the kindling on the top of the start-up fuelon 3
rows, from biggest to smallest. The kindling is made of between 12-15 small
pieces thatare about 10% of moisture content. Place newspaper sheets on top of
the kindling. Light up thepaper and let the door at 90 degrees between one
minute and one minute and 30 seconds, thenclose the door. Air control is fully
open.
When there are only faint flames remaining and most of the wood is turned into
coal, break ashes and level coal bed. Close the door.
Add High Fire load in an East-West configuration. Put 3 first pieces on the
coal bed. Leave about 2 inches of air space between the rear firebrick and the
first piece. See Figure 11 and 12 for an example of high burn load inside the
firebox. The front (3rd) piece should stand off on the steel andirons by
approximately 1-2 inches. The 2 other pieces should be added on top of the
first 3, stacked in the middle, in an East-West orientation. Let the door open
at 90 degrees between
one minute and one minute and 30 seconds. Close the door, start the blower at
maximum speed, and let burn until the weight is down to target.
For optimal loading of a high fire, take small to medium size fuel pieces (between 2- and 3-inches cross section dimensions approximately) on the bottom and use medium to large size fuel pieces (3.5 to 4.5 inches of cross section dimensions approximately) on top. To make sure combustion is equal, put the biggest piece on top of the first three, at the front of the firebox. See an example of high burn load in the Figure 13 above.
1.1.3 Low burn rate
After the high fire, if there is visible yellow flame, close the air control.
When the charcoal bed weight is between 14 and 17% of the low fire load
weight, turn off the blower, open the door, stir the coals slightly, just
enough to have a level plane coal bed, and let the door remain slightly open
for 1 minute before loading the low burn test fuel.
For the loading, put 3 first pieces on the coal bed in an East-West
orientation. Leave approximately 1 inch of air space between the rear
firebrick and the first piece. There should be air space between all pieces.
The front (3rd) piece may contact the steel andirons. The 2 top pieces
(fourth and fifth) should be added on top of the first 3, slightly angled (10°
from the 3 wood pieces at the bottom). The distance between the logs should be
approximately 1 inch. See Figure 14 and 15 for an example of low burn load
inside the firebox.
For optimal low fire load, use medium to large size fuel pieces (between 4-
and 5.5-inches cross section dimensions approximately) on the bottom and use
small to medium size fuel pieces (2.5 to 4 inches cross section dimensions
approximately) on top. To make sure combustion is equal, put the smallest
piece on top of the first three, at the back of the firebox (see Figure 16 for
an example of low burn load).
Let the door ajar at 90° until the flames roll on top of the fuel (between 2:00 and 4:00 minutes) and then close the door with the primary air control open. See picture below for rolling flame:
Close the primary air control by small increments (ex: 1/16 of an inch), from
½’’ to fully closed, between 4 and 15 minutes after the loading period. Before
closing further, make sure the flame intensity is increasing or stable. Close
the air control completely. Turn ON the blower at maximum speed.
1.1.4 Medium burn rate
After the high fire, if there is visible yellow flame, close the air control.
When the charcoal bed weight is between 14 and 17% of the medium fire load
weight, turn off the blower, open the door, stir the coals slightly, just
enough to have a level plane coal bed, and let the door remain slightly open
for 1 minute before loading the medium burn test fuel.
For the loading, put 3 first pieces on the coal bed in an East-West
orientation. Leave about 1 to 2 inches of air space between the rear firebrick
and the first piece. The front (3rd) piece should stand off from the steel
andirons by approximately 1 inch. The 2 top pieces (fourth and fifth) should
be added on top of the first 3, slightly angled (10° from horizontal, top
view). The distance between the logs should be approximately 1 inch. See
Figure 17 and 18 for an example of medium burn load inside the firebox.
For optimal medium fire load, use medium to large size fuel pieces (between 4-
and 5.5-inches cross section dimensions approximately) on the bottom and use
small to medium size fuel pieces (2.5 to 4 inches cross section dimensions
approximately) on top. To make sure combustion is equal, put the smallest
piece on top of the first three, at the back of the firebox (see Figure 19 for
an example of medium burn load).
Let the door ajar at 90° until the flames roll on top of the fuel (between 2:30 and 5:00) and then close the door with the primary air control open. See picture below for rolling flame:
Close the primary air control by small increments (ex: 1/16 of an inch) until
reaching the midpoint of air control position, between 4 and 15 minutes after
the loading period. Before closing further, make sure the flame intensity is
increasing or stable.
Turn ON the blower at maximum speed.
Clearances to Combustible Material
When the insert is installed so that its surfaces are at or beyond the minimum
clearances specified, combustible surfaces will not overheat under normal and
even abnormal operating conditions.
NO PART OF THE INSERT MAY BE LOCATED CLOSER TO THE COMBUSTIBLE THAN THE
MINIMUM CLEARANCE FIGURES GIVEN.
CLEARANCES MAY ONLY BE REDUCED BY MEANS APPROVED BY THE REGULATORY AUTHORITY.
3.1 Minimum Masonry Opening and Clearances to Combustibles
| MINIMUM CLEARANCES
---|---
F| 16″ (406 mm)
G| 9″ (229 mm)
H| 27″ (686 mm)
I| 27″ (686 mm)
Q| 84″ (213 cm)
| MAXIMUM THICKNESS
---|---
O| 5″ (127 mm)
P| 12″ (305 mm)
| MINIMUM MASONRY OPENING
---|---
J| 21 ½” (546 mm)
K1| 27 ½” (700 mm)
L| 12 ¾” (324 mm)
3.2 Floor Protection
It is necessary to have a floor protection made of non-combustible materials
that meets the measurements specified in the “Table 1 : Floor Protection”
below.
3.2.1 Installation Raised of 4″ (102 mm) and Less
If non-combustible material floor protection needs to be added in front of and
level with the hearth extension of the masonry fireplace (F = 4″ (102 mm) or
less), an R-value equal to or greater than 1.00 is required and should extend
at least 22″ (559 mm) in front of the unit (B). Refer to “Additional Floor
Protection – Not Raised Installation”
3.2.2 Installation Raised of More Than 4″ (102 mm)
If the extension of the masonry hearth is raised at least 4″ (102 mm) from the
floor protection, a noncombustible material, without an R-value, must extend
at least 16″ (406 mm in USA) or 18″ (457 mm in Canada) in front of the unit
(B). Refer to “Additional Floor Protection – Raised Installation”.
3.3 R Value
There are two ways to calculate the R-value of the floor protection. First, by
adding the R-values of materials used, or by the conversion if the K factor
and thickness of the floor protection are given.
To calculate the total R value from R values of the materials used, simply add
the R-values of materials. If the result is equal to or greater than the
R-value requirements, the combination is acceptable. R-values of some selected
materials are shown below.
Table 2 : Thermal Characteristics of Common Floor Protection Materials
MATERIAL| CONDUCTIVITY (K)
PER INCH| RESISTANCE (R)
PER INCH THICKNESS
---|---|---
Micore® 160| 0.39| 3.
Micore® 300| 0.49| 2.
Durock®| 2.| 0.52
Hardibacker®| 2.| 0.51
Hardibacker® 500| 2.| 0.44
Wonderboard®| 3.| 0.31
Cement mortar| 5.00| 0.2
Common brick| 5.00| 0.2
Face brick| 9.00| 0.11
Marble| 14.3 – 20.00| 0.07 – 0.05
MATERIAL| CONDUCTIVITY (K)
PER INCH| RESISTANCE (R)
PER INCH THICKNESS
---|---|---
Ceramic tile| 13.| 0.008
Concrete| 1.050| 0.950
Mineral wool insulation| 0.320| 3.120
Limestone| 7.| 0.153
Ceramic board (Fibremax)| 0.450| 2.
Horizontal still air (1/8″ thick)’| 0.135| 0,920**
Exemple:
Required floor protection R of 1.00. Proposed materials: four inches of brick
and one inch of Durock® board:
Four inches of brick (R = 4 x 0,2 = 0,8) plus 1 inch of Durock® (R = 1 x 0.52
= 0.52).
0.8 + 0.52 = 1.32.
This R value is larger than the required 1.00 and is therefore acceptable.
In the case of a known K and thickness of alternative materials to be used in
combination, convert all K values to R by dividing the thickness of each
material by its K value. Add R values of the proposed materials as shown in
the previous example.
Exemple:
K value = 0.75
Thickness = 1
R value = Thickness/K = 1/0.75 = 1.33
Installing Options on Your Product and Replacing Parts
4.1 Replacement and Adjustment
4.1.1 Door
Note: The images shown are for guidance only and may be different from
your product, but the assembly remains the same.
In order for the insert to burn at its best efficiency, the door must provide
a perfect seal with the firebox. Therefore, the gasket should be inspected
periodically to check for a good seal. The tightness of the door seal can be
verified by closing and latching the door on a strip of paper.
The test must be performed all around the door. If the paper slips out easily
anywhere, either adjust the door or replace the gasket.
4.1.2 Adjustment
The gasket seal may be improved with a simple latch mechanism adjustment:
- Remove the split pin by pulling and turning it using pliers.
- Turn the handle one counterclockwise turn to increase pressure.
- Reinstall the split pin with a small hammer.
4.1.3 Door Alignment
To align, open the door and loosen the pressures screws located on the lower
and upper hinges of the door using a 3/32” Allen key to free the adjustable
hinge rods.
Using a flat screwdriver, turn the adjustable hinge rods in the direction
shown to adjust the doors. Tighten all door hinge pressure screws when they
are at the desired positions.
Configurations 1-2-3-4-5-6, show in which direction these act on the
adjustment of the door.
4.1.4 Gasket
It is important to replace the gasket with another having the same diameter
and density to maintain a good seal.
-
Remove the door and place it face-down on something soft like a cushion of rags or a piece of carpet.
-
Remove the old gasket from the door. Use a screwdriver to scrape the old gasket adhesive from the door gasket groove.
-
Apply a bead of approximately 3/16″ (5 mm) of high temperature silicone in the door gasket groove. Starting from the middle, hinges side, press the gasket into the groove. The gasket must not be stretched during installation.
-
Leave about ½″ (10 mm) long of the gasket when cutting and press the end into the groove. Tuck any loose fibers under the gasket and into the silicone.
-
Close the door. Do not use the insert for 24 hours.
4.1.5 Glass Replacement
The glass used is a ceramic glass, 5/32″ (4 mm) thick,16 5/8″W X 10 3/16″H (422mm x 259mm) tested to reach temperatures up to 1400º F. If the glass breaks, it must be replaced by a ceramic glass from SCHOTT with the same specification. Contact your dealer to obtain a genuine replacement part. Tempered glass or ordinary glass will not withstand the high temperatures of this unit.
WARNING : DO NOT USE SUBSTITUTE MATERIALS WHEN REPLACING THE GLASS.
To remove or replace the glass (D): -
Remove the door from its hinges and lay it on a soft, flat surface.
-
Remove the screws (A), the glass retainers (B), and the metal frames (C).
-
Remove the glass (D). If it is damaged install a new one in place. The replacement glass must have a gasket all around (see procedure below).
-
Reinstall the glass, being careful to centre the glass in the door and not to over-tightening the retaining screw.
The two main causes of broken door glass are uneven placement in the door and overtightening the retaining screws.
4.1.6 Glass Gasket Replacement
The glass gasket is flat, adhesive-backed, woven fibreglass. The gasket must
be centred on the edge of the glass.
-
Follow the steps of the previous section to remove the glass.
-
Remove the old gasket and clean the glass thoroughly.
-
Peel back a section of the paper covering the adhesive and place the gasket on a table with the adhesive side up.
-
Stick the end of the gasket to the middle of one edge, then press the edge of the glass down onto the gasket, taking care that it is perfectly centred on the gasket.
-
Peel off more of the backing and rotate the glass. The gasket must not be stretched during installation.
-
Cut the gasket to the required length.
-
Pinch the gasket onto the glass in a U shape, all around the glass.
By following these instructions, the edge clearances are maintain.
4.2 Blower and Ash Lip Installation
-
Install the ash lip (A) on the insert with three screws (B).
-
Center the blower on the ash lip and push it against the firebox. Then push it until it clips.
4.3 Faceplate Installation
-
Remove the faceplate extension (K) secured between the firebox and the convection air jacket.
-
Lay the panels on a flat and non abrasive surface. Align the top panel holes (L) with the left (N) and right (M) panels. Secure together using the four bolts (P) and nuts (O) provided.
-
Align the holes of the faceplate extension (K) with the holes in the faceplate panels and screw them using bolts (P) and nuts (O) provided.
-
Center the insert into the fireplace opening.
If necessary, adjust the height of the insert using the levelling bolts (T) on each side of the insert until the faceplate is properly seated on the floor of the hearth extension. -
Align the notch in the faceplate extension with the bolt (Q) welded to the air jacket located and slide the faceplate assembly just over the bolt’s head and washer (R). Then push towards the fireplace.
-
Once the faceplate is in place, secure the assembly by tightening nuts (S) using a 7/16″ (11 mm) open end wrench.
4.4 Optional Fresh Air Intake Kit Installation
Note: The fresh air intake kit may be installed on the right or left end
side of the unit. The unused side must be covered by the plate provided in the
user manual kit.
-
Install the fresh air intake adapter (E) with four screws (F) then secure the flexible pipe 1 (H) (not included) to the adapter using one of the pipe clamps (G). Secure the other end of the pipe to the outside wall termination (J) using the other pipe clamp. The outside wall termination must be installed outside of the home.
-
Install the plate (K) with four screws (L) on the unused side of the insert.
4.5 Optional Fire Screen Installation
In the United States or in provinces with a particulate emissions limit (e.g.:
US EPA), the use of opendoor wood stoves with a rigid firescreen is
prohibited.
-
Open the door.
-
Hold the fire screen by the two handles and bring it close to the door opening.
-
Lean the upper part of the fire screen against the top door opening making sure to insert the top fire screen brackets behind the primary air deflector.
-
Lift the fire screen upwards and push the bottom part towards the insert then let the fire screen rest on the bottom of the door opening.
Warning: Never leave the insert unattended while in use with the fire screen.
4.6 Log Retainers Installation
4.7 Air Tubes and Baffle Installation
-
Starting with the rear tube, lean and insert the right end of the secondary air tube into the rear right channel hole. Then lift and insert the left end of the tube into the rear left channel.
-
Align the notch in the left end of the tube with the key of the left air channel hole. Using a« Vise grip » hold the tube and lock it in place by turning the tube as shown. Make sure the notch reaches the end of the key way.
-
Install the baffle.
-
Repeat steps 1 and 2 for the three other tubes.
-
To remove the tubes use the above steps in reverse order.
Note that secondary air tubes (A) can be replaced without removing the baffle board (B) and that all tubes are not necessarely identical (look at the part number on the tube).
4.8 Removal Instructions
For inspecting purposes, the insert may need to be removed. To remove the
insert, follow these instructions:
- Unscrew the faceplate fastener (B) holding the faceplate (C) on the insert.
- Remove faceplate (C) by pulling on it.
- Remove the blower assembly (D).
- Remove the three screws securing the pipe connector (A).
- Unscrew the bolts securing the insert to the floor on each side of the unit (E).
4.9 Exploded Diagram and Parts List
IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for this unit, please provide the model number and the serial number. We reserve the right to change parts due to technology upgrades or availability. Contact an authorized dealer to obtain any of these parts. Never use substitute materials. Use of non-approved parts can result in poor performance and safety hazards.
# | Item | Description | Qty |
---|---|---|---|
1 | 30898 | ROUND WOODEN BLACK HANDLE | 2 |
2 | AC01299 | RIGID FIRESCREEN | 1 |
3 | AC07868 | 1/2″ BLACK COIL HANDLE | 1 |
4 | 30101 | SPRING TENSION PIN 5/32″0 X 1 1/2″L | 1 |
5 | SE70697 | REPLACEMENT HANDLE WITH LATCH KIT | 1 |
6 | AC09185 | DOOR LATCH KIT | 1 |
7 | AC06500 | SILICONE AND 5/8′ X 8′ BLACK DOOR GASKET KIT (AC-DGKNC) | 1 |
8 | SE24328 | VENTIS SERIAL 1.7 CAST IRON DOOR | 1 |
9 | SE70789 | VENTIS 1.7 GLASS 16 5/8″W X 10 3/16″H | 1 |
10 | AC06400 | 3/4″ X 6′ x 1/8′ FLAT BLACK SELF-ADHESIVE GLASS GASKET (AC-GGK) |
1
11| SE70742| GLASS AND MOULDING KIT| 2
12| PL70884| RIGHT GLASS FRAME| 2
13| SE53585| GLASS RETAINER KIT WITH SCREWS (12 PER KIT)| 1
14| 30507| BLACK TORX SCREW WITH FLAT HEAD TYPE F 1/4-20 X 3/4″| 4
15| SE75734| ASH SELF ASSEMBLY| 1
16| SE70719| DAMPER ASSEMBLY| 1
17| 30187| STAINLESS WASHER ID 17/64″ X OD 1/2″| 1
18| 30206| ZINC WASHER 5/16’ID X 3/4’0D| 1
19| 30060| THREAD-CUTTING SCREW 1/4-20 X 1/2″ F HEX STEEL SLOT WASHER C102
ZINC| 2
20| 30782| HEX FLANGE NUT SERRATED 1/4-20 STAINLESS 18-8| 1
21| SE70720| AIR CONTROL ROD ASSEMBLY| 1
22| AC07866| 1/4″ BLACK COIL HANDLE| 1
23| AC01298| 5″0 FRESH AIR INTAKE KIT| 1
24| PL75736| RIGHT OR LEFT DECORATIVE SIDE PANEL| 2
25| SE74167| DOOR HINGE REPLACEMENT KIT| 1
26| 30337| SQUARE HEAD SET SCREW 1/2-13 X 1-1/2′| 2
27| PL34052| LINER FIXATION BRACKET| 3
28| 29015| 4″ X 9″ X 1 1/4″ REFRACTORY BRICK| 12
29| 29010| 4 1/2″ X 9″ X 1 1/4″ REFRACTORY BRICK| 4
30| PL36031| 3 5/8′ X 9″ X 1 1/4″ REFRACTORY BRICK| 1
31| PL70516| SECONDARY AIR TUBE| 3
32| PL75747| 1.7 SERIES SECONDARY AIR TUBE| 1
33| 21586| 18 7/8″ X 9 1/2″ X 1 1/4″ VERMICULITE BAFFLE| 1
| Item| Description| Qty
---|---|---|---
34| PL65325| 32 X 50 FACEPLATE TOP| 1
35| PL65326| 32 X 50 FACEPLATE SIDE| 2
36| VBA1556| 34′ X 50′ LARGE FACEPLATE| 1
37| PL70587| FACEPLATE EXTENSION| 1
38| VBA1555| 29′ X 44′ REGULAR FACEPLATE| 1
39| PL65323| 29 X 44 FACEPLATE TOP| 1
40| PL65324| 29 X 44 FACEPLATE SIDE| 2
41| 44089| DOUBLE CAGE BLOWER 144 CFM 115V – 60Hz – 1.1A| 1
42| SE75737| BLOWER ASSEMBLY| 1
43| 60013| POWER CORD 96° X 18-3 type SJT (50 pcs per carton)| 1
44| 44028| CERAMIC THERMODISC F110-20F| 1
45| 44085| RHEOSTAT KNOB| 1
46| 44087| RHEOSTAT NUT| 1
47| 44080| RHEOSTAT WITHOUT NUT (MODEL KBMS-13BV)| 1
48| ACO5959| METALLIC BLACK STOVE PAINT – 342 g (12oz) AEROSOL| 1
49| SE46165| INSTRUCTION MANUAL KIT| 1
VENTIS LIMITED LIFETIME WARRANTY
The warranty of the manufacturer extends only to the original retail purchaser
and is not transferable. This warranty covers brand new products only, which
have not been altered, modified nor repaired since shipment from factory.
Proof of purchase (dated bill of sale), model name and serial number must be
supplied when making any warranty claim to your VENTIS dealer.
This warranty applies to normal residential use only. This warranty applies to
normal residential use only. This warranty is void if the unit is used to burn
material other than cordwood (for which the unit is not certified by EPA) and
void if not operated according to the owner’s manual. Damages caused by
misuse, abuse, improper installation, lack of maintenance, over firing,
negligence or accident during transportation, power failures, downdrafts,
venting problems or under-estimated heating area are not covered by this
warranty.
The recommended heated area for a given appliance is defined by the
manufacturer as its capacity to maintain a minimum acceptable temperature in
the designated area in case of a power failure.
This warranty does not cover any scratch, corrosion, distortion, or
discoloration. Any defect or damage caused by the use of unauthorized or other
than original parts voids this warranty. An authorized qualified technician
must perform the installation in accordance with the instructions supplied
with this product and all local and national building codes. Any service call
related to an improper installation is not covered by this warranty.
The manufacturer may require that defective products be returned or that
digital pictures be provided to support the claim. Returned products are to be
shipped prepaid to the manufacturer for investigation. Transportation fees to
ship the product back to the purchaser will be paid by the manufacturer.
Repair work covered by the warranty, executed at the purchaser’s domicile by
an authorized qualified technician requires the prior approval of the
manufacturer. All parts and labour costs covered by this warranty are limited
according to the table below.
The manufacturer, at its discretion, may decide to repair or replace any part
or unit after inspection and investigation of the defect. The manufacturer
may, at its discretion, fully discharge all obligations with respect to this
warranty by refunding the wholesale price of any warranted but defective
parts. The manufacturer shall, in no event, be responsible for any uncommon,
indirect, consequential damages of any nature, which are in excess of the
original purchase price of the product. A one-time replacement limit applies
to all parts benefiting from lifetime coverage. This warranty applies to
products purchased after March 1st , 2015.
DESCRIPTION | WARRANTY APPLICATION |
---|---|
PARTS | LABOUR |
Combustion chamber (welds only), castings and convector air-mate | Lifetime** |
4 years
Plating (defective manufacture) – subject to limitations above Ceramic glass
(thermal breakage only)| Lifetime| N/A
Stainless steel firebox components, vermiculite, C-Cast or equivalent baffle
and secondary air tubes, glass retainers and handle assembly| 5 years| 3
years
Surrounds and heat shields, ash drawer, steel legs, pedestal and trim
(aluminum extrusions)| 5 years| N/A
Carbon steel firebox components| 3 years| 2 years
Blowers, heat sensors, switches, rheostat, wiring and electronics| 2 years| 1
year
Paint (peeling*), gaskets, insulations, refractory bricks (fireplace only**)
and ceramic fibre blankets
N/A| 1 year|
All parts replaced under the warranty| 90 days| N/A
Labour cost and repair work to the account of the manufacturer are based on a
predetermined rate schedule and must not exceed the wholesale price of the
replacement part.
Shall your unit or a components be defective, contact immediately your VENTIS
dealer. To accelerate processing of your warranty claim, make sure to have on
hand the following information when calling:
- Your name, address and telephone number
- Bill of sale and dealer’s name
- Installation configuration
- Serial number and model name as indicated on the nameplate fixed to the back of your unit
- Nature of the defect and any relevant information
Before shipping your unit or defective component to our plant, you must obtain
an Authorization Number from your VENTIS dealer.
Any merchandise shipped to our plant without authorization will be refused
automatically and returned to sender.
This document is available for free download on the manufacturer’s website. It
is a copyrighted document.
Resale is strictly prohibited. The manufacturer may update this document from
time to time and cannot be responsiblefor problems, injuries, or damages
arising out of the use of information contained in any document obtained from
unauthorized sources.
Stove Builder International inc.
250, rue de Copenhague,
St-Augustin-de-Desmaures (Québec) Canada
G3A 2H3
1-877-356-6663
www.occanada.com
tech@occanada.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>