MITSUBISHI ELECTRIC 017 HiW Multi-Split Branch Box User Manual
- June 8, 2024
- Mitsubishi Electric
Table of Contents
017 HiW Multi-Split Branch Box
User Manual
017 HiW Multi-Split Branch Box
MXZ branch box systems require indoor units to be numerically addressed during
installation for the branch box to map the ports to an M-Net address.
One or two branch boxes may be connected to an outdoor unit at a time and come
in 3 and 5 port configurations. The maximum number of ports supported by the
outdoor unit is identified in the product nomenclature (MXZ-4C36NAHZ2,
MXZ-5C42NAHZ2, MXZ-8C48NAHZ2). Additional ports on the branch box will remain
inactive.
M-Net control via 2-core AWG 16 shielded wire is used between the outdoor unit
and branch box. Branch boxes use A-Control communication from the branch box
to indoor units.
M-Net system addressing is performed by setting of rotary switches at the
outdoor and branch box unit(s) and SW1 in branch box. Outdoor units use rotary
switches SWU2 and SWU1; SWU2 represents the 10’s digits and SWU1 the single
digits. Branch boxes use rotary switches SW12 and SW11; SW12 represents 10
digits and SW11 are single digits. Setting dip switches SW1 on the branch box
to ‘ON’ ena bles connectivity o f indoor units to branch box(es).
- The port A of branch box (A) has an address of ‘001’
- Rotate SW12 to ‘0’ and SW11 to ‘1’ for address ‘001’ for branch box (A)
- Three ports are enabled by SW1 , therefore turn dip switches SW1-1, SW1-2, and SW1-3 to ON position
- The first port of branch box (B) is addressed to ‘004’ because addresses ‘001’ to ‘003’ are assigned on branch box (A)
- Rotate SW12 to ‘0’ and SW11 to ‘4’ for address ‘004’ for branch box (B)
- Two ports are required on branch box (B) therefore turn switches SW1-1 and SW1-2 ON
- As branch box (A) is addressed ‘001’ add 50 to determine outdoor address ‘051’
- Outdoor unit: Rotate SWU2 to ‘5’ and SWU1 to ‘1’ for address ‘051’ for first outdoor unit
For more information on how to perform all functions listed in this document, visit www.mitsubishitechinfo.ca or email us at HowItWorks@mitsubishielectric.ca
MITSUBISHI ELECTRIC SALES CANADA INC. HVAC DIVISION
4299 141 Avenue. Matham. °nano L3R 0.12. Canada
Phone 905475.7728
Fax 905475-5231
HowItWorks@MitsubishiElectric.ca
Multi-Split Branch Box Addressing
November 24, 2022
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>