E13 607 94 Vadsbox Room Installation Guide

June 12, 2024
VADSBO

E13 607 94 Vadsbox Room Installation Guide
E13 607 94 Vadsbox Room

E number: E13 607 94
Art. number: V-42D0096-001Y

Ready-made Casambi box with connectors for 1-10 DALI or DALI-2 luminaires. Has TW (warm/cold white) and RGBW-support.

Installation

Warning!
High voltage. Risk of electric shock. Installation should only be performed by a qualified electrician. Make sure that the power supply is switched off before connecting.

Vadsbox is a junction box intended for the fitting of products such as dimmers, control modules and relays. Vadsbox is IP20 compliant and intended for placement in suspended ceilings or for surface mounting indoors.

Vadsbox is equipped with a 5-pole spring connector, which can be removed from the fitting if necessary. Vadsbox’s base plate includes brackets which, with the help of the included cable ties, allow for a universal fitting of products, as well as simple internal cable management and strain relief.

Open locking clips
To open the Vadsbox press a screwdriver against the locking clips on each long side, as per the picture below.
Open locking clips
Press

Dimensions

Dimension
Dimension

Technical data

Product name Vadsbox
Product number V-65L1602-001Y
E-number E14 383 97
Fitting Superficial
Material PC/ABS
Insulation class IP20
Dimensions LxWxD 170x125x38,5mm
Cable entry 16mm knock-outs, and multiple cut-out options
Working temperature -20 + 50°C
Weight 178g
Flame retardance V0
Approval CE

Cable entry options

knock-outs based on cable size in several places/Varies entradas
Cable entry optionscables/Entradas recordable para 2 cables conductors
Knock-Outs 16mm

Wall mounting

Wall mounting
Included

Examples of strain relief

Examples of strain relief
Included

Installation manual CBU-A2D

Warning!

High voltage. Risk of electric shock. The installation should only be carried out by an authorized electrician.

High voltage CBU-A2D is a Bluetooth controllable, Casaba enabled 2 channel 0-10V/ DALI controller. CBU-A2D has a universal 100-277 VAC input voltage range. CBU-A2D can control one or two 0-10V controllable LED drivers, or it can control a tunable white LED driver with two 0-10V control interfaces.
The product can also be configured into a DALI mode where it can be connected to a DALI LED driver or DALI sensor for presence and/or daylight harvesting functions.

CBU-A2D can be controlled with Casaba app which can be downloaded free of charge from Apple App Store and Google Play Store.

Different Casaba enabled products can be used from a simple one luminaire direct control to a complete and full fea-tured light control system where up to 250 units form automatically an intelligent mesh network.

Technical data

Label : CBU-A2D
Item number : V-42B0006-001
Input voltage :   100-240VAC (CE/UL/CSA) 277VAC (UL/CSA only)
Frequency : 50-60Hz
Max. mains current : 35mA
Output 1 voltage, 0-10V :   0-10VDC, max. 7 mA (sinking)
Output 1 voltage, DALI :   12VDC, max. 20 mA (sourcing)
Max. number of drivers :   1 driver + 1 sensor/push button
Output 2 voltage, 0-10V :   0-10 VDC, max. 7 mA (sinking)
Output 2 voltage, : relay
control :   12 VDC, max. 100 mA (sourcing)
Max. number of drivers :   1
Operating frequencies :   2,4…2,483 Ghz
Max. output power -4 : dBm
Ambient temperature, ta : 20…+45°C (-4…+113°F)
Max. case temperature, tc :   +70 °C (+158°F)
Storage temperature :   25…+70 °C (-13…+158°F)
Max. relative humidity :   0…80%, non-cond
Wire range, solid & stranded :  0,5-1,5 mm2 / 16-20 AWG
Wire strip length :   6-7 mm (.25”)
Tightening torque :   0,4 Nm/4 Kgf.cm/2,6 Lb-In
Dimensions : 76,0×26,0x23,0mm
Weight : 40g
Casing classification : IP20
Protection class : Built-in Class II
Certifications : CE

Dimensions

Dimension
Dimension
Dimension

Installation

Make sure that the mains voltage is switched off when making any connections. Use 0.5-1.5 mm2 solid or stranded conductor electrical wires. Strip the wire 6-7 mm from the end. Insert the wires into the corresponding holes and tighten the connector screws.

If the connected LED driver cannot be turned off completely from the control interface, an external relay with 12 VDC coil can be connected to channel 2. Make sure the relay is protected against flyback voltage, e.g. do not use a PCB relay without the flyback diode. A suitable fixture configuration must be selected in order to control a relay.

CBU-A2D, as any other Casambi product, should not be placed in a metal enclosure or next to large metal structures. Metal will effectively block radio signals which are crucial to the operation of the product. A thorough connectivity testing is strongly recommended in the installation site

Range

The range between two CBU-A2D units or between a CBU-A2D and a smart phone can vary a lot depending on obstacles and surrounding material. In open air the range between two CBU-A2Ds can be in excess of 200 ft, but if the unit is encapsulated into a metal structure, the range can be only few feet. Therefore, thorough testing is highly suggested.

Casambi uses mesh network technology so each CBU-A2D acts also as a repeater. When testing the network, it is important to test that each unit can be controlled from any point of the network covered area.

Wiring diagram, Push Button
Wiring diagram

Wiring diagram, 10 DALI drivers
Wiring diagram
Wiring diagram, DALI sensor
Wiring diagram
Wiring diagram, one driver and relay
Wiring diagram
Wiring diagram, two drivers (only 0-10V)
Wiring diagram

Visiting:
Phone:
+46 (0)31-23 56 00
E-mail:
info@vadsbo.net
order@vadsbo.net
E-mail:
info@vadsbo.net
order@vadsbo.net
Vadsbox Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals