Arrowhead Alarm AJ-718 Auto Resetting Heat Detector User Manual

June 12, 2024
Arrowhead Alarm

AJ-718
Auto Resetting Heat Detector
with Wireless Interconnect
V1.01OP

Specifications

Detection Type Electronic Thermistor Sensing
Fixed Temp. Trigger 57˚C
Operating Temp. Range 0  0˚C to 49˚C
Humidity 0 to 95% RH, no condensation or icing
Power Source Battery up to 10 year life
Buzzer Output 85db @ 3 meters
Wireless Frequency 433MHz
Interconnect Range up to 50 meters apart
Dimensions 45mm x Ø116mm
Compatible with AJ-765 Smoke Detector

AJ-R106 Remote Test & Hush Controller

Operation & Testing

Routine Testing of heat detectors should be done once a month.
To test the AJ-718 heat detectors press the test button for less than 1 second. The sounder should activate.
Any other linked detectors should also activate within 20 seconds.
The detectors sounder will automatically reset, when all the smoke has cleared.
Hush feature. When the heat detector has been activated, pressing the test button for less than 1 second will silence that smoke detectors sounder.
Indication:
Green Flash every 60 seconds, Detector is performing correctly
Red Flash every 8 seconds plus beep, Faulty, Clean/Replacement required
Red Flash every 50 seconds plus beep, Battery Low, Replacement required
Red Flashing with No beeping, in Hush mode for 9 minutes

**Routine cleaning is required to ensure no false triggers.

Mounting Clearances

Arrowhead Alarm AJ 718 Auto Resetting Heat Detector - Mounting
ClearancesArrowhead Alarm
AJ 718 Auto Resetting Heat Detector - Mounting Clearances
2*Always refer to latest standards/building code for mounting locations

Pairing AJ-718 Heat Detectors with Wireless Interconnect

Step 1.
Power On
Remove the back and plug the battery lead into the matching socket.
Note. AJ-718 heat detectors can also be paired with AJ-765 smoke detectors and AJ-R106 remote.

Step 2.
Clear Memory
Press & hold the test button until the Green light has flashed 4 times.
The Green light will then flash back 3 times slowly.
This must be done on all detectors before Pairing.

Step 3.
Select a Master
Press & hold the test button of the detector to be the master, until the Green light has flashed 3 times.
The Red light will then start flashing to indicate its in Pairing mode.
(60 seconds maximum)

Step 4.
Learn in a detector
Press & hold the test button of a slave detector, until the Green light has flashed 2 times.
The Red light will then start flashing as it tries to learn The Green light will flash 3 times to indicate it has paired.
Repeat Step 4, on all other detectors until they have been paired.Arrowhead
Alarm AJ 718 Auto Resetting Heat Detector - detectors Step 5.
Wait 60 second before testing

Step 6.
Testing
Press the test button (for less than 1 second) on one of the detectors.
Within 20 seconds all detectors paired together should also activate.
Note. The hush button can be pressed on each detector, without affecting the wireless interlink test.

ARROWHEAD ALARM PRODUCTS Ltd.
1A Emirali Road, Silverdale 0932.
Ph. 09 414 0085
www.aap.co.nz
v1.01