CANARM P Series Wall Mount Shutter Exhaust Fan Instruction Manual
- June 12, 2024
- CANARM
Table of Contents
AX & P SERIES EXHAUST FANS
OPERATION INSTRUCTIONS AND PARTS MANUAL
READ AND SAVE THESE INSTRUCTIONS
WARRANTY
CANARM Ltd. warrants every new fan to be free of defects in material and
workmanship, to the extent that, within a period of one year from the date of
purchase CANARM Ltd. shall either repair or replace at CANARM’s option, any
unit or part thereof, returned freight prepaid, and found to be defective.
This warranty does not include any labour or transportation costs incidental
to the removal and reinstallation of the unit at the user’s premises.
Components repaired or replaced are warranted through the remainder of the
original warranty period only.
This warranty applies to the original purchaser-user only; it is null and void
in case of alteration, accident, abuse, neglect, and operation not in
accordance with instructions.
NOTICE: No warranty claims will be honored by CANARM Ltd. unless prior authorization is obtained.
INSTALLATION OR PRODUCT PROBLEMS? DO NOT RETURN TO STORE OF PURCHASE. CONTACT CANARM SERVICE AT 1-800-265-1833 (CANADA) 1-800-267-4427 (U.S.A.) 1-800-567-2513 (EN FRANÇAIS) MONDAY TO FRIDAY 8:00 – 5:00PM E.S.T.
INSTRUCTION MANUAL FOR AX & P SERIES EXHAUST FANS
READ INSTRUCTIONS COMPLETELY BEFORE INSTALLATION & SAVE FOR REFERENCE
Congratulations on the purchase of your quality built direct drive, wall
exhaust ventilation fan. All of these models use totally enclosed motors with
thermal overload protection. Variable speed motors are high efficiency motors
which save on electrical costs and can be run as a single speed motor. The
motors are mounted on heavy gauge welded steel rod motor mounts that have a
Bright Zinc finish. 30″ fans and larger have powder coated guards. Fans come
fully assembled and 100% of fans are tested for proper operation before
shipping.
THESE ARE GENERAL INSTRUCTIONS WHICH COVER OUR SINGLE, VARIABLE AND TWO SPEED AX & P FANS, AS WELL AS OUR SINGLE SPEED EXPLOSION PROOF MODELS.
AX SERIES FANS:
These models have a rugged, sturdily constructed housing made from all aluminum extrusions. The louvers open automatically when the fan starts up and close when the fan stops.
MODEL| A X A
SQUARE| B| C
c/c
---|---|---|---
P| P-4~
P08| 13 1/4″| 6 1/2″| –| 12″
P10| 15 1/4″| 6 1/2″| –| 14″
P12| 17 1/4″| 11″| 13 3/4″| 16″
P14| 19 1/4″| 11″| 13 3/4″| 18″
P16| 21 1/4″| 11″| 13 3/4″| 20″
P18| 23 1/4″| 11 1/4″| 14″| 22″
P20| 25 1/4″| 11 1/4″| 14″| 24″
P24| 29 1/4″| 11″| 13 3/4″| 28″
P30| 35 1/4″| 13 1/4″| | 34″
P36| 41 1/4″| 13 1/2″| | 40″
P SERIES FANS:
The P Series is a sturdily constructed panel mounted exhaust fan made with a durable powder coated finish.
MODÈLE| A X A
SQUARE| B| C
c/c
---|---|---|---
P| P-4~
P08| 13 1/4″| 6 1/2″| –| 12″
P10| 15 1/4″| 6 1/2″| –| 14″
P12| 17 1/4″| 11″| 13 3/4″| 16″
P14| 19 1/4″| 11″| 13 3/4″| 18″
P16| 21 1/4″| 11″| 13 3/4″| 20″
P18| 23 1/4″| 11 1/4″| 14″| 22″
P20| 25 1/4″| 11 1/4″| 14| 24″
P24| 29 1/4″| 11″| 13 3/4″| 28″
P30| 35 1/4″| 13 1/4″| –| 34″
P36| 41 1/4″| 13 1/2″| –| 40″
AX & P SERIES EXHAUST FANS
Explosion proof fans are equipped with single speed explosion proof motors and aluminum blades so sparks cannot occur if a metal object obstructs the blade path. Explosion proof fans have the same quality housing panel and heavy gauge welded guard as the AX & P Fans. These fans should be used to ventilate hazardous areas. Locations are considered hazardous if the atmosphere contains or may contain gas, vapor, or dust in explosive quantities.
THE MOTOR AMBIENT TEMPERATURE IS NOT TO EXCEED +40°C OR -25°C UNLESS THE MOTOR NAMEPLATE SPECIFICALLY PERMITS ANOTHER VALUE. THE FOLLOWING TABLE INDICATES WHICH HAZARDOUS CLASSIFICATIONS CANARM EXPLOSION PROOF FANS DO AND DO NOT MEET.
Canarm explosion proof fans DO meet the following hazardous classifications.
CLASS 1, DIVISION 1 (GASES, VAPORS)
GROUP C Acetaldehyde, cyclopropane, diethlether, Ethylene, isoprene
GROUP D Acetone, acrylonitrile, ammonia, benzene, butane, ethylene
dichloride, gasoline, hexane, methane, methanol, naphtha, propane, propylene
styrene, toluene, vinyl, acetate, vinyl chloride, xylene
CLASS 2, DIVISION 1 (COMBUSTIBLE DUSTS)
GROUP F Carbon black, coke or coal dust
GROUP G Flour, starch or graindust
|
Canarm explosion proof fans DO NOT meet the following hazardous classifications.
CLASS 1, DIVISION 1 (GASES, VAPORS)
GROUP A Acetylene
GROUP B Butadiene, ethylene oxide, hydrogen, propylene oxide
CLASS 2, DIVISION 1 (COMBUSTIBLE DUSTS)
GROUP E Aluminum, magnesium and other metal dusts with similar
characteristics
---|---
INSTALLATION
Installation is fast and simple. A sturdy framed wall opening should be prepared in advance to the size indicated for your fan in the charts above. With lag bolts for wooden frames or nut, bolt and lock washers for steel frames, secure the fan using the four mounting holes provided, one in each corner of the fan.
ELECTRICAL CONNECTIONS
WARNING: BE SURE POWER IS OFF AT THE ELECTRICAL PANEL BEFORE WIRING.
WARNING: ALL ELECTRICAL WORK SHOULD BE PERFORMED BY A QUALIFIED
ELECTRICIAN.
These fans are supplied with single, two or variable speed motors. Single and
two speed motors are 120V only. Variable speed motors are dual voltage. All
dual voltage motors are pre-wired at 240V in our factory. Rewire motor as per
motor nameplate if running fan at 120V. Please see the motor nameplate for
wiring diagram. Make electrical connections in motor connection box as per the
motor nameplate. Follow Chart #1 for wire sizes. Two speed fans require a two
speed control or 3 position toggle switch to change from high/low/off. See
wiring diagram with control for 2 speed wiring instructions.
CHART#1
Table A Minimum Wire Sizes for Three-Phase Motors
Motor HP | 25 to 50 Feet | 100 Feet | 150 to 200 Feet |
---|---|---|---|
200V | 230V | 460V | 200V |
230V | 460V | ||
1/8 | 14(18)* | 14(18)* | 14(18)* |
14(18)
1/6| 14(18)| 14(18)| 14(18)| 14(18)| 14(18)| 14(18)| 14| 14(16)|
14(18)
1/4| 14(18)| 14(18)| 14(18)| 14(16)| 14(18)| 14(18)| 14| 14| 14(18)
1/3| 14(18)| 14(18)| 14(18)| 14(16)| 14(16)| 14(18)| 12| 14| 14(18)
1/2| 14(16)| 14(18)| 14(18)| 12| 14(16)| 14(18)| 10| 12| 14(18)
3/4| 14(16)| 14(16)| 14(18)| 12| 14| 14(18)| 10| 10| 14(16)
1| 14| 14(16)| 14(18)| 12| 12| 14(18)| 8| 10| 14(16)
11/2| 12| 14| 14(18)| 10| 10| 14(16)| 6| 8| 14
2| 12| 12| 14(18)| 8| 10| 14(16)| 6| 6| 12
3| 10| 12| 14(18)*| 6| 8| 14| 4| 6| 12
Table B Minimum Wire Sizes for Single-Phase Motors
Motor HP | 25 to 50 Feet | 100 Feet | 150 to 200 Feet |
---|---|---|---|
200V | 230V | 460V | 200V |
230V | 460V | ||
1/8 | 14(18)* | 14(18)* | 14 |
1/6 | 14(16)* | 14(18)* | 12 |
1/4 | 14 | 14(18)* | 10 |
1/3 | 14 | 14(18)* | 10 |
1/2 | 12 | 14(18)* | 8 |
3/4 | 10 | 14(16)* | 6 |
1 | 10 | 14(16)* | 6 |
1 1/2 | 8 | 14 | 6 |
2 | 6 | 14 | 4 |
3 | 6 | 12 | 3 |
NOTE:
- NEC Article 310-5 – *Minimum conductor size for general wiring at 115-440VAC is number 14AWG.
- Above wire sizes based on approximate 5% voltage drop during starting: copper conductors: and 75°C type THHW, THW, THWN, RH, RHW insulation etc. For aluminum wire, increase two wire size steps minimum. See NEC Article 310 for ampacities of aluminum conductors.
- Type S, SO, SJ, SJO, etc. flexible cable wire sizes. See NEC article 400 for ampacity.
If your unit contains the ECsmart Motor please follow these wiring diagrams:
OPERATION
WARNING: VARIABLE SPEED FANS SHOULD HAVE THE MINIMUM SPEED SET TO OPEN
LOUVERS AT LEAST ONE INCH FOR PROPER MOTOR COOLING AND TO PREVENT MOTOR
FAILURE.
All fans are direct drive. Fans with variable speed motors can be operated as
an energy efficient single speed fan or in variable operation with the proper
controller. As mentioned above two speed fans require a two speed control or 3
position toggle switch to change from high speed to low and off.
WARNING: GUARDING SHOULD BE USED IF FANS ARE MOUNTED LOWER THAN SEVEN FEET (2 METRES) OFF FLOOR OR GROUND LEVEL.
ACCESSORIES
Canarm provides a complete line of manual and thermostatic controls. Canarm also offers wall mount exhaust shutter kits, replacement shutter sets, and weather protection hoods.
MAINTENANCE
MOTORS ARE EQUIPPED WITH AUTOMATIC OVERLOAD PROTECTION AND MAY RESTART WITHOUT WARNING. ALWAYS DISCONNECT FROM POWER BEFORE ATTEMPTING SERVICE. Motor, blade and louvers should be kept clean of any buildup to prevent premature motor failure and to achieve proper performance. Automatic louvers should be kept operating freely. As with all mechanical equipment scheduled inspections should include checking that all hardware is secure and blade set screws are tight.
Canarm Ltd. – Corporate Head Office
2157 Parkedale Avenue, PO Box 367 Brockville, Ontario Canada K6V 5V6
Tel: 613-342-5424; Fax:
613-342-8437
www.canarm.com
hvacsales@canarm.ca
AX & P_EXHAUST FANS_M_M0111