novus N1040T Time and Temperature Controller Owner’s Manual
- June 12, 2024
- Novus
Table of Contents
N1040T Controller
TIME AND TEMPERATURE CONTROLLER – USER GUIDE – V2.1x N
SAFETY ALERTS
The following symbols are used on the equipment and throughout this manual to draw the user’s attention to important information related to the safety and use of the equipment.
****|
---|---
CAUTION:
Read the manual completely before installing and operating the equipment.|
CAUTION OR HAZARD:
Risk of electric shock.
All safety recommendations appearing in this manual must be followed to ensure
personal safety and prevent damage to the instrument or system. If the
instrument is used in a manner other than that specified in this manual, the
device safety protections may
not be effective.
INSTALLATION / CONNECTIONS
The controller should be attached to a panel, following the sequence of steps below:
- Make a panel cutout, as shown in the SPECIFICATIONS section.
- Remove the mounting clamp from the controller.
- Insert the controller into the panel cutout.
- Reattach the mounting clamp on the controller, pressing until a firm hold is obtained.
ELECTRICAL CONNECTIONS
The layout of the features on the back panel of the controller is shown in
Figure 1:
INSTALLATION RECOMMENDATIONS
- Input signal conductors must run through the plant separately from the supply and output conductors. If possible, in grounded conduits.
- The power supply for the electronic instruments must come from a proper instrumentation network.
- It is essential to use RC FILTERS (noise suppressors) at contactor coils, solenoids, etc.
- In control applications, it is essential to consider what can happen when any part of the system fails. The internal devices of the equipment do not guarantee full protection.
FEATURES
SIGNAL INPUT
The input type to be used must be defined during equipment configuration.
Table 1 shows the available input options:
TYPE | MEASUREMENT RANGE | |
---|---|---|
Thermocouple J | Range: -110 to 950 °C (-166 to 1742 °F) | |
Thermocouple K | Range: -150 to 1370 °C (-238 to 2498 °F) | |
Thermocouple T | Range: -160 to 400 °C (-256 to 752 °F) | |
Pt100 | Range: -200 to 850 °C (-328 to 1562 °F) |
Table 1 – Input type
DIGITAL INPUT (DIG IN)
Available at terminals 15 and 16 on the back panel. It recognizes the closure
of Dry Contact switches.
The A3 flag indicates the Digital Input condition:
On = DI enabled (closed).
Off = DI disabled (open).
OUTPUTS
The controller has 2 or 4 output channels, according to the model ordered.
These channels must be configured to operate as Control Output, T1 Timer
Output, T2 Timer Output, or Alarm 4 Output.
OUTPUT 1 Voltage pulse output type, 5 Vdc / 50 mA max.
Available at terminals 4 and 5.
OUTPUT 2 SPST-NO Relay. Available at terminals 6 and 7.
OUTPUT 3 SPST-NO Relay. Available at terminals 13 and 14.
OUTPUT 4 SPDT Relay. Available at terminals 10, 11, and 12.
TEMPERATURE CONTROL OUTPUT
The process control output can operate in the following modes: 1) ON/OFF Mode
or 2) PID Mode.
To operate in ON/OFF Mode, you must set the PB parameter to 0.0.
The values of the PID parameters can be set automatically with the Auto-tuning
function (ATvN).
ALARM OUTPUT
The controller has an alarm, which can be directed to any output channel and
can operate with one of the functions described in Table 2:
| Alarm off.
---|---
| Absolute Minimum Value Alarm.
It triggers when the PV
(temperature) value is below the value set by the Alarm Setpoint (SPA4).|
| Absolute Maximum Value Alarm.
It triggers when the PV value is above the value set by the Alarm Setpoint.|
| Differential Value Alarm.
In this function, the SPFN parameter represents a difference between PV and
control SP.
|
Positive SPA4| Negative SPA4
| Minimum Differential Value Alarm.
It triggers when the PV value is below the point set by SP-SPA4 (using alarm 1
as an example).
|
Positive SPA4| Negative SPA4
| Maximum Differential Value Alarm.
It triggers when the PV value is above the point set by SP+SPA4.
|
Positive SPA4| Negative SPA4
| Open Sensor Alarms (Sensor Break Alarm).
It operates when the input presents problems such as a broken sensor, poorly
connected sensor, etc.
Table 2 – Alarm functions
Important note: Alarms configured with functions diff, and diffk will also
trigger the related output when the controller identifies and signals a sensor
failure. A relay type output configured to act as a Maximum Alarm ( ), for
example, will act when the SPAL value is exceeded and when the sensor
connected to the controller input is broken.
ALARM INITIAL BLOCK
The Initial Block feature inhibits the alarm from being activated if an alarm
condition exists in the process when the controller goes into operation. The
alarm will only be enabled after the process has passed a non-alarm condition.
This function is useful, for example, at the beginning of the process control
operation. At this point, the PV value is still far from the value set with
SP. Thus, alarm situations are expected and often their signaling is unwanted.
The Initial Block is not valid for the**IErr**
function (Open Sensor).
OFFSET
Feature that allows you to make small adjustments to the PV indication. It
allows you to correct measurement errors that appear, for example, when
replacing a temperature sensor.
LOOP BREAK DETECTION FUNCTION
The parameter sets a maximum time interval, in minutes, for PV to react to the
command from the control output. If there is not a minimal and proper reaction
throughout this interval, the controller will signal the occurrence of a LBD
event on its display. This indicates problems in the control loop.
If you set the parameter to 0 (zero), this function is disabled. This function
allows you to detect problems in the installation, such as a bad actuator or a
failure in the power supply process to the load.
SAFE OUTPUT FUNCTION DURING SENSOR FAILURE
Function that puts the control output into a safe condition for the process
when identifying an error in the sensor input.
When identifying a sensor failure, the controller will set the percentage
value (set in parameter) for the control output. The controller will remain in
this condition until the sensor failure disappears.
When in ON/OFF Mode, the values for are only 0 and 100 %.
When in PID Mode, any values between 0 and 100 % are accepted.
USB INTERFACE
The USB interface is used to CONFIGURE, MONITOR, or UPDATE the FIRMWARE. To do
this, you must use QuickTune software, which offers features to create, view,
save, and open configurations from the device or from files on your computer.
The feature to save and open configurations in files allows you to transfer
configurations between devices and create backups.
For specific models, QuickTune allows you to upgrade the firmware (internal
software) of the controller via USB interface.
To MONITOR, you can use any supervisory (SCADA) or laboratory software that
supports Modbus RTU communication over a serial communication port.
When connected to the USB interface of a computer, the controller will be
recognized as a conventional serial port (COM x).
You should use QuickTune software or consult the Device Manager in the Windows
Control Panel to identify the COM port assigned to the device.
Refer to the Modbus memory mapping in the device communication manual and the
supervisory software documentation.
To use the USB communication, follow the steps below:
- Download QuickTune software, free of charge, from our website and install it on the computer to be used. The USB drivers required for the operation of the communication will be installed with the software.
- Connect the USB cable between the device and the computer. The controller does not need to be powered. The USB interface will provide enough power for the communication to operate (other device functions may not operate).
- Run QuickTune, configure the communication, and start the device recognition.
| The USB interface IS NOT ISOLATED from the signal input (INPUT) and possible
digital inputs and outputs of the controller. Its purpose is
temporary use during CONFIGURATION and MONITORING periods.
For the safety of people and equipment, it should only be used when the
equipment is fully disconnected from the input/output signals.
The USB interface can be used in any other situation, but it requires careful
consideration by the people performing the installation.
For MONITORING over long periods and with the inputs and outputs connected, it
is recommended to use the RS485 interface, available or optional in most of
our devices.
---|---
TIMERS
The controller has 2 timers, which can operate independently of the
temperature control.
T1 TIMER
T1 is the main timer. It has several features that provide different modes of
operation.
T1 TIMER − STARTUP MODES
T1 Timer has 4 trigger modes:
RUN Allows you to start time counting when activating control ( ).
SP Allows you to start time counting when the PV value reaches the SP value
set for the process.
F Allows you to start time counting by using the key.
Once the timing has started, pressing the key again will interrupt the
process.
To start a new cycle, press the key again.
DI Allows you to start time counting via Digital Input. When you trigger the
DI (close contact), the time counting will start.
If the DI is disabled (open contact) before the end of the timer, it will be
interrupted.
Returning to DI will start a new cycle.
Note: If you manually set the parameter to NO (control disabled), the
triggering options key and DI will not allow you to re-enable control ( ).
T1 TIMER − OPERATION MODES
T1 Timer has 3 operation modes: off T1 output turns off at the end of T1.
In this mode, T1 output turns on at the beginning of T1 and turns off at the
end of T1.
The A1 flag turns on at the beginning of the timer and flashes after the end
of the T1 interval.
T1 output turns on at the end of T1.
When T1 timer starts, the T1 output remains off. At the end of the timer, T1
output is turned on and will remain in this condition until a new cycle
starts.
The A1 flag flashes during the timing of T1. After T1, it N1040T Controller
turns on permanently, signaling that the output is still on.
On.x T1 output remains on at the end of T1.
The T1 output is switched on at the beginning of T1 timer and remains in this
condition even at the end of the timing.
The A1 flag turns on during the timing of T1. After T1, it starts flashing,
signaling that the output is still on.
The operation modes define the behavior of the outputs linked to the timer.
You can link to any available output: OUT1, OUT2, OUT3, or OUT4.
The A1 flag indicates the current stage of the timer.
T2 TIMER
Secondary timer. It starts its timing at the end of T1. It can also be linked
to any available output on the controller. The linked output always turns on
at the beginning of T2 and turns off at the end.
The A2 flag indicates the condition of timing T2:
T2 in progress → A2 on.
T2 not started or already finished → A2 off.
TIMING DIRECTION
The time counting for the timers can occur in 2 modes: 1) Increasing Mode or
2) Decreasing Mode.
In Increasing Mode (UP), counting starts at 0 and goes up to the programmed
time interval (T1, T2)
In Decreasing Mode (DOWN), it starts at the programmed time value and goes
down to 0.
BEHAVIOR OF THE TEMPERATURE CONTROL AT THE END OF THE TIMER
During the timing intervals of T1 and T2, the temperature control has normal
operation.
The output defined as Temperature Control acts to bring the PV value to the
value set in SP. However, at the end of the T1 + T2 interval, it is possible
to configure the controller to disable temperature control, setting the
parameter to NO. See .(.0 Parameter (Timer Cycle).
TIMER TIME BASE
The TBAS parameter (Timer Cycle) allows you to set the time base to be used.
The options are:
MM:SS. The time intervals T1 and T2 are shown in minutes and seconds.
HH:MM. The time intervals T1 and T2 are shown in hours and minutes.
OPERATION
The front panel of the controller can be seen in Figure 2:
Display: Displays the measured variable, configuration parameter symbols, and
their respective values/conditions.
TUNE flag: Remains on while the controller is in the tuning process.
RUN flag: Indicates that the controller is in operation.
OUT flag: Indicates the status of the temperature control output.
A1 flag: Indicates the status of the output linked to T1.
A2 flag: Indicates the status of the output linked to T2.
A3 flag: Indicates the Digital Input condition.
A4 flag: Indicates the Alarm 4 condition.
Key: Key used to advance to successive parameters and parameter cycles.
Increment Key and Decrement Key: Keys used to change parameter values.
Key: Key used to move back parameters during configuration.
STARTUP
When powered up, the controller displays its software version number for the
first 3 seconds. After that, it will show the measured process variable (PV)
value (temperature) in the upper display and the SP value in the lower
display. This is the Indication Screen.
To be used in a process, you need to configure the controller. To configure
it, you must define each of its parameters.
The configuration parameters are gathered into affinity groups, called
parameter cycles:
Operation / Tuning / Timer / Alarms / Input / Calibration
The key gives access to the cycles and their parameters.
By holding down the key, the controller jumps from one cycle to another every
2 seconds, displaying the first parameter of each cycle:
To enter the desired cycle, simply release the key when its first
parameter is displayed. To advance through the parameters of this cycle, press
the key with short touches.
At the end of each cycle, the controller will return to the Indication Screen.
The symbol for each parameter will be shown in the upper display while its
respective value/condition will be shown in the lower display.
PARAMETER DESCRIPTION
OPERATION CYCLE
PV + SP| PV Indication Screen.
The value of the measured variable (PV) temperature is shown in the upper
display (red).
The control Setpoint value (SP) is shown in the lower display (green).
---|---
PV + TM| PV Indication screen and elapsed time.
The upper display (red) shows the measured temperature value (PV).
The lower display (green) shows the countdown of the time interval set for T1
Time.
You cannot adjust this screen.
Timer 1| Allows you to set the T1 Time interval.
Adjustable between 00:00 and 99:59 (HH:MM or MM:SS).
This parameter will be displayed in this cycle when defined in T.en parameter.
| Alarm SP. Allows you to define the actuation point of the alarm outputs.
For alarms programmed with Differential type functions, these parameters set
deviations.
This parameter will be displayed in this cycle when defined in sp4 parameter.
| Allows you to enable or disable the controller’s action on the process. It
acts as a switch, turning the controller on or off.
YES Enabled outputs.
NO Disabled outputs.
This parameter will be displayed in this cycle when defined in rvn.e
parameter.
TUNING CYCLE
Auto-tuning| AUTO-TUNING. Allows you to enable the automatic tuning of the PID
parameters ( ).
Auto-tuning is off.
Perform tuning in Fast Mode.
Perform tuning in Accurate Mode.
See SETTING THE PID PARAMETERS chapter.
---|---
Proportiona Band| Proportional Band. Value of the P term of the PID control
mode. In percent of the maximum range of the input type.
Adjustable between 0 and 500.0 %.
When set to 0.0 (zero), it defines ON/OFF control mode.
Integral Rate
| Integral Rate. Value of the I term of the PID control mode. In repetitions
per minute (Reset).
Adjustable between 0 and 24.00.
Displayed only if proportional band ≠ 0.
Integral Rate| Integral Rate. Value of the I term of the PID control mode. In
repetitions per minute (Reset).
Adjustable between 0 and 24.00.
Displayed only if proportional band ≠ 0.
Derivative
Time| Derivative Time. Value of the D term of the PID control mode. In
seconds.
Adjustable between 0 and 250 seconds.
Displayed only if proportional band ≠ 0.
| PWM Cycle Time. Value of the PWM Cycle period of the PID control. In
seconds.
Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band ≠ 0.
Hysteresis| Control hysteresis. Hysteresis value for ON/OFF control.
Adjustable between 0 and the measurement range width of the selected input
type.
Displayed if proportional band Pb = 0.
Action| Allows you to set the control logic:
Reverse Action control. Suitable for
heating. Turns on the control output when PV is below SP.
Direct Action control. Suitable for refrigeration. Turns on the control output
when PV is above SP.
Soft Start| Soft Start Function. Allows you to set the time interval during
which the controller will limit the control output (MV) rise speed.
Adjustable between 0 and 9999 s.
The value zero (0) disables the Soft Start function.
| Allows you to set the operation mode of the OUT1,
OUT2, OUT3, and OUT4 output channels:
Not used.
It acts as temperature control.
It acts as an Alarm 4 output.
It acts as a LBD function output.
It acts as a T1 Timer output.
It acts as a T2 Timer output.
TIMER CYCLE
Timer 1| Allows you to set the T1 Time interval.
Adjustable between 00:00 and 99:59 (HH:MM orMM:SS).
---|---
Timer Enable| Allows you to display the T1 Time parameter (T1) also in the
Operation Cycle.
Enables T1 to be displayed in the Operation Cycle.
DOES NOT enable T1 to be displayed in the Operation Cycle.
| Allows you to set the timing direction of T1.
Progressive counting, starting from 0.
Countdown.
Timer Start| Allows you to set the T1 timer startup mode.
The DI starts and resets the timer.
key starts, stops, and resets the timer.
It starts when PV reaches SP.
It starts when you enable control ( = ).
Timer End| Allows you to set the behavior of the T1 output at the end of T1
timer.
output turns off at the end of T1.
output turns on at the end of T1.
output remains on at the end of T1.
Timer End Control Off| Allows you to set the temperature control behavior at
the end of the T1 + T2 timers. yes
Finishes control at the end of the timer ( = no).
The temperature control continues to operate.
Timer 2| Allows you to set the T2 Time interval.
Adjustable between 00:00 and 99:59 (HH:MM or MM:SS).
Time interval where the T2 output will remain on after the end of T1 timer.
time base| Allows you to set the time base for T1 and T2 timers.
Min Hours and minutes (HH:MM).
Minutes and seconds (MM:SS).
ALARM CYCLE
Function
Alarm| Allows you to set the alarm functions according to the options in Table
2.
---|---
| Alarm SP. Value that defines the actuation point of the alarm output.
For Differential type functions, this parameter defines the deviations between
PV and SP.
This parameter is not used for the alarm function.
| SP Enable. Allows you to display the parameter in the Operation Cycle.
Displays the parameter in the Operation Cycle.
NO DOES NOT display the parameter in the Operation Cycle.
Blocking
Alarm| Alarm 4 − Initial Block.
Enables the Initial Block.
NO DOES NOT enable the Initial Block.
Hysteresis of Alarm| Alarm hysteresis. Allows you to set the difference
between the PV value at which the alarm is turned on
and the value at which it is turned off.
Flas| Allows you to indicate the occurrence of alarm conditions by flashing
the PV indication on the indication screen.
Enables the alarm signaling by PV flashing.
DOES NOT enable the alarm signaling by PV flashing.
INPUT CYCLE
Type| Allows you to define the input type to be used.
J -110 to 950 °C / -166 to 1742 °F
K -150 to 1370 °C / -238 to 2498 °F
T -160 to 400 °C / -256 to 752 °F
Pt100 -200 to 850 °C / -328 to 1562 °F
---|---
Filter| Input digital filter.
Used to improve the stability of the measured signal (PV).
Adjustable between 0 and 20. At 0, it means the filter is off. At 20, it means
the filter is at maximum.
The higher the filter value, the slower the response of the measured value.
Decimal Point| Allows you to set the display mode of the decimal point.
Unit| Allows you to set the temperature unit to be used:
°f Fahrenheit.
°( Celsius.
Offset| Allows you to make corrections to the indicated PV value.
SP Low Limit| Allows you to set the lower limit to adjust SP.
SP High Limit| Allows you to set the upper limit to adjust SP.
Loop break
detection time| Time interval for the LBD function.
Maximum time interval for the PV to react to control output commands. In
minutes.
| Percentage value to be applied to the output when occurs a failure in the
sensor connected to the controller input.
CALIBRATION CYCLE
All input types are factory calibrated. When a recalibration is necessary, it
must be performed by a specialized professional.
If you access this cycle by accident, do not change its parameters.
Password| Password field. This parameter is displayed before the protected
cycles.
See CONFIGURATION PROTECTION chapter.
---|---
Calibration| Allows you to enable the controller calibration.
When not enabled, the corresponding parameters are hidden.
Input Low
Calibration| Declaration of the range start calibration signal applied to the
analog input.
Input High
Calibration| Declaration of the range end calibration signal applied to the
analog input.
Restore| Allows you to restore the factory calibrations.
Cold Junction| Cold junction temperature.
Password
Change| Allows you to set a new password, which must not be 0.
Protection| Allows you to set the Protection Level. See Table 3.
RUN Enable| Allows you to display the RUN (rvn) parameter also in the
Operation Cycle.
Yes Displays RUN in the Operation Cycle.
no DOES NOT display RUN in the Operation Cycle.
Run| Allows you to enable or disable the controller’s action on the process.
It acts as a switch, turning the controller on or off.
Yes Enables outputs.
no Disables outputs.
Serial
Number| It displays the last 4 digits of the electronic serial number of the
controller.
Serial
Number| It displays the last 4 digits of the electronic serialnumber of the
controller.
CONFIGURATION PROTECTION
The controller allows you to protect your configuration and prevent undue
changes.
In the Calibration Cycle, the Protection parameter ( ) defines the protection
level to be adopted, limiting access to the cycles, as shown in Table 3:
PROTECTION LEVEL | PROTECTED CYCLES |
---|---|
1 | Only the Calibration cycle is protected. |
2 | The Input and Calibration cycles are protected. |
3 | The Alarm, Input, and Calibration cycles are protected. |
4 | The Timer, Alarm, Input, and Calibration cycles are protected. |
5 | The Tuning, Timer, Alarm, Input, and Calibration cycles are protected. |
6 | All cycles, except the SP screen in the Operation Cycle, are protected. |
7 | All cycles are protected. |
Table 3 – Configuration Protection Levels
PASSWORD
When accessing the protected cycles, you will need to enter the password to be
able to change they configuration.
You must enter the password in the PASS parameter, the first parameter of the
protected cycles. Without it, the parameters of the protected cycles can only
be viewed.
The password is set in the Password Change parameter (PAS.(), presented in the
Calibration Cycle.
The controller is supplied with the Access Password set to 1111.
PASSWORD PROTECTION
The controller has a safety system. It helps prevent the input of several
passwords in an attempt to get the correct password right.
Once 5 consecutive invalid passwords are identified, the controller will stop
accepting passwords for 10 minutes.
MASTER PASSWORD
If you forget your password, you can use the Master Password feature. When
inserted, this password allows you to change the Password Change parameter
(PAS.() and set a new password for the controller.
The master password is composed of the last three digits of the controller’s
serial number plus the number 9000.
For a device with serial number 07154321, for example, the master password is
9 3 2 1.
You can obtain the serial number of the controller by pressing for 5 seconds.
SETTING THE PID PARAMETERS
During automatic tuning, the process is controlled in ON/OFF mode at the
programmed Setpoint (SP).
In some processes, automatic tuning can take many minutes to complete.
The recommended procedure for running it is:
- Set the desired SP value for the process.
- In the Atvn screen, enable automatic tuning by selecting between FAST or FULL options.
The FAST option performs the tuning in the shortest possible time.
The FULL option prioritizes more precise tuning.
During automatic tuning, the TUNE flag will remain lit on the front of the
controller. You must wait until the tuning process is finished before you can
use the controller.
During the Auto-tuning, PV oscillations can be induced in the process around
the Setpoint.
If the tuning does not result in satisfactory control, Table 5 gives
guidelines for correcting the process behavior:
PARAMETER | PROBLEM DISCOVERED | SOLUTION |
---|---|---|
Proportional Band | Slow response | Decrease |
Great oscillation | Increase | |
Integration Rate | Slow response | Increase |
Great oscillation | Decrease | |
Derivative Time | Slow response or instability | Decrease |
Great oscillation | Increase |
Table 4 – Manual adjustment of the PID parameters
For more details, check
www.novusautomation.com.
MAINTENANCE
PROBLEMS WITH THE CONTROLLER
Connection errors and improper programming are the most common errors during
controller operation. A final review can avoid wasted time and damage.
The controller displays some messages that are intended to help you identify
problems:
MESSAGE | PROBLEM DESCRIPTION |
---|---|
—- | Open Input. No sensor or signal. |
Connection and/or configuration problems. |
Review the connections and the configuration.
Table 5 – Error messages
Other error messages shown by the controller represent internal damage that
necessarily implies sending the equipment for maintenance.
INPUT CALIBRATION
All controller input types leave the factory already calibrated, and
recalibration is not recommended for inexperienced operators.
If you need to recalibrate an input, proceed as described below:
a) In the type parameter, set the input type to be calibrated.
b) Configure the lower and upper SP limits for the maximum span of the input
type.
c) Access the Calibration Cycle.
d) Enter the password.
e) Enable the calibration when setting the parameter to YES.
f) Using an electrical signal simulator, apply to the input terminals a signal
level close to the lower limit of the configured input range.
g) In the inL( parameter, use the and keys to adjust the display reading such
as to match the applied signal. Then press .
h) Apply a signal near the upper limit of the configured input’s measurement
range to the input terminals.
i) In the parameter, use the and keys to adjust the display reading such as to
match the applied signal. Then press until you return to the PV Indication
Screen.
j) Confirm the calibration done.
Note: When checking the controller, make sure that the Pt100 excitation
current required by the calibrator used is compatible with the Pt100
excitation current used in this instrument: 0.170 mA.
SPECIFICATIONS
DIMENSIONS:…………………………………… 48 x 48 x 80 mm (1/16 DIN)
Panel cut-out: …………………………. 45.5 x 45.5 mm (+0.5 -0.0 mm)
Approximated weight: ……………………………………………………..75 g
POWER SUPPLY:
…………………. 100 to 240 Vac (50/60 Hz) / 48 to 240 Vcc / ±10 %
Optional 24 V ………………… 12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Maximum consumption: ……………………………………………….. 6 VA
ENVIRONMENTAL CONDITIONS:
Operating temperature: ………………………………………… 0 to 50 °C
Relative humidity: …………………………………………… 80 % @ 30 °C
(For temperatures above 30 °C (86 °F), reduce by 3 % for each °C)
Installation category II, Installation degree 2; Altitude < 2000 m
INPUT:
Accepted types: ……………………………………………….. J, K, T, Pt100
Internal resolution: ………………………………… 32767 levels (15 bits)
Display resolution: ………………………………………… 0.1 / 1 (°C / °F)
Input reading rate: ……………………………… up to 10 per second ().
Accuracy: …. J, K, T Thermocouples: 0.25 % of the span ±0.1 °C
………………………………………….. Pt100: 0.2 % of the span ±0.1 °C
Input impedance: ……………………………………………………… 4.5 mΩ
Pt100 measurement: ……………………….. 3-wire type, (α=0.00385)
With cable length compensation, excitation current of 0.170 mA.
() Value adopted when the Digital Filter parameter is set to 0.
For Digital Filter values other than 0, the Input Reading Rate value is 5
samples per second.
DIGITAL INPUT (DIG IN) …………….. Dry contact / NPN collector-open
OUTPUT 1:…………………………………. Voltage pulse, 5 V / 50 mA max.
OUTPUT 2:…………………………. SPST Relay; 1.5 A / 240 Vac / 30 Vdc
OUTPUT 3:…………………………. SPST Relay; 1.5 A / 240 Vac / 30 Vdc
OUTPUT 4:…………………………… SPDT Relay / 3 A / 240 Vac / 30 Vdc
FRONT PANEL: ……………………. IP65, Polycarbonate (PC) UL94 V-2
HOUSING: ……………………………………………. IP30, ABS+PC UL94 V-0
CONNECTIONS SUITABLE FOR PIN TYPE TERMINALS.
PROGRAMMABLE PWM CYCLE FROM 0.5 TO 100 SECONDS.
IT STARTS OPERATION 3 SECONDS AFTER BEING CONNECTED TO THE POWER SUPPLY.
CERTIFICATIONS: CE, UKCA, and UL.
IDENTIFICATION
N1040T-PRRR| Standard model.
Power Supply 100~240 Vac / 48~240 Vdc
---|---
N1040T-PRRR-24V| Model with power supply 12~24 Vdc / 24 Vac
WARRANTY
Warranty conditions are available on our website www.novusautomation.com/warranty.