S S REGELTECHNIK THERMASGARD RTM Room Temperature Measuring Transducers Instruction Manual
- June 12, 2024
- S S REGELTECHNIK
Table of Contents
- S S REGELTECHNIK THERMASGARD RTM Room Temperature Measuring Transducers
- Product Usage Instructions
- Dimensional drawing
- THERMASGARD® RTM
- TECHNICAL DATA
- Measuring transducers, calibrateable, with active output
- Installation and Commissioning
- General notes
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
S S REGELTECHNIK THERMASGARD RTM Room Temperature Measuring Transducers
Product Information
- Product Name: Room temperature measuring transducers
- Model: RTM 1 – Display Type: LCD (optional)
- Sensor Type: Pt1000 – Sensor Class: B (according to DIN EN 60751) – Measuring Ranges: 0 – 10 V or 4…20 mA – Connection Type: 2- or 3-wire connection – Power Supply:
- DC: 24 V
- AC: 24 V
- Working Resistance: Ra (ohm) = (Ub – 14 V) / 0.02 A for I variant, RL > 5 kOhm for U variant – Power Consumption:
- < 1.0 W / 24 V DC
- < 2.2 VA / 24 V AC
- Ambient Temperature Range: ~ -25°C to ~ 85°C
- Housing Material: Plastic (ABS), color pure white (similar to RAL 9010) or optional stainless steel (V2A)
- Dimensions:
- Baldur 1: 85 x 85 x 27 mm (B x H x D)
- Stainless Steel: 75 x 75 x 25 mm (B x H x D)
- Electrical Connection: Screw terminals
- Humidity Range: < 95% r.H., non-condensing air
- Protection Class: III (according to EN 60 730)
- Protection Type: IP 30 (according to EN 60 529)
- Standards: CE conformity, electromagnetic compatibility according to EN 61326, according to EMC directive 2014 / 30 / EU
- Optional Feature: Two-line display with illumination for displaying the actual temperature and internal diagnostics (sensor breakage, sensor short circuit)
Product Usage Instructions
Power Supply Connection
- Ensure correct wiring according to the provided diagrams.
- For Single Operation: Connect the power supply with AC 24V~ or DC 15-36V to GND.
- For Parallel Operation: Connect two power supplies with AC 24V~ or DC 15-36V to GND. – For 0-10V
- Output: Connect the output signal wire to 0-10V and the ground wire to 0V/GND. – For 4…20 mA
- Output: Connect the output signal wire to 4…20 mA and the ground wire to 0V/GND.
Mounting and Installation
- Before mounting and installation, read the provided instructions and follow all the mentioned guidelines.
- Use screws to secure the transducer in place. The process connection can be made by screws.
- Ensure proper electrical connection using the screw terminals.
Usage Guidelines
- The transducer is calibratable and can measure room temperature within the specified ranges.
- The output can be either 0 – 10 V or 4…20 mA, depending on the selected model.
- The two-line display (optional) can show the actual temperature and internal diagnostics, including sensor breakage and sensor short circuit.
- The transducer is suitable for use in environments with humidity below 95% r.H., without condensation.
- It has a protection class of III and protection type of IP 30, ensuring suitable protection against external factors.
- The transducer complies with CE conformity and electromagnetic compatibility standards.
Note: For further information or additional measurement range options, refer to the product manual or contact customer support. Please make sure to refer to the original user manual for complete and accurate information regarding your specific product model.
Operating Instructions, Mounting & Installation
Room temperature measuring transducers, calibratable, with multi-range
switching and active output
Dimensional drawing
Housing Baldur 1
Housing stainless steel
THERMASGARD® RTM
Calibratable room temperature measuring transducer THERMASGARD® RTM 1 with continuous output, with or without optional display for displaying the actual temperature in an elegant housing made of plastic, with snap-on lid, base with 4-hole attachment for installation on verti-cally or horizontally installed in-wall flush boxes, with predetermined breaking point for on-wall cable entry, or in housing made of stainless steel (top and bottom part are of stainless steel, the lid is screwed on), vandal-proof version e.g. for schools, military barracks, and public buildings. This room temperature transmitter ⁄ residential room temperature sensor is used to detect ⁄ display temperatures in closed dry rooms, in apartments, in offices, supermarkets and business facilities.
TECHNICAL DATA
- Power supply: 24 V AC ⁄ DC (± 10 %) for U variant 15…36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
- Working resistance: Ra (ohm) = (Ub -14 V) ⁄ 0.02 A for I variant
- Load resistance: RL > 5 kOhm for U variant
- Power consumption: < 1.0 W ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
- Sensor: Pt1000, DIN EN 60751, class B
- Measuring ranges: multi-range switching with 8 switchable measuring ranges, see table (other ranges optional) operating range –30…+70 °C with manual zero point correction (± 10 K)
- Deviation, temperature: typically ± 0.2 K at +25 °C
- Output: 0 – 10 V or 4…20 mA
- Ambient temperature: measuring transducer –30…+70 °C
- Connection type: 2- or 3-wire connection
- Process connection: by screws
- Housing: plastic, material ABS, colour pure white (similar to RAL 9010), (optional stainless steel) V2A (1.4301)
- Dimensions: 85 x 85 x 27 mm (Baldur 1) 75 x 75 x 25 mm (stainless steel)
- Electrical connection: 0.14 – 1.5 mm² via terminal screws
- Installation: wall mounting or on in-wall flush box Ø 55 mm, base with 4-hole for mounting on vertically or horizontally installed in-wall flush boxes for cable entry from the back, with predetermined breaking point for on-wall cable entry from top ⁄ bottom in case of plain on-wall installation
- Humidity: < 95 % r. H., non-precipitating air
- Protection class: III (according to EN 60 730)
- Protection type: IP 30 (according to EN 60 529)
- Standards: CE conformity, electromagnetic compatibility according to EN 61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
- Optional: Two-line display with illumination, cutout 36 x 15 mm (W x H), for displaying the ACTUAL temperature and the internal diagnostics (sensor breakage, sensor short circuit)
THERM ASGARD ® **RTM 1** Room temperature measuring transducers
Type ⁄ WG01| Sensor| Output| Features|
Display| Item No.
RTM1 – U| | | | | IP 30, U – variant
RT M1- U| Pt1000| 0 – 10 V| –| | 1101-41A1-0000-200
RT M1- U LCD| Pt1000| 0 – 10 V| Display | ■| 1101-41A1-2000-200
RT M1- U VA| Pt1000| 0 – 10 V| Stainless steel housing V2A (1.4301)| |
1101-4151-0000-200
RTM1 – I| | | | | IP 30, I – variant
RT M1- I| Pt1000| 4…20 mA| –| | 1101-41A2-0000-200
RT M1- I LCD| Pt1000| 4…20 mA| Display | ■| 1101-41A2-2000-200
RT M1- I VA| Pt1000| 4…20 mA| Stainless steel housing V2A (1.4301)| |
1101-4152-0000-200
Extra| charge:| Other ranges optional
Note:| ***** When equipped with display, the measuring range of 0…+50 °C is
fixed.
Measuring transducers, calibrateable, with active output
TEMPERATURE RANGES:
When selecting measuring transducer ranges, it is necessary to ensure that the
maximum temperatures permissible for sensor ⁄ housing are not exceeded !
Ambient temperature for measuring transducers: – 30 …+ 70 °C
Apparent ohmic resistance = see load resistance diagram
SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or
reverse polarity protection diode is integrated in this device variant. This
internal one-way rectifier also allows operating 0 – 10 V devices on AC supply
voltage.
The output signal is to be tapped by a measuring instrument. Output voltage is
measured her against zero potential (O V) of the input voltage!
When this device is operated on DC supply voltage, the operating voltage input
UB+ is to be used for 15…36 V DC supply and UB – or GND for ground wire!
When several devices are supplied by one 24 V AC voltage supply, it is to be
ensured that all ”positive“ operating voltage input terminals (+) of the field
devices are connected with each other and all ”negative“ operating voltage
input terminals (–) (= reference potential) are connected together (in-phase
connection of field devices). All outputs of field devices must be referenced
to the same potential!
In case of reversed polarity at one field device, a supply voltage short-
circuit would be caused by that device. The consequential short-circuit
current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!
Installation and Commissioning
Devices are to be connected under dead-voltage condition. Devices must only be
connected to safety extra-low voltage. Consequential damages caused by a fault
in this device are excluded from warranty or liability. These devices must be
installed and commissioned by authorized specialists. The technical data and
connecting conditions shown on the device labels and in the mounting and
operating instructions delivered together with the device are exclusively
valid. Deviations from the catalogue representation are not explicitly
mentioned and are possible in terms of technical progress and continuous
improvement of our pro ducts. In case of any modifications made by the user,
all warranty claims are forfeited. Operating this device close to other
devices that do not comply with EMC directives may influence functionality.
This device must not be used for monitoring applications, which serve the
purpose of protecting persons against hazards or injury, or as an EMERGENCY
STOP switch for systems or machinery, or for any other similar safety-relevant
purposes.
Dimensions of housing or housing accessories may show slight tolerances on the
specifications provided in these instructions.
Modifications of these records are not permitted.
In case of a complaint, only complete devices returned in original packing
will be accepted.
Our “General Terms and Conditions for Business“ together with the “General
Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry“ (ZVEI conditions) including supplementary clause
“Extended Retention of Title“ apply as the exclusive terms and conditions“.
Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations and
standards applicable for the place of measurement (e.g. such as welding
instructions, etc.).
Particularly the following shall be regarded:
- VDE ⁄ VDI directive technical temperature measurements, measurement set – up for temperature measurements.
- The EMC directives must be adhered to.
- It is imperative to avoid parallel laying of current-carrying lines.
We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC. Before mounting, make sure that the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of:
- Measuring range
- Permissible maximum pressure, flow velocity
- Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
CONNECTING CONDITIONS
Output: 0 – 10 V
The output voltage follows linear to the temperature signal applied at the
input terminals and generates a proportional output signal of 0 – 10 V. The
voltage outputs are short-circuit proof against ground wire. Applying voltage
supply to the output terminals will destroy the device.
Output: 4 … 20 mA
In case of the 4 … 20 mA measuring transducer, display and evaluating elements
are connected in series in the current loop. The measuring transducer thereby
liWiths the flowing current in variance of the input signal. 4 mA are for the
measuring transducer‘s internal current consumption. The apparent ohmic
resistance can either be connected in the plus or minus path of the measuring
transducer. In case of an apparent ohmic resistance in the plus path, power
supply and resist.
SAFETY REGULATIONS
These devices shall only be used for their intended purpose. Respective safety
regulations issued by the VDE, the states, their control authorities, the TÜV
and the local energy supply company must be observed. The buyer has to ensure
adherence to the building and safety regulations and has to avoid all dangers
of any kind. We do not assume any warranty for faults or damages arising or
resulting from improper use of our equipment or from non-observance of
operating instructions. These instruments must be installed by authorised
specialists only!
Preferably shielded cables should be used in order to prevent damages ⁄
errors. It is imperative to avoid laying parallel with current-carrying lines.
EMC directives must be adhered to.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardized conditions.
When operating under deviating conditions, we recommend performing an initial
manual adjustment on-site during commissioning and subsequently at regular
intervals. Commissioning is mandatory and may only be performed by qualified
personnel!
General notes
Our “General Terms and Conditions for Business“ together with the “General
Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry“ (ZVEI conditions) including supplementary clause
“Extended Retention of Title“ apply as the exclusive terms and conditions.
In addition In addition, the following points are to be observed:
- These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
- Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
- This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
- No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
- Consequential damages caused by a fault in this device are excluded from warranty or liability.
- These devices must be installed and commissioned by authorized specialists.
- The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
- In case of any modifications made by the user, all warranty claims are forfeited.
- This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
- Operating this device close to other devices that do not comply with EMC directives may influence functionality.
- This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
- Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
- Modifications of these records are not permitted.
- In case of a complaint, only complete devices returned in original packing will be accepted.
These instructions must be read installation and commissioning and all notes provided therein are to be regarded!
To open the housing, set a screwdriver (2.0) in the groove at center, press down, and lift up the bottom frame slightly. Pull top cover forward and hold it.
Connection *:
- 2-wire connection for devices with ⁄ without display (not illuminated)
- 3-wire connection for devices with illuminated display
Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.
Measuring ranges (adjustable)| DIP 1| DIP 2|
DIP 3
---|---|---|---
– 20 °C … + 150 °C| O N| O N| O N
– 50 °C … + 50 °C| OFF| O N| O N
– 20 °C … + 80 °C| O N| OFF| O N
– 30 °C … + 60 °C| OFF| OFF| O N
0 °C … + 40 °C| O N| O N| OFF
0 °C … + 50 °C ***| OFF| O N| OFF
0 °C … + 100 °C| O N**| OFF| OFF
0 °C … + 150 °C| OFF| OFF| OFF
(observe max. permissible temperature ranges!)
- (default / fixed with display)
© Copyright by S+S Regeltechnik GmbH
Reprint in full or in parts requires permission from S+S Regeltechnik GmbH.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>