Regulus PS 200 N Plus Thermal Stores User Manual
- June 12, 2024
- Regulus
Table of Contents
Installation and Operation Manual
THERMAL STORES
PS 200 N+, PS 300 N+, PS 400 N+, PS 500 N+,
PS 600 N+, PS 700 N+, PS 800 N+, PS 900 N+,
PS 1000 N+, PS 1100 N+, PS 1500 N+, PS 2000 N+
PS N+
www.regulus.eu
Description
PS N+ Thermal Stores are intended for storing and subsequent distribution of
thermal energy from solid-fuel fired boilers, heat pumps, solar collectors,
electric boilers etc. These tanks do not enable installation of heat
exchangers, only direct installation of an electric heating element. 230V or
3x230V/400V heating elements (2-12 kW output) can be installed directly into
the 6/4” connections. Tanks are fitted with nine connections for heat sources
and a heating system, four connections for installing sensor sheaths and one
connection for a safety valve. A 100mm thick insulation for these tanks can be
purchased as a separate item.
1.1 – Models
Twelve models of 181, 280, 397, 474, 561, 656, 804, 860, 927, 1040, 1504 and
2005 l capacity.
1.2 – Tank protection
The inner surface has no finish, no anticorrosion protection, the outer
surface is lacquered in gray.
1.3 – Thermal Insulation
Thermal insulation is available as a separate item. For easier handling, the
insulation shall not be fitted on the tank until it reaches its definite place
of installation. The insulation is made of fleece, 100 mm thick, with a hard
polystyrene
surface. It is closed by a quick lock.
1.4 – Connection points on the tank
8× side connections in a circular section of 90°, G 6/4“ F thread
1× top connection, G 6/4“ F thread“
4× side connections for sensor sheaths, G 1/2“ F thread
1× connection for installation of a 3bar safety valve, G 1/2“ F thread
1.5 – Packaging
Thermal stores are delivered standing, each screwed to its separate pallet,
packed in bubble wrap.
General Information
This Manual is an integral and important part of the product and must be
handed over to the User. Read carefully the instructions in this Manual as
they contain important information concerning safety, installation, operation
and maintenance. Keep this Manual for later reference. The appliance shall be
installed by a qualified person according to valid rules and Manufacturer‘s
Instructions, otherwise the Warranty is null and void.
This appliance is designed to accumulate thermal energy of heating water and
distribute it subsequently. It must be connected to a heating system and heat
sources.
Using the thermal store for other purposes than above described is forbidden
and the manufacturer accepts no responsibility for damage caused by improper
or wrong use. The thermal store must not be used as a hot water storage tank!
Dimensions and Other Technical Data
Dimensions scheme
CONNECTIONS
pos.| conn.
Heat sources
B1| G 6/4″ F
B2| G 6/4″ F
Heating system
H1| G 6/4″ F
H2| G 6/4″ F
Control and safety
C1| G 1/2″ F
C2| G 1/2″ F
C3| G 1/2″ F
T| G 1/2″ F
P| G 1/2″ F
Universal inlet/outlet
U1| G 6/4″ F
U2| G 6/4″ F
U3| G 6/4″ F
U4| G 6/4″ F
U5| G 6/4″ F
Tank code: ……………………………………………………………. a
Insulation code: …………………………………………………… b
Storage volume: …………………………………………………………. c
Max. working pressure in tanks PS200 N+ ÷ PS1100 N+: … 4 bar
Max. working pressure in tanks PS1500 N+ ÷ PS2000 N+: 3 bar
Max. working temperature in tank: ………………………………… 95 °C
Empty weight: …………………………………………………………….. d
Tipping height without insulation: ………………………………….. V1
Type – model| | PS200 N+| PS300 N+| PS400 N+| PS500
N+| PS600 N+| PS700 N+| PS800 N+| PS900 N+| PS1000
N+| PS1100N+| PS1500 N+| PS2000 N+
---|---|---|---|---|---|---|---|---|---|---|---|---|---
Tank code| a| 14717| 14720| 13783| 14723| 15135| 15138| 15141|
15144| 15147| 15150| 15153| 15156
Insulation code| b| 19295| 19048| 19304| 19296| 19332| 19316|
19297| 19298| 19049| 19305| 19303| 19312
Storage volume [l]| c| 181| 280| 397| 474| 560| 656| 804| 860| 927|
1040| 1504| 2005
Empty weight [kg]| d| 42| 52| 71| 72| 80| 85| 99| 103| 109| 128|
176| 209
Tipping height [mm]| V1| 1370| 1435| 1930| 1940| 1965| 2080| 1890|
2020| 2120| 2125| 1965| 2055
Dimensions [mm]| ø D1| 650| 750| 750| 800| 850| 900| 1000| 990|
1000| 1050| 1300| 1450
| ø D| 450| 550| 550| 600| 650| 700| 800| 790| 800| 850| 1100| 1250
| B1| 1093| 1120| 1610| 1615| 1625| 1635| 1455| 1645| 1690| 1740| 1475|
1510
| B2| 193| 220| 220| 225| 235| 245| 315| 255| 300| 260| 335| 370
| H1| 1351| 1405| 1905| 1915| 1935| 1955| 1845| 1975| 2080| 2080| 1885|
1955
| H2| 193| 220| 220| 225| 235| 245| 315| 255| 300| 260| 335| 370
| C1| 1093| 1120| 1610| 1615| 1625| 1635| 1455| 1645| 1690| 1740| 1475|
1510
| C2| 413| 440| 565| 560| 570| 580| 605| 590| 635| 615| 625| 660
| C3| 843| 870| 1265| 1270| 1280| 1290| 1155| 1300| 1345| 1385| 1175|
1210
| T| 993| 1020| 1480| 1485| 1495| 1505| 1335| 1515| 1560| 1620| 1355|
1390
| P| 333| 360| 450| 450| 440| 450| 450| 390| 435| 395| 450| 450
| U1| 1093| 1120| 1610| 1615| 1625| 1635| 1455| 1645| 1690| 1740| 1475|
1510
| U2| 333| 360| 450| 435| 440| 455| 515| 465| 510| 490| 535| 570
| U3| 793| 795| 1150| 1155| 1165| 1175| 1075| 1185| 1230| 1270| 1095|
1130
| U4| 493| 520| 680| 685| 695| 705| 695| 715| 760| 740| 715| 750
| U5| 893| 920| 1380| 1385| 1395| 1405| 1235| 1415| 1460| 1500| 1255|
1290
Operation
In a thermal store, heating water can be heated up by various types of hot-
water boilers, renewable energy sources (heat pumps, solar collectors), or
possibly also by electric heating elements.
The thermal store is connected to the energy source using a G 6/4“ connection
fitting. Should the tank be connected to a solar thermal system, a heat
exchanger shall be used for the connection because heating water is not used
as the heat transfer fluid in a solar thermal system. The individual tank
outlets are fitted according to the circuits to be connected.
Typical Layout Examples with Thermal Store
Example I.
Heat pump and electric heating element.
KEY
- Regulus heat pump (RTC, CTC)
- pump station for heat pump – CSE TC W iPWM MFB
- electric heating elements for heating system
- heating system expansion vessel
- collector/manifold, HV 60/125-2
- pump station for heating system 2 – CSE2 MIX
- pump station for heating system 1 – CSE2
- thermal store for central heating – PS xxx N+ (K+, N25)
ÚT – central heating (heating system)
KK – ball valve
ZV – check valve
AOV – automatic air vent valve
VK – drain valve
SVE – expansion vessel service valve
PV-ÚT – safety valve for heating system
MFB – Magnet Filterable
Example II.
Biomass boiler (fireplace insert/stove) and electric heating element.
KEY
- hot water storage tank
- el. heating element for DHW w. thermostat
- electric heating elements for heating system
- thermal store for central heating – PS xxx N+ (K+, N25)
- heating system expansion vessel
- boiler load unit – thermostatic
- biomass boiler (fireplace insert/stove)
- pump station for heating system – CSE MIX
- pump station for DHW heating – CSE OTS ZV
- pump station for DHW recirculation – CSE TVMIX ZV
- safety kit for HW storage tank
- DHW expansion vessel
SV – cold water
TV – hot water
CV – hot water recirculation
ÚT – central heating (heating system)
KK – ball valve
ZV – check valve
AOV – automatic air vent valve
PTR – pressure temperature relief valve
REDV – pressure reducing valve (optional)
VK – drain valve
SVE – expansion vessel service valve
PV-ÚT – safety valve for heating system
MFB – Magnet Filterball
F – filter
BVTS – safety relief valve of boiler cooling loop
Installation and Commissioning
Installation shall meet valid rules and may be done by qualified staff only.
Defects caused by improper installation, use or handling are not covered by
warranty.
After the tank is installed and connected to an existing heating system, it is
recommended to clean the entire heating system using a suitable cleaning
agent, e.g. BP 400.
Anti-corrosion protective liquid should be also used, e.g. BP 100 Plus.
6.1 – Connection to heat sources
Place the tank on the floor, as close to your heat source as possible. Fit the
insulation, cf. Installing Insulation on the Tank. Connect the heating system
according to the recommended connection layout – see Chap. 5.Install a drain
valve at the lowest point of the tank. Install an air vent valve at the
highest point of the system. Insulate all the connecting piping.
6.2 – Connection to a solar thermal system
This thermal store is primarily not designed to be connected to a solar
thermal system. However, when needed, such a connection can be done by means
of a heat exchanger between the solar thermal system and the thermal store. In
such an event, all the connecting piping between the tank and this heat
exchanger shall be thoroughly insulated.
6.3 – El. heating element installatio n
These thermal stores can be equipped with electric heating elements of output
up to 12 kW depending on the volume of the thermal store – see the table of
max. output of heating elements in hot water tanks and thermal stores. They
can be connected either directly (elements with integrated thermostat) or via
the controller of the entire heating system.
All electric heating elements shall be protected by a safety thermostat.
The electric heating element shall be wired by a professionally qualified
person only.
6.4 – Commissioning
Ground the tank before commissioning.
This tank is not designed for DHW heating.
The tank shall be filled up together with the heating system, respecting valid
standards and rules. In order to minimize corrosion, special additives for
heating systems should be used. The quality of heating water depends on the
quality of filling water at commissioning, on the top-up water quality and on
the frequency of topping up. This has a strong influence on the lifetime of
heating systems. Poor quality of heating water may cause problems like
corrosion or incrustation, esp. on heat transfer surfaces. Fill the heating
circuits with the appropriate fluids and air-bleed the entire system. Check
all connections for leaks and verify the system pressure. Set the heating
controller in compliance with the documentation and manufacturer’s
recommendations.
Check regularly proper function of all control and adjustment elements.
Installing Insulation on the Tank
Product description
Fleece insulation with a hard polystyrene surface, closed by a quick lock.
Warning
Insulation installation shall be done in two or three persons, depending on
its size. The PU leather surface coated fleece insulation must not be
installed at temperatures below 20 °C. If this cannot be avoided, the
insulation shall be pre-warmed in another room to at least 20 °C. It is
impossible to install insulation of lower temperature, there is a risk of
damage.
Do not use any tools for installation.
Keep away from open fire.
Installing insulation
- Put the bottom insulation under the tank and place the tank following installation instructions.
- Wrap the insulation around the tank carefully. Check that the insulation adheres to its body perfectly. This can be reached by rubbing and patting the insulation by hand from its centre evenly in both directions until the insulation adheres to the tank’s surface completely and no bubbles are left.
- Use the holes for connections as a rest during the insulation installation.
- At least one person presses the insulation to the tank, pulling both ends together. The other person closes the quick lock from the side.
- Put on the upper insulation and cover.
- Push on the covering plastic rosettes depending on the size of connections, or put on the flange plug(s) with insulation.
- Finish the tank installation in compliance with the respective instructions and valid standards and rules.
Warranty on insulation
The insulation is covered by a 24-month warranty. This period starts the next
day after the insulation is sold.
-
Warranty shall become null and void if:
○ the procedure described in the Installation Manual was not respected,
○ the product was used for other purposes than intended. -
Warranty does not cover:
○ usual wear and tear,
○ damage caused by fire, water, electricity or another natural disaster,
○ defects caused by failure to use the product in compliance with its intended purpose, by improper use and insufficient maintenance,
○ defects caused by mechanical damage to the product,
○ defects caused by tampering or incompetent repair.
Maintenance
If the tank is fitted with a heating element, disconnect it from the mains
first. Clean the exterior of the tank with a soft cloth and a mild detergent.
Never use abrasive cleaners or solvents.
Check all tank connections for leaks.
Disposal
Packaging shall be disposed of in compliance with the valid rules. When the product reaches the end of its life, it shall not be disposed of as household waste. It shall be dropped off at a Local Waste Recycling Centre. Insulation shall be recycled as plastic and the steel vessel as scrap iron.
Warranty
This product is covered by warranty according to the conditions described in this Manual and according to the Warranty Certificate. A Warranty Certificate is an integral part of the supply
©2023 We reserve the right to errors, changes and improvements without prior
notice.