Regulus Romtherm PS E+ Thermal Stores Instruction Manual
- October 30, 2023
- Regulus
Table of Contents
- Description
- General Information
- Dimensions and Other Technical Data
- Operation
- Typical Layout Example with Thermal Store
- Installation and Commissioning
- Installing Insulation on the Tank
- Maintenance
- Disposal
- Warranty
- Customer Support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Regulus Romtherm PS E+ Thermal Stores
THERMAL STORES
PS 500 E+, PS 750 E+, PS 1000 E+, PS 1100 E+, PS 1250 E+
Description
PS E+ Thermal Stores are intended for storing and subsequent distribution of thermal energy from solid-fuel fired boiler. 230V or 3x230V/400V heating elements (2-12 kW output) can be installed directly into the 6/4” connections. Tanks are fitted with four side connections, one top connection and two connections for sensor sheaths. A 100mm thick insulation for these tanks can be purchased as a separate item.
Models
Five models of 473, 756, 927, 1038 and 1260 l capacity.
Tank protection
The inner surface has no finish, no anti corrosion protection, the outer surface is lacquered in gray.
Thermal Insulation
Thermal insulation is available as a separate item. For easier handling, the insulation shall not be fitted on the tank until it reaches its definite place of installation. The insulation is made of fleece, 100 mm thick, with a hard polystyrene surface. It is closed by a quick lock.
Connection points on the tank
4× side connections, G 6/4“ F thread
1× top connection, G 6/4“ F thread
2× side connections for sensor sheaths, G 1/2“ F thread
Packaging
Thermal stores are delivered standing, each screwed to its separate pallet, packed in bubble wrap.
General Information
This Manual is an integral and important part of the product and must be handed over to the User. Read carefully the instructions in this Manual as they contain important information concerning safety, installation, operation and maintenance. Keep this Manual for later reference. The appliance shall be installed by a qualified person according to valid rules and Manufacturer‘s Instructions, otherwise the Warranty is null and void.
This appliance is designed to accumulate thermal energy of heating water and distribute it subsequently. It must be connected to a heating system and heat sources.
Using the thermal store for other purposes than above described is forbidden and the manufacturer accepts no responsibility for damage caused by improper or wrong use. The thermal store must not be used as a hot water storage tank!
Dimensions and Other Technical Data
Code
Thermal store| PS 500 E+| PS 750 E+| PS 1000 E+| PS 1100 E+| PS 1250 E+
Tank code| 14754| 15212| 15851| 15215| 15992
Insulation code (accessor.)| 19319| 19309| 19313| 19335| 19324
Application
Storage and subsequent distribution of thermal energy from solid-fuel boilers.
Energy efficiency data (as per EC Regulation No. 813/2013)
| PS 500 E+ w.
insulation
| PS 750 E+ w.
insulation
| PS 1000 E+
w. insulation
| PS 1100 E+
w. insulation
| PS 1250 E+
w. insulation
Energy efficiency class| C| –| –| –| –
Standing loss| 90 W| 115 W| 128 W| 135 W| 152 W
Storage volume| 473 l| 756 l| 927 l| 1038 l| 1260 l
Technical data
Total tank volume| 473 l| 756 l| 927 l| 1038 l| 1260 l
Max. working temperature in tank| 95 °C| 95 °C| 95 °C| 95 °C| 95 °C
Max. working pressure in tank| 4 bar| 4 bar| 4 bar| 4 bar| 3 bar
Material
Tank material| S235JR| S235JR| S235JR| S235JR| S235JR
Dimensions, tipping height, weight
Tank diameter| 600 mm| 750 mm| 800 mm| 850 mm| 950 mm
Tank diameter with insulation| 800 mm| 950 mm| 1000 mm| 1050 mm| 1150 mm
Tank overall height| 1915 mm| 1975 mm| 2080 mm| 2080 mm| 2065 mm
Tipping height without insulation| 1940 mm| 2020 mm| 2120 mm| 2130 mm| 2120 mm
Heating elem. max. length / output| 680 mm
/ 9 kW
| 755 mm
/ 9 kW
| 815 mm
/ 12 kW
| 815 mm
/ 12 kW
| 955 mm
/ 12 kW
Empty weight| 68 kg| 90 kg| 106 kg| 124 kg| 125 kg
Accessories
Insulation (code)| 19319| 19309| 19313| 19335| 19324
El. heating element| models ETT-A, C, D, F, P, M
Thermal store| PS 500 E+| PS 750 E+| PS 1000 E+| PS 1100 E+| PS 1250 E+
---|---|---|---|---|---
Tipping height without insulation| 1940 mm| 2020 mm| 2120
mm| 2130 mm| 2120 mm
Marking| Connection| Height [mm]| Connection| Height [mm]| Connection| Height
[mm]| Connection| Height [mm]| Connection| Height [mm]
Heating system
H1| G 6/4″| 1915| G 6/4″| 1975| G 6/4“| 2080| G 6/4″| 2080| G 6/4″| 2065
H2| G 6/4″| 225| G 6/4″| 225| G 6/4“| 300| G 6/4″| 255| G 6/4″| 300
Control and safety
C1| G 1/2″| 1545| G 1/2″| 1575| G 1/2“| 1620| G 1/2″| 1665| G 1/2“| 1620
C2| G 1/2″| 505| G 1/2″| 535| G 1/2“| 580| G 1/2″| 535| G 1/2“| 580
Universal inlet/outlet
U1| G 6/4″| 1625| G 6/4″| 1655| G 6/4“| 1700| G 6/4″| 1745| G 6/4“| 1700
U2| G 6/4″| 975| G 6/4″| 955| G 6/4“| 1050| G 6/4″| 1045| G 6/4“| 1000
U3| G 6/4″| 375| G 6/4″| 405| G 6/4“| 450| G 6/4″| 405| G 6/4“| 450
Tank dimensions [mm]
V (tank height)| 1915| 1975| 2080| 2080| 2065
Ø Di (tank diameter)| 600| 750| 800| 850| 950
Ø De (diam. w. insulation)| 800| 950| 1000| 1050| 1150
Operation
In a thermal store, heating water can be heated up by various types of hot-
water boilers, or possibly also by electric heating elements.
The thermal store is connected to the energy source using a G 6/4“ connection
fitting. The individual tank outlets are fitted according to the circuits to
be connected.
Typical Layout Example with Thermal Store
Example
Biomass boiler (fireplace insert/stove)
KEY
- hot water storage tank
- electric heating element with thermostat
- thermal store for central heating – PS xxx E+ (ES+)
- heating system expansion vessel
- boiler load unit – thermostatic
- biomass boiler (fireplace insert/stove)
- pump station for heating system – CSE MIX
- pump station for DHW heating – CSE OTS ZV
- pump station for DHW recirculation – CSE TVMIX ZV
- safety kit for HW storage tank
- DHW expansion vessel
SV – cold water
TV – hot water
CV – hot water recirculation
ÚT – central heating (heating system)
KK – ball valve
ZV – check valve
AOV – automatic air vent valve
PTR – pressure temperature relief valve
REDV – pressure reducing valve (optional)
VK – drain valve
SVE – expansion vessel service valve
PV-ÚT – safety valve for heating system
MFB – Magnet Filterball
F – filter
BVTS – safety relief valve of boiler cooling loop
Installation and Commissioning
Installation shall meet valid rules and may be done by qualified staff only.
Defects caused by improper installation, use or handling are not covered by
warranty.
After the tank is installed and connected to an existing heating system, it is
recommended to clean the entire heating system using a suitable cleaning
agent, e.g. BP 400.
Anti-corrosion protective liquid should be also used, e.g. BP 100 Plus.
Connection to heat sources
Place the tank on the floor, as close to your heat source as possible. Fit the insulation, cf. Installing Insulation on the Tank. Connect the heating system according to the recommended connection layout – see Chap. 5.Install a drain valve at the lowest point of the tank. Install an air vent valve at the highest point of the system. Insulate all the connecting piping.
El. heating element installation
These thermal stores can be equipped with electric heating elements of output
up to 12 kW depending on the volume of the thermal store – see the table of
max. output of heating elements in hot water tanks and thermal stores. They
can be connected either directly (elements with integrated thermostat) or via
the controller of the entire heating system.
All electric heating elements shall be protected by a safety thermostat.
The electric heating element shall be wired by a professionally qualified
person only.
Commissioning
Ground the tank before commissioning.
This tank is not designed for DHW heating.
The tank shall be filled up together with the heating system, respecting valid
standards and rules. In order to minimize corrosion, special additives for
heating systems should be used. The quality of heating water depends on the
quality of filling water at commissioning, on the top-up water quality and on
the frequency of topping up. This has a strong influence on the lifetime of
heating systems. Poor quality of heating water may cause problems like
corrosion or incrustation, esp. on heat transfer surfaces.
Fill the heating circuits with the appropriate fluids and air-bleed the entire system. Check all connections for leaks and verify the system pressure. Set the heating controller in compliance with the documentation and manufacturer’s recommendations. Check regularly proper function of all control and adjustment elements.
Installing Insulation on the Tank
Product description
Fleece insulation with a hard polystyrene surface, closed by a quick locks.
Warning
Insulation installation shall be done in two or three persons, depending on
its size. The PU leather surface coated fleece insulation must not be
installed at temperatures below 20 °C. If this cannot be avoided, the
insulation shall be pre-warmed in another room to at least 20 °C. It is
impossible to install insulation of lower temperature, there is a risk of
damage.
Do not use any tools for installation.
Keep away from open fire.
Installing insulation
- Put the bottom insulation under the tank and place the tank following installation instructions.
- Wrap the insulation around the tank carefully. Check that the insulation adheres to its body perfectly. This can be reached by rubbing and patting the insulation by hand from its centre evenly in both directions until the insulation adheres to the tank’s surface completely and no bubbles are left.
- Use the holes for connections as a rest during the insulation installation.
- At least one person presses the insulation to the tank, pulling both ends together. The other person closes the quick lock from the side.
- Put on the upper insulation and cover.
- Push on the covering plastic rosettes depending on the size of connections, or put on the flange plug(s) with insulation.
- Finish the tank installation in compliance with the respective instructions and valid standards and rules.
Warranty on insulation
- Warranty shall become null and void if:
- the procedure described in the Installation Manual was not respected,
- the product was used for other purposes than intended.
- Warranty does not cover:
- usual wear and tear,
- damage caused by fire, water, electricity or another natural disaster,
- defects caused by failure to use the product in compliance with its intended purpose, by improper use and insufficient maintenance,
- defects caused by mechanical damage to the product,
- defects caused by tampering or incompetent repair.
Maintenance
If the tank is fitted with a heating element, disconnect it from the mains first. Clean the exterior of the tank with a soft cloth and a mild detergent. Never use abrasive cleaners or solvents. Check all tank connections for leaks.
Disposal
Packaging shall be disposed of in compliance with the valid rules. When the product reaches the end of its life, it shall not be disposed of as household waste. It shall be dropped off at a Local Waste Recycling Centre. Insulation shall be recycled as plastic and the steel vessel as scrap iron.
Warranty
This product is covered by warranty according to the conditions described in this Manual and according to the Warranty Certificate. A Warranty Certificate is an integral part of the supply.
Customer Support
©2023 We reserve the right to errors, changes and improvements without prior notice.
REGULUS spol. s r.o.
E-mail: sales@regulus.eu
Web: www.regulus.eu
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>