AKO PROPlus 3PH BASIC Electronic Panel User Guide
- June 13, 2024
- AKO
Table of Contents
AKO PROPlus 3PH BASIC Electronic Panel
Presentation
PROPlus 3PH is the global electronic solution to manage positive and negative cold room stores, in combination with:
- Standard condensing units
- Streamlined condensing units
- Or as a service panel in decentralised systems.
It offers a high degree of IP65 protection for installation in damp environments. It is easy to install thanks to its new connection strip.
Maintenance
Clean the surface of the unit with a soft cloth, water and detergent. Do not
use abrasive detergents, petrol, white spirits or solvents.
Precautions
Using the equipment without following the manufacturer’s instructions may
affect the device’s safety requirements. To ensure that the device operates
correctly, only probes supplied by AKO should be used. Between -40 ºC and +20
ºC, if the NTC probe is extended up to 1,000 m with minimum 0.5 mm² wire, the
maximum deviation will be 0.25 ºC (Wire for probe extension ref. AKO-15586).
IMPORTANT:
- The AUX 1, AUX 2 and AUX 3 relays are programmable, and their operation depends on the configuration (see page 25).
- The function of the digital inputs depends on the configuration (See page 26).
- The recommended currents and powers are the maximum working currents and powers.
Versions and references
| Condensing unit| Condenser fans| Evaporator fan|
Defrost resistances| Light| Power supply
---|---|---|---|---|---|---
AKO- 15690| 2,5 – 4 A| 3 A (I+N)| 4 A (I+N)| 7.000 W| 1 A (230 W)|
400 V / III
50/60 Hz
AKO- 15691| 4 – 6,3 A
AKO- 15692| 6,3 – 10 A| 10.200 W
AKO- 15693| 10 – 16 A
AKO- 15697| –| –| 5 A (I+N)
AKO- 15699| 1.6 – 2.5 A (III)
AKO-15699- 1| 6.3 – 10 A (III)| 20.000 W
AKO-15690- EVC| 2,5 – 4 A| 3 A (I+N)| 4 A (I+N)| 7.000 W
AKO-15691- EVC| 4 – 6,3 A
AKO-15692- EVC| 6,3 – 10 A| 10.200 W
AKO-15693- EVC| 10 – 16 A
AKO-15697- EVC| –| –| 5 A (I+N)
AKO-15699- EVC| 1.6 – 2.5 A (III)
Recommendations
Disconnect the voltage before carrying out any operations inside the electrical panel. All wiring should be according to current standards and should be carried out by authorised staff. Only carry out the wiring foreseen in the wiring diagrams. Using the electrical panel not observing the manufacturer’s instructions may alter the appliance’s safety requirements. A tool is needed to remove any fixed part.
- Panel installation:
- It is advisable to leave a clean safety space without obstacles around the panel.
- Do not knock or make sudden movements on the panel.
- Carry out the wiring according to the installation manual.
- The probes and their cables should NEVER be installed in a conduit together with power, control or feeder cables.
- The earth terminals that the panels contain are installed to guarantee the continuity of earthing, however, earthing is not carried out by the terminal and should be carried out outside the panel.
- The neutral ratings are of the TT type. The IT rating should not be used.
- Circuit breakers (protective switches) are of the phase/s + neutral, curve C type, guaranteeing switching and protection against overcurrents.
- Close the panel when your are not working on it.
- Residual current protection outside the electrical panel according to low voltage electrotechnical regulations.
- The panels meet European standard EN 61439-1 / EN 61439-2.
- Terminals for copper external conductors.
- Checks before starting the panel up:
- Power supply voltages and frequencies will be the ones that figure in the “Technical specifications” section.
- Check that there are no loose parts or foreign bodies on connections or switchgear.
- Check that there is no dust or damp inside the panel.
- Check the correct fastening of the switchgear and components.
- Check the correct tightening of the screws and power connections.
- Check the correct connection of the power conductors.
- Check the correct insulation of the outer lines and that they do not mechanically force the inner connections of the panel. Check that the maximum current of the Q1 and Q3 current breaker (according to model) has been set correctly. Before starting the installation up, we recommend preheating the compressor’s housing.
- Checks during the panel start-up:
- Check that no electric arcs occur.
- Check that the relays or contactors do not produce ratios.
- Check that there is no overheating in cables, controllers and the rest of the switchgear.
- Checks after the first 24 hours of operation:
- Check that no overheating occurs.
- Retighten screws and power connections.
- Periodical preventive maintenance:
- The panel should remain closed using its lock.
- Retighten the power connections once a year.
- Check the wear of the switchgear once a year.
- Clean the outer surface of the panel with a soft cloth, water and detergent. Do not use abrasive detergents, petrol, white spirits or solvents.
- Technical data:
- Working ambient temperature: –5 ºC to 40 ºC
- Rated isolation voltage Ui = 440 V~
- Electrical panels with degree of protection: IP 65
- CEM B environment
- Terminals for copper conductors
- Resistance to short-circuits Icc=6 kA
- Rated pulse voltage (Vimp) 2,5 KV
- Cable isolation voltage:
- Operation: 500V (Halogen free)
- Power: 750V (Halogen free)
Description
If pump down is active, it indicates the operation of the compressor.
If pump down is active, it indicates that the solenoid is open, otherwise it
indicates that the compressor is in operation.
Quick access to functions
Messages
Component location
ATTENTION: Make sure to turn of the equipment’s power supply before
handling it, as different areas may be energised.
IMPORTANT: The availability of the elements described depends on the
panel model.
Identification
- F1: Defrost circuit breaker
- FM: Operation circuit breaker
- Q1: Compressor motor guard
- Q3: Evaporator fan motor guard
- K1M: Compressor contactor
- K2M: Defrost contactor
- K4M: Evaporator fan contactor
- T2: EVC Transformer
- EVC1: Controller for expansion valve
Pressure switch wiring options
- Combine high-low pressure controller (AKO-15690/1/2/3 – AKO-15690/1/2/3-EVC)
- Separate Low pressure controller per AC input (AKO-15690/1/2/3 – AKO-15690/1/2/3-EVC)
- Pressure controller equivalence
Basic configuration
The basic configuration menu allows the equipment to be configured for the most common applications. Press the SET key for 5 seconds to access it. If the access code is activated, a 2 digit code is requested, if the code entered is not correct the unit will not enter programming. If more specific configuration is required use the advanced configuration menu (See user manual on www.ako.com) After 20 seconds without touching any key, the unit returns to the previous level without saving changes or it will exit programming.
Function of the keys in programming
-
SP: Set point
It defines the temperature that should be inside the cold storage room:- Minimum: –45.0 *
- Maximum: 99
(Depends on the bottom/top locking of the set point).
-
d0: Defrost frequency
Time that must elapse between the starting of each defrost. -
d1: Maximum defrost duration
The defrost will end after this time has elapsed since it started. -
F3: Fan status during defrost
It defines the status of the fans during defrost. 0= OFF 1= ON -
A1: Maximum alarm probe 1
Defines the temperature at which the maximum alarm will be triggered. Only affects probe 1.- Minimum: –45.0 *
- Maximum: 99
(Depends on the bottom/top locking of the set point).
-
A2: Minimum alarm probe 1
Defines the temperature at which the minimum alarm will be triggered. Only affects probe 1.- Minimum: –45.0 *
- Maximum: 99
(Depends on the bottom/top locking of the set point).
Connectivity
The unit has a port for RS485 date connection (MODBUS), which can be managed using a PC. Up to 127 units can be connected to a PC with AKONet (AKO-5010), or to the AKO-5011 web server. Each of these units should have a different MODBUS address, that is defined using the P5. Using the AKONet software it is possible to display and capture the data of any connected unit, and configure its parameters.
- AKONet: Management software for AKO units with RS485 (MODBUS) communication. If it is installed in a server the software can be accessed from any PC in the network or even from Internet (it requires the server having connection to Internet and fixed IP).
- AKO-5011: Web server that includes the AKONet software. It can carry out the same functions as the PC, with the advantage of having a server dedicated to communication with the units.
Parameters
The parameters are grouped into 6 sections depending on their function. Press the keys for 10 seconds to access it. The Def. column shows factory-set default parameters. Temperature values are expressed in ºC. (Equivalent temperature in ºF)
Level 1.- REGULATION AND CONTROL
Description | Units | Min | Def | Max. | |
---|---|---|---|---|---|
SP | Temperature Adjustment (Set Point) | (ºC/ºF) | -45 | 0.0 | 99 |
C0 | Calibrating probe 1 (Offset) | (ºC/ºF) | -20.0 | 0.0 | 20.0 |
C1 | Probe 1 differential (Histeresis) (Histéresis) | (ºC/ºF) | 0.1 | 2.0 |
20.0
C2| Upper blocking of the set point (cannot be set above this value)|
(ºC/ºF)| C3| 99| 99
C3| Lower blocking of the set point (cannot be set below this value)|
(ºC/ºF)| -45| -45| C2
C4| Type of delay for protection of the compressor
0 =OFF/ON (since the last disconnection);
1 =OFF-ON/ON-OFF (since the last shut-down /start-up)
| | 0| 0| 1
C5| Protection delay time (value of the option selected in parameter
C4)| (min.)| 0| 0| 120
C6| Status of COMP. relay with probe fault : 0 =OFF; 1
=ON; 2 =Average based on last 24 hours prior to probe fault; 3 =ON-OFF
as prog. C7 and C8| | 0| 2| 3
C7| Time relay ON in case of faulty probe: (If C7=0 and C8:;0,
the relay will always be OFF deenergised)| (min.)| 0| 10| 120
C8| Time relay OFF in case of fault of probe 1: (If C8=0 y C7:;0, the
relay will always be ON energised)| (min.)| 0| 5| 120
C9| Maximum duration of the continuous cycle mode. ( 0 =disabled)|
(h.)| 0| 0| 48
C10| Variation of the set point (SP) in continuous cycle mode, when it
reaches this point (SP+C10), it reverts to the normal mode. (SP+C10 ;: C3) (
0 =OFF) The value of this parameter is always negative, except if it is 0|
(ºC/ºF)| 0| -50| C3-SP
C11| Idle time of the digital input for the change Set Point function to
be activated (Only if P10 or P11 =1) ( 0 =OFF)| (h.)| 0| 0| 24
C12| Variation of the set point (SP) when the change set point function
is active. (SP+C12 > C2) ( 0 = disabled)| (ºC/ºF)| C3-SP| 0,0| C2-SP
EP| Exit to Level 1| | | |
Level 1.- DEFROST CONTROL
Level 1.- FAN CONTROL
Description | Units | Min | Def | Max. | |
---|---|---|---|---|---|
F0 | Fan shut-down temperature as per probe 2 (if P4 :; 1) | (ºC/ºF) | -45 | ||
45 | 99,0 | ||||
F1 | Probe 2 differential (If P4 :; 1) | (ºC/ºF) | 0,1 | 2,0 | 20,0 |
F2 | Stop fans when stopping compressor 0 =No, 1 =Yes | 0 | 1 | 1 | |
F3 | Fan status during defrost: 0 =Off; 1 =On | 0 | 0 | 1 | |
F4 | Starting delay after defrost (if F3=0) Will only operate if it is | ||||
higher than d9 | (min.) | 0 | 3 | 99 | |
EP | Exit Level 1 |
Level 1.- ALARM CONTROL
Level 1.- GENERAL STATUS
Description | Units | Min | Def | Max. | |
---|---|---|---|---|---|
P1 | Delay of all functions on receiving electrical power | (min.) | 0 | 0 |
255
P2| Función del código de acceso (password) 0 = Inactivo; 1 =
Bloqueo acceso a parámetros; 2 = Bloqueo del teclado| | 0| 0| 2
P3| Configures the default factory settings 0 = No changes 1
=Return to default settings| | 0| 0| 1
P4| Selection of type of inputs 1 =1 probe 2 =2 probes| |
1| 2| 2
P5| MODBUS address| | 1| 1| 225
P6| AUX 1 relay configuration 0 =Deactivated 1
=Pump down 2 = Same compressor status| | 0| | 2
P62| AUX 2 relay configuration 0 =Deactivated
1 =Alarm 2 = Same compressor status 3 =Same unit status 4
=Pump down| | 0| | 4
P63| AUX 3 relay configuration 0 =Deactivated
1 =Light 2 =Same unit status| | 0| 1| 2
P7| Temperature display mode 0 =Integers in ºC 1 =One
decimal in ºC 2 =Integers in ºF 3 =One decimal in ºF| | 0| 1| 3
P8| Probe to be displayed (as per parameter P4) 0 =visualization
of all the probes in sequence; 1 =Probe 1 2** =Probe 2| |
0| 1| 2
The options available in each setting can vary depending on the model.
Nivel 1.- ACCESS CONTROL AND INFORMATION (tid)
Lev | Description | Units | Min | Def | Max. |
---|---|---|---|---|---|
L5 | Access code (Password) | 0 | 0 | 99 | |
PU | Program version (Information) | – | |||
Pr | Program revision (Information) | – | |||
EP | Exit Level 1 |
Default parameters according to models
Parameter | |
---|---|
P11 | |
AKO- 15690/1/2/3 | 0 =Deactivated |
=Alarm
AKO- 15697| 0 =Deactivated| 2 =Same compressor status|
1 =Alarm
AKO-15699/699-1| 2 =External alarm| 2 =Same compressor status|
1 =Alarm
AKO-15690/1/2/3-EVC| 0 =Deactivated| 0 =Deactivated| 4
=Pump down
AKO-15697- EVC| 0 =Deactivated| 0 =Deactivated| 2
=Same compressor status
AKO-15699- EVC| 2 =External alarm| 0 =Deactivated| 2
=Same compressor status
Technical specifications
- Rated voltage Un …………………………………………………………………………………………400 V~ ±10 % 50/60 Hz ±5 %
- Rated voltage Ue …………………………………………………………………………………………230 V~ ±10 % 50/60 Hz ±5 %
- ALARM relay …………………………………………………………………………………………………………… 8A at 250V, cosj=1
- Probe temperature range ……………………………………………………………………………………………..–45.0 ºC to 99.9 ºC
- Resolution, setting and differential ………………………………………………………………………………………………….0.1 ºC
- Thermometric precision …………………………………………………………………………………………………………………± 1 ºC
- Precision of the NTC probe at 25 ºC ……………………………………………………………………………………………….± 0.4 ºC
- Input for NTC probe ……………………………………………………………………………………………………………..AKO-14901
- Maximum input power in the operation …………………………………………………………………………………………….30 VA
- Working ambient temperature ………………………………………………………………………………………………-5 ºC to 40 ºC
- Storage ambient temperature …………………………………………………………………………………………….–30 ºC to 70 ºC
- Overvoltage category …………………………………………………………………………………….II s/ EN 61439-1 / EN 61439-2
- Degree of pollution ……………………………………………………………………………………….II s/ EN 61439-1 / EN 61439-2
- Degree of protection ………………………………………………………………………………………………………………………IP65
- Dimensions ……………………………………………………………………………………………….400(An) x 300(Al) x 135(P) mm
- Double isolation between power supply, secondary circuit and relay output.
- Type of assembly ………………………………………………………………………………………………………………..Fixed internal/Internal buzzer/Encapsulated assembly
For further information, please refer to the user manual available on our website www.ako.com.