ARISTON DEOS 16s Dehumidifier User Manual

June 4, 2024
Ariston

ariston-logo

ARISTON DEOS 16s Dehumidifier

ARISTON=-3DEOS-16s-Dehumidifier-product

SAFETY RULES

READ THIS MANUAL CAREFULLY AND STORE IT SAFELY, AS IT CONTAINS IMPORTANT INFORMATION FOR SAFE INSTALLATION, USE AND MAINTENANCE OF YOUR NEW APPLIANCE.

RULE| RISK|
---|---|---
Do not perform any operations that involve opening the appliance.| Electrocution due to exposure to live components.

Personal injury caused by burns due to overheated components, or wounds caused by sharp edges or protrusions.

|
Make sure that the systems to which the appliance should be connected comply with the applicable regulations.|

Electrocution due to exposure to live wires.

| ****


Do not start or stop the appliance simply by plugging it into the mains electricity socket or unplugging it.

| ****

Electrocution through contact with a damaged cable or plug, or socket.

|
Do not damage/modify/heat the power cable or place heavy objects on top of it.|

Electrocution due to non-insulated live wires.

| ****


Do not leave any objects on top of the appliance.

| ****

Personal injury due to objects falling as a result of vibrations.

| ****


Do not climb onto the appliance.

| ****

Personal injury due to the appliance falling.

| ****


Do not attempt to clean the appliance without first turn- ing it off and unplugging it or switching the dedicated switch off.

| ****


Electrocution due to exposure to live components.

| ****


Do not direct the air flow towards gas hobs or gas stoves.| Explosions, fires or intoxication due to the discharge of gas from supply nozzles. Flames extinguished by the air flow.| ****
Do not place your fingers in the air outlets or in the air inlet grilles.| Electrocution due to exposure to live components. Personal injury from cuts.|


Do not drink the condensate water.| Personal injury from poisoning.|
If you notice a burnt smell or see smoke coming out of the device, disconnect it from the power supply, open all windows and contact the technician.|

Personal injury from burns or fume inhalation.

| ****
Ensure that there is sufficient ventilation in the room in which the dehumidifier is installed if a combustion appliance is also located there.|


Lack of oxygen.

|
Do not operate the unit in the presence of hazardous substances and flammable or corrosive gases.| Risk of fire, injury, explosion.|

If the power cable is damaged, it must be replaced by the manufacturer or by the relevant technical assis- tance service, or – at all events – by a suitably qualified technician, in order to prevent potential risks.| ****


Electrocution due to exposure to live wires.

|
Avoid prolonged exposure to the air flow.| Health issues.|

Do not use any insecticides, solvents or aggressive detergents to clean the appliance.| Damage to plastic or painted parts.|
Do not use the appliance for any purpose other than normal domestic use.| Damage to the device caused by operation overload. Damage to objects caused by improper use.|

Do not allow children or inexperienced persons to operate the appliance.| Damage to the appliance caused by improper use.|
Do not direct the air flow towards valuable items, plants or animals.| Damage or deterioration due to excessive cold/heat, humidity, ventilation.|

Make sure that the appliance is connected to an efficient earthing system.|


OPERATING AND MAINTENANCE INSTRUCTIONS

WARNINGS (for using R290/R32 refrigerant only)

  • Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
  • The appliance shall be stored in a room without continuously operating ignition sources (for example open flames, an operating gas appliance or an operating electric heater).
  • Do not pierce or burn.
  • Be aware that the refrigerants may not contain an odor.
  • The appliance should be installed, operated, and stored in a room with a floor area larger than 4 m2.
  • Compliance with national gas regulations shall be observed.
  • Keep ventilation openings clear of obstruction. The appliance shall be stored so as to prevent mechanical damage from occurring.
  • A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
  • Any person who is involved with working on or breaking into a refrigerant circuit should hold a currently valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with industry-recognized assessment specifications.
  • Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of a person competent in the use of flammable refrigerants.
  1. Transport of equipment containing flammable refrigerants
    See transport regulations

  2. Marking of equipment using signs
    See local regulations

  3. Disposal of equipment using flammable refrigerants
    See national regulations.

  4. Storage of equipment/appliances
    The storage of equipment should be in accordance with the manufacturer’s instructions.

  5. Storage of packed (unsold) equipment
    Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

  6. Information on services

    • Checks to the area
      Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.

    • Work procedure
      Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed.

    • General work area
      All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

    • Checking for presence of refrigerant
      The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.

    • Presence of fire extinguisher
      If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

    • No ignition sources
      No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.

    • Ventilated area
      Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.

    • Checks to the refrigeration equipment
      Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:  The charge size is in accordance with the room size within which the refrigerant-containing parts are installed;The ventilation machinery and outlets are operating adequately and are not obstructed; If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

    • Checks to electrical devices
      Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.

    • Initial safety checks shall include:
      That capacitor are discharged: this shall be done in a safe manner to avoid possibility of sparking; That there no live electrical components and wiring are exposed while charging, recovering or purging the system; That there is continuity of earth bonding.

  7. Repairs to sealed components

    • During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it isabsolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
    • Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
      NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.
  8. Repair to intrinsically safe components
    Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

  9. Cabling
    Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

  10. Detection of flammable refrigerants
    Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

  11. Leak detection methods
    The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic
    leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

  12. Removal and evacuation
    When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be Vused. However, it is important that best practice is followed since flammability is a consideration. The following procedure

    • shall be adhered to:
    • Remove refrigerant;
    • Purge the circuit with inert gas;
    • Evacuate;
      Purge again with inert gas; Open the circuit by cutting or brazing.The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.
  13. Charging procedures
    In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

  14. Decommissioning
    Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.

    • Become familiar with the equipment and its operation.
    • Isolate system electrically.
    • Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protective equipment is available and being used correctly; The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders conform to the appropriate standards.
    • Pump down refrigerant system, if possible.
    • If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
    •  Make sure that cylinder is situated on the scales before recovery takes place
    • Start the recovery machine and operate in accordance with manufacturer’s instructions.
    • Do not overfill cylinders. (No more than 80 % volume liquid charge).
    •  Do not exceed the maximum working pressure of the cylinder, even temporarily.
    •  When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
    • Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
  15. Labeling
    Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be
    dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

  16. Recovery
    When removing refrigerants from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shallbe in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

PRECAUTIONS AND INFORMATION

Never attempt to personally perform maintenance interventions that imply opening the machine: the presence of charged components and the gas contained in the refrigeration circuit make these operations particularly dangerous. Always contact a specialised technical assistance centre.

CAUTION

  • Always unplug the appliance prior to effecting any operation.
  • Prevent water from entering through the upper grille. Do not obstruct the air flow.
  • Never use the dehumidifier outdoors.
  • Do not use the appliance in places where corrosive vapours or dangerous substances are present.
  • Do not place objects on top of the appliance.
  • Before removing the appliance, make sure that the condensate collector tank is empty.
  • Do not pull on the power cable to turn the appliance off.
  • Never open the dehumidifier body.
  • After turning the appliance off, wait a few minutes before turning it back on.
  • Do not use the appliance on inclined surfaces.
  • Do not use extensions for the power cable.

IMPORTANT

  • Do not turn the appliance on and off continuously and avoid tilting it. If the appliance does not switch on, unplug it from the socket and contact the local dealer for assistance.
  • Do not spray insecticides or other chemical substances onto the appliance as they may cause warping of the plastic structure.
  • This dehumidifier is exclusively designed for domestic use: any other use must be regarded as improper use. Warning: the dehumidifier does not operate at temperatures below 5°C or above 32°C.

AFTER-SALES ASSISTANCE
If necessary, contact your dealer or the manufacturer’s technical assistance centre for further information.
MAINTENANCE
Dirt may sometimes build up in the dehumidifier after it has been used for several seasons, resulting in a loss of efficiency. It is important to regularly empty the condensate water deposited in the appliance and periodically perform maintenance operations; contact the local dealer for technical assistance.

HUMIDITY CONCEPTS

ARISTON=-3DEOS-16s-Dehumidifier-fig2

AIR HUMIDITY
A certain amount of water vapor is always present in the air: the air’s capacityto withhold water vapor increases with its temperature. For example, at a temperature of 26°C, the maximum humidity content is 21.4 g of water vapor per kg of air, while at 30°C, the maximum humidity content is 27.2 g of water vapor per kg of air. In actual fact, the maximum humidity contents constitute extreme cases that do not occur at our latitudes. In these conditions, air is said to be ‘saturated’ (i.e. it cannot contain any more humidity) and the water vapor begins to condense. ‘Relative humidity refers to the ratio between the air’s actual humidity and the maximum possible humidity content at that particular temperature. For example, if said temperature were to be 26°C, the actual humidity content would be 10.7 g of water vapour for each kg of air, and the relative humidity would be:

10.7 x 100
= 50%
21.4

Relative humidity is always expressed as a percentage value (%). Apart from natural causes, the air’s humidity in enclosed spaces can increase due to the number of people present, the activities being performed, etc. Both too little and too much humidity are harmful to the human body, for opposite reasons, and should thus be avoided.

PRODUCT DESCRIPTION

ARISTON=-3DEOS-16s-Dehumidifier-fig3

CONTROL PANEL

ARISTON=-3DEOS-16s-Dehumidifier-fig4

  1. ON/OFF BUTTON
    Press to switch the dehumidifier on and off. The indicator light of the ON/OFF button remains lit when the appliance i functioning and unlit when the appliance is off

  2. MODE BUTTON
    Press to select the desired operating mode: STANDARD, CONTINUOUS, AUTO or LAUNDRY. STANDARD MODE: the appliance functions until the desired humidity level is reached. CONTINUOUS MODE: the appliance functions at the maximum dehumidification level until the tank fills u In this mode, the ‘+’ and ‘­’ control buttons are not enabled (‘cont’ indicator on). AUTO MODE: the dehumidifier sets the relative humidity ( in a comfortable range of 45%-55%) in relation to the ambient temperature to maximize occupant comfort. In this mode humidity setting buttons are not enabled (‘smd’ indicator on). LAUNDRY MODES: The dehumidifier sets the fan speed to high. In this mode, the ‘+’ and ‘control’ buttons are not enabled (‘Dryer’ indicator light on).

  3. HUMIDITY SETTING BUTTONS
    The desired relative humidity level can be set to between 35% (minimum) and 80% (maximum), with 5% increments each time the ‘+’ and ‘-’ control buttons are pressed. When the set humidity level is reached, the compressor stops. The humidity setting buttons are disabled in the continuous and auto mode.

  4. HUMIDITY SETTING BUTTONS
    The desired relative humidity level can be set to between 35% (minimum) and 80% (maximum), with 5% increments each time the ‘+’ and ‘-’ control buttons are pressed. When the set humidity level is reached, the compressor stops. The humidity setting buttons are disabled in the continuous and auto mode.

  5. FAN button
    Press to select fan speed in three steps-low, med and high. The fan speed indicator light illuminates under different Press to set the start delay when the appliance is of, or the switch-off delay when it is on. The indicator light to the left of fanspeed settings, when select high fan speed, both the low and med fan speed lights illuminate.

  6. TIMER button
    the timer button will light up. Press or hold the ‘+’ and ‘-’ control buttons to set the desired delay: 30 min (0.5 hours) increments occur between 0 and 10 hours, and 1-hour increments between 10 and 24 hours. Restore the delay to 0.0 or switch off the appliance to cancel the timer function.

  7. DISPLAY

  8. WIRELESS button (available only on NET models)
    Press the WIRELESS pad for 3 seconds to initiate the Wireless connection mode. The LED DISPLAY shows AP for 8 min to indicate you can set a Wireless connection.

AUTO-RESTART
This function enables the dehumidifier to restart, after a blackout, from the last stored settings.
ANTI-FROST FUNCTION
Prevents the evaporator from frosting, thereby extending the dehumidifier’s life and enhancing energy saving. When this function is active, the fan continues to turn while the compressor stops.
TANK FULL STOPPAGE
The dehumidifier stops when the condensate collection tank is full or incorrectly positioned. ‘P2’ will appear on the display and the ‘full’ indicator light turns on.
IMPORTANT: When the compressor stops, it is necessary to wait 3 minutes before it restarts.

CONDENSATE DISCHARGE

The dehumidifier can discharge the condensate water in two different
ways:
DISCHARGE INTO TANK
The condensate water falls directly in the tank located in the lower section of the dehumidifier. When the tank fills up, the machine automatically stops functioning, the full tank indicator light switches on and ‘P2’
appears on the display.
PROCEDURE FOR EMPTYING THE TANK:

  • Pull out the tank slightly using the appropriate handles on the sides (Fig. A).
  • Pull the tank out fully while being careful not to spill the condensate water.
  • Do not place the tank on the ground as its irregular underside may cause the water to spill out.
  • Empty out the water.
  • Put the tank back into its housing. The dehumidifier will automatically start functioning again.

WARNING:

  • Do not remove the float (located inside the tank) when emptying out the water.
  • Make sure to put the tank properly back into its housing (after having emptied it).
  • Incorrect positioning of the tank may prevent the dehumidifier from starting. Check that the full tank safety indicator light is off. Before removing the tank, it is advisable to tap the top part of the dehumidifier a few times to ensure that all the water has fallen into the tank. A few drops of water may nonetheless drip down once the tank has been pulled out.
  • Before undertaking any operation on the appliance, make sure that the power supply has been disconnected.

CONTINUOUS DRAINAGE
Allows for discharging the condensate water without letting it fall into the collection tank. This function is particularly useful when the dehumidifier must be operated for long periods, making it difficult to empty the tank continuously.
INSTRUCTIONS

  • Remove the rubber cap from the right-hand outlet located on the rear of the appliance (Fig. B).
  • Connect the hose (not included) with 13.5 mm internal diameter to the outlet (Fig.C) Make sure that the other end of the hose terminates at a water collection point lying lower than the discharge outlet.
  • Switch the appliance on

CAUTION
Do not touch the selector with wet hands (risk of personal injury due to electrocution). Do not start or stop the appliance by simply plugging it into the power socket or unplugging it (risk of personal injury due to electrocution). Avoid prolonged direct exposure to the air flow (risk of personal injury due to sensitisation of the skin).

POSITIONING TIPS

ARISTON=-3DEOS-16s-Dehumidifier-fig11

For the correct operation of your dehumidifier, we advise you to observe the distances shown in Fig. D. Position the dehumidifier on a stable, smooth and horizontal surface. The appliance can be moved using the wheels. Before moving the appliance, disconnect the power supply and empty the condensate collection tank.

BASIC MAINTENANCE

Before cleaning the appliance, unplug it and disengage the automatic switch.
CLEANING THE DEHUMIDIFIER

  • Clean the dehumidifier using a cloth dampened in lukewarm water (no more than 40°C) and neutral soap. Do not use solvents or aggressive detergents.
  • Do not spray water directly onto the appliance.

CLEANING THE TANK
Clean the condensate collection tank regularly (every 2-3 weeks) in order to prevent mold and bacteria build-up. Use water and non-aggressive detergents.
CLEANING THE FILTERS
Dust filter
Cleaning the filter regularly (to be performed at least every 30 days) is essential to ensure optimal dehumidifier performance.

  • Remove the rear grille by raising the lower part and sliding it out downwards (Fig. E).
  • Remove the filter from the grille and clean it using a vacuum cleaner or wash it with lukewarm water and neutral detergent.
  • Dry it thoroughly (do not leave it exposed to sunlight).
  • Put the filter and grille back in place.

Anti-odour filter
(removes bad odours and volatile organic compounds)

  • Remove the anti-odour filter from its appropriate housing on the dust filter.
  • Replace the filter every 24 months.

WARNING
Do not use the dehumidifier without the dust filter.
END-OF-SEASON MAINTENANCE

  1. Remove any condensate water present in the tank.
  2. Clean the appliance, tank and dust filter.
  3. Cover the appliance to protect it against dust.
  4. Store the dehumidifier in a dry and well-ventilated place.

IN CASE THE DEHUMIDIFIER MALFUNCTIONS

BEFORE CONTACTING THE TECHNICAL ASSISTANCE CENTRE, PERFORM THE FOLLOWING CHECKS:

PROBLEM CAUSE SOLUTION
The appliance does not start by pressing the ON/OFF button. 1)    The plug is

not properly inserted.

2)       The main switch is not properly inserted.

3)      The tank full indicator light is lit.

4)        The tank is either full or not properly in- serted.

| 1)    Insert the plug correctly.

2)       Check the main switch.

3)      Empty the tank.

4)      Put the tank properly back into place.

The appliance is not able to dehumidify the room enough.| 1)      The air inlet or outlet are obstructed (by curtains, objects, walls, etc.).

2)       The set humidity level is not low enough.

3)       The windows and doors of the room are not closed.

4)       The room temperature is either too low (lower than 5°C) or too high (above 32°C).

5)       The air filter is clogged.

| 1)    Free the air inlet and outlet.

2)       Appropriately adjust the humidity level.

3)      Close all windows and doors.

  1. Clean the air filter.

The appliance is very noisy.| 1)    The air filter is clogged.

2)       The appliance is inclined.

3)      The appliance is resting on a non-flat sur- face.

| 1)    Clean the air filter.

2)       3) Reposition the appliance.

‘P2’ appears on the display.| Tank full.| Empty the tank and put it correctly back in place.
‘AS’ appears on the display.| The humidity sensor is disconnected or has short-circuited.| Contact the technical assistance service.
‘ES’ appears on the display.| The temperature sensor is disconnected or has short-circuited.| Contact the technical assistance service.

PRODUCT TECHNICAL SHEET

Type of appliance Dehumidifier
Supplier brand ARISTON
DEOS 16s NET
--- ---
Dehumidification(1) litres/day
Power consumption(1) (max) W
Sound pressure(1) dB(A)
Type of refrigerant
GWP(2)
Operating temperature °C
Tank capacity litres
Power supply and no. of phases Hz – V – Ph
Type of compressor
Maximum air flow rate m3/h
Standard refrigerant charge kg
Dimensions mm
Weight (net/gross) kg
  1. Relative to operation at 30°C and 80% relative humidity.
  2. Refrigerant loss contributes to climate change. In the case of their release into the atmosphere, refrigerants with lower global warming potential (GWP) have less impact on global warming compared to refrigerants with a higher GWP. This appliance contains a refrigerant fluid with a GWP of 3. In other words, if 1 kg of this refrigerant fluid were released into the atmosphere, the impact on global warming would be 3 times greater compared to 1 kg of CO2, over a period of 100 years. In no case whatsoever must the user attempt to intervene on the refrigerant circuit or dismantle the product. In case of need, please contact a qualified professional.

Ariston Thermo UK Ltd.
Artisan Building • Hillbottom Road
High Wycombe • HP12 4HJ
UNITED KINGDOM
Ariston Thermo SpA
Viale A. Merloni, 45 • 60044 Fabriano (AN) – ITALY
ariston.com
Customer Service 0333 240 8777 Call charges depend on your agreement with your network provider.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Ariston User Manuals

Related Manuals