RUUD RP14AZ Endeavor Line Achiever Series iM Heat Pumps Instruction Manual

June 12, 2024
RUUD

Heat Pumps
RP14AZ

Endeavor™ Line Achiever ® Series

iM Heat Pumps

RUUD RP14AZ Endeavor Line Achiever Series iM Heat
Pumps

RP14AZ

Cooling Efficiencies up to: 14.3 SEER2/10.4 EER2
Heating Efficiency: 7.6 HSPF
Nominal Sizes: 1.5 to 5 Tons [5.3 to 17.6 kW] Cooling & Heating Capacities: 17.1 kBTU to 55.5 kBTU


FORM NO. P22-828 REV. 2

Features and Benefits
  • Swept Wing Fan Technology¹: Features quieter operation and improved unit acoustics
  • Two-Stage Scroll Compressor²: Features two speeds (high and low) of cooling and heating, providing more precise temperature control, lower humidity and greater efficiency when compared to single stage compressors
  • Inverted Reversing Valve: Allows for faster heat transfer with gravity assist shifting and reduced joint stress for increased reliability
  • PlusOne® Expanded Valve Space: 3 in. – 4 in. – 5 in. service valve space—provides a minimum working area of 27-square inches for easier access
  • PlusOne® Triple Service Access: 15 in. wide, industry leading corner service access, two fastener, removeable corner and individual louver panels—makes repairs easier and faster

¹Does not apply to the 3.5 and 4 Ton
²Does not apply to the 1.5 Ton 1-stage model

Heat Pumps
R Brand R – Ruud
P Product Category P – Heat Pump
14 SEER2 14 – 14.3 SEER2
A Region A – All Regions
Z Refrigerant Z – R-410A
18 Capacity 18 – 18,000 [5.28 kW] 24 – 24,000 [7.03 kW] 30 –

30,000 [8.79 kW] 36 – 36,000 [10.55 kW] 42 – 42,000 [12.31 kW] 48 – 48,000 [14.07 kW] 60 – 60,000 [17.58 kW]
A| Major Series| A – 1st Design
J| Voltage| J – 208/230/1/60
1| Type| 1 – 1-Stage
2 – 2-Stage
N| Controls| N – Non-Comm.
A| Minor Series| A – 1st Design

[ ] Designates Metric Conversions

AVAILABLE MODELS

|

DESCRIPTION

---|---

RP14AZ18AJ1NA

| Endeavor™ Line Achiever ® Series 1 1/2 ton 14.3 SEER2 1-Stage iM Heat Pump-208/230/1/60

RP14AZ18AJ2NA

| Endeavor™ Line Achiever ® Series 1 1/2 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

RP14AZ24AJ2NA

| Endeavor™ Line Achiever ® Series 2 ton 14.3 SEER2 2-Stage Heat iM Pump-208/230/1/60

RP14AZ30AJ2NA

| Endeavor™ Line Achiever ® Series 2 1/2 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

RP14AZ36AJ2NA

| Endeavor™ Line Achiever ® Series 3 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

RP14AZ42AJ2NA

| Endeavor™ Line Achiever ® Series 3 1/2 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

RP14AZ48AJ2NA

| Endeavor™ Line Achiever ® Series 4 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

RP14AZ60AJ2NA

| Endeavor™ Line Achiever ® Series 5 ton 14.3 SEER2 2-Stage iM Heat Pump-208/230/1/60

STANDARD EQUIPMENT


R-410A Refrigerant
Scroll Compressor
Field Installed Filter Drier
Front Seating Service Valves
Internal Pressure Relief Valve
Internal Thermal Overload
Long Line capability
Low Ambient capability with Kit
3-4-5 Expanded Valve Space
Composite Basepan
2 Screw Control Box Access
15″ Access to Internal Components
Quick release louver panel design
No fasteners to remove along bottom
Optimized Venturi Airflow
Single row condenser coil
Powder coated paint
Rust resistant screws
QR code
External gauge ports
Service trays
External gauge ports
Service trays

General Data

RUUD RP14AZ - Table 1

Electrical Data

RUUD RP14AZ - Table 2

¹Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.

Accessories

RUUD RP14AZ - Table 3

*Bi-flow kits are required when installing a liquid line solenoid on a heat pump.

Weighted Sound Power Level (dBA)

UNIT SIZE – VOLTAGE, SERIES

| STANDARD RATING (DBA)| TYPICAL OCTAVE BAND SPECTRUM (dBA without tone adjustment)
---|---|---
125| 250| 500| 1000| 2000| 4000|

8000

RP14AZ18A

| 73| 39.8| 55| 62.1| 67.0| 60.0| 57.4| 51.2
RP14AZ24A| 73| 40.4| 55.4| 62.5| 65.9| 58.7| 56.4|

48.9

RP14AZ30A

| 72| 48.9| 55.3| 63.6| 61.0| 59.1| 56.5| 48.7
RP14AZ36A| 72| 50.1| 55.8| 64.4| 61.5| 58.7| 55.1|

50.9

RP14AZ42A

| 72| 48.6| 56.2| 63.1| 61.7| 60.0| 56| 50.0
RP14AZ48A| 74| 49.3| 56| 64.5| 64.5| 60.1| 54.9|

47.7

RP14AZ60A

| 74| 43.9| 55.2| 63.4| 65.8| 61.7| 57.9|

52.9

NOTE: Tested in accordance with AHRI Standard 270-08 (not listed in AHRI)

Unit Dimensions

RUUD RP14AZ - Table 5

RUUD RP14AZ - Unit Dimensions

  1. ALLOW 60″ [1524 mm] OF CLEARANCE

  2. SERVICE PANELS/INLET CONNECTIONS / HIGH & LOW VOLTAGE ACCESS
    ALLOW 24″ [610 mm] OF CLEARANCE

  3. AIR INLET LOUVERS ALLOW
    6″ [152 mm] MIN. OF CLEARANCE ALL SIDES
    12″ [305 mm] RECOMMENDED

ST-A1226-02-00

[ ] Designates Metric Conversions

CLEARANCES

RUUD RP14AZ - CLEARANCES 3

NOTE: NUMBERS IN () = mm

IMPORTANT: When installing multiple units in an alcove, roof well or partially enclosed area, ensure there is adequate ventilation to prevent re-circulation of discharge air.

ST-A1225-01-00

Control Wiring

FIGURE 4
CONTROL WIRING FOR AIR HANDLER

NOTES:

  1. Jumper “E” to “W2” to transfer control of supplemental heat to 1st stage when the emergency heat switch is on.
  2. This wire turns on heat for defrost, omit for most economical operation.
  3. Wire with colored tracing stripe.

RUUD RP14AZ - Control Wiring

  1. TYPICAL THERMOSTAT:
    HEAT PUMP WITH ELECTRIC HEAT

WIRING INFORMATION
Line Voltage
-Field Installed 
-Factory Standard

NOTE: RED WIRE REQUIRED WITH RANCO DDL DEMAND DEFROST CONTROL.

Application Guidelines
  1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.
  2. Minimum outdoor operation air temperature for cooling mode without low-ambient operation accessory is 55°F (12.8°C).
  3. Maximum outdoor operating air temperature is 125°F (51.7°C).
  4. For reliable operation, unit should be level in all horizontal planes.
  5. Use only copper wire for electric connections at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
  6. Do not apply capillary tube indoor coils to these units.
  7. Factory-supplied filter drier must be installed.
Refrigerant Line Size Information

RUUD RP14AZ - Table 6

RUUD RP14AZ - Table 7

NOTES:

  1. Do not exceed 200 ft linear line length.
  2. *Do not exceed 100 ft vertical separation if outdoor unit is above indoor unit.
  3. Always use the smallest liquid line allowable to minimize refrigerant charge.
  4. Applications shaded in light gray indicate capacity multipliers between 0.90 and 0.96 which are not recommended, but are allowed.
  5. Applications shaded in dark gray are not recommended due to excessive liquid or suction pressure drop.
Performance Data @ AHRI Standard Conditions – Cooling

RUUD RP14AZ - Table 8

NOTE: This data includes DTC (Designated Test Combination) ratings and is for reference purposes only. A full listing of official ratings and system match-ups, along with downloadable certificates, will be accessible from the AHRI website: www.ahridirectory.org later this year.

[ ] Designates Metric Conversions

Notes

**GENERAL TERMS OF LIMITED WARRANTY***

Ruud will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.

*For complete details of the Limited and Conditional Warranties, including applicable terms and conditions, contact your local contractor or the Manufacturer for a copy of the product warranty certificate.

Conditional Parts
(Registration Required)……………………………Ten (10) Years

Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.

© 2023 Rheem Manufacturing Company. Ruud trademarks owned by Rheem Manufacturing Company.

In keeping with its policy of continuous progress and product improvement, Ruud reserves the right to make changes without notice.

Ruud Heating, Cooling & Water Heating • 5600 Old Greenwood Road
Fort Smith, Arkansas 72908 • www.ruud.com

Ruud Canada Ltd./Ltée • 125 Edgeware Road, Unit 1
Brampton, Ontario • L6Y 0P5 • ruud-canada.ca


PRINTED IN U.S.A. 4/23 QG FORM NO. P22-828 REV. 2

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

RUUD User Manuals

Related Manuals