MEAN WELL LCM-40DA LED Driver Installation Guide
- June 12, 2024
- MEAN WELL
Table of Contents
LCM-40(DA), LCM-60(DA)
installation manual
Features
- 180~295VAC input only
- Built-in active PFC
- Output current level selectable by DIP switch
- Built-in DALI interface and push dimming function (DA version)
- Built-in 0~10Vdc and PWM signal dimming function (Non-DA version)
- Power supply synchronization function up to 10 units
- Temperature compensation function by external NTC
- Class Ⅱ power unit, ungrounded
- Built-in 12V/50mA auxiliary output
- Full plastic case enclosed
- No load power consumption <1W (1.2W for DA version)
- Protection s: Short circuit / Over voltage / Over temperature
- 3 year warranty
- Suitable for intelligent LED lighting
Wiring
- Housing with cable clamp for remote installation
- Use wires with an adequate cross-section (see 5)
- Use suitable mounting tools to do the wiring and mounting (see 5)
- Use a MCB (miniature circuit breaker) with an adequate current rating to protect the lighting system (see 6)
Environmental limitations
- Maximum ambient temperature must not exceed 60℃
- Always allow adequate ventilation clearances, 50mm, around the unit in use to prevent it from overheating
- Only install the unit in interior environments
Cautions
- This unit must be installed by a qualified electrician
- This unit is not suitable for applications that DC/DC converters are connected before LED lamps
Settings and connections
- Output Current Level Settings
The LCM can provide various output currents by setting the DIP switch. The settings of the DIP switch are shown in the tables below.Voltage ran ge| Sel ectable Current| 1| 2| 3| 4| 5| 6
---|---|---|---|---|---|---|---
2-1 00V| 35 0mA| —| —| —| —| —| —
2-8 0V| 50 0mA| ON| —| —| —| —| —
2-6 7V| 60 0mA| ON| ON| —| —| —| —
2-5 7V| 70 0mA*| ON| ON| ON| —| —| ON
2-4 5V| 90 0mA| ON| ON| ON| ON| —| ON
2-4 0V| 1050mA| ON| ON| ON| ON| ON| ON
LCM-60(DA)
Voltage ran ge | Sel ectable Current | 1 | 2 | 3 | 4 | 5 | 6 |
---|---|---|---|---|---|---|---|
2-90V | 50 0mA | — | — | — | — | — | — |
2-90V | 60 0mA | ON | — | — | — | — | — |
2-86V | 700mA* | ON | ON | — | — | — | — |
2-67V | 90 0mA | ON | ON | ON | — | — | ON |
2-57V | 10 50mA | ON | ON | ON | ON | — | ON |
2-42V | 14 00mA | ON | ON | ON | ON | ON | ON |
Note: 1. Factory default setting is 700mA.
2. Output voltage and output wattage must not exc eed the rated values.
Terminal blocks assignment for LCM
- Connection of LED Lamps
** Press down the “push bu tton” by a slotted screw driver to insert or remove the cable. Connection of Dimming Functions
a. 0-10Vdc or 10V PWM (non-DA version only) b. DALI (DA version only) Note: Maximum DALI cable length is 300m (based on a 1.5mm² or 14AWG cable)
c. Push dim (DA version only) Note: ON LY use open push button witho ut indicator light.
Warning:** Risk of short circuit. The push button can only be linked betwee n the PUSH and the AC/L (brown or black).
DO NOT connect the push button to the AC/N (blue or white).
Dimming control mechanism
Function | Pushing time |
---|---|
Turn ON/OFF | 0.1 ~ 1 sec |
Dim UP/DOWN | 1.5 ~ 10 sec |
Reset | > 11 sec |
None | < 0.05 sec |
– It will always dim up when light intensity is lower than 10%, whe reas it
will always dim down when light intensity is higher than 90%
– Factory dimming setting: 100%
d. Synchronization operation
The lights driven by LCM units (slaves) can be dimmed synchronously through a
LCM unit (the master) directly controlled via 0-10Vdc, 10V PWM, DALI or push
dim dimming function. The wiring is shown as below.– Mating housing for SYN.
connectors : JST B2B-XH or equivalent
– Maximum number of the LCM units : 10 (1 master + 9 slaves)
– Maximum cable length between each units : 20m (based on a cable with cross-
section of 0.15mm² ~0.3mm² or AWG No. of 22 ~ 26)
Note 1: DO NOT connect dimming circuitry to slaves.
Note 2: Please make sure all units are set to 100% dimming setting
(factory default) before synchronizing.
- NTC Connection
- Recommended Screwdriver, Wire and Torque Setting
Type| The cover (the blue one)| Scr ew ter minal
(FAN±, NT C±, DIM±)| Push ter minal
(ACL/N, PUSH, DA±, Vo±)
---|---|---|---
Solid wire| —–| ψ0.404 -ψ0.643 mm| ψ1. 024 -ψ1.628mm
Stranded wire| —–| 0.12 9 – 0.3 26mm²| 0.823 – 2.08 mm²
Ameri can wire gauge| —–| 22 – 26AWG| 14 – 1 8AWG
Wire stripping length| —–| 7mm (0.27″)| 10mm (0.39″)
Screwdriver| 6mm Phillips| 3mm Philli ps| 3mm Phillips
Recommended tightening torque| 4.6 kgf-cm ( 4 lb-in)| 2.88 kgf-cm (2.5 lb-in)| —–
Suggested push-down strength| —–| —–| 3 – 4 kp (6.61-8.81 lbF) - Suggested Maximum Number of the LCM Units that can be Connected to a MCB (miniature circuit breaker) at 230Vac**
Model| B10| B16| C10| C16**
---|---|---|---|---
LCM-40(DA)| 10| 16| 17| 28
LCM-60(DA)| 9| 15| 16| 26
Note: These calculated values are based on MCB S201 series manufactured by ABB.