Product Information
The product is a splice kit, specifically designed for use with F-10, T-18, and T-18 CT cables. It is used for joining cables together and ensuring proper insulation and connection.
Product Usage Instructions
- Slide both shrink tubings provided onto the cables. Use 1 piece of 12 mm shrink tubing with a length of 180 mm and 1 piece of 9 mm shrink tubing with a length of 110 mm.
- Strip off 60 mm of the outer sheath of the cable, and cut away the earth, leaving a maximum of 10 mm.
- Twist the earth wire and secure it in place with an uninsulated terminal.
- Strip away 30 mm of the inner insulation from the cable.
- Make 2 cuts in the semi-conductor material leading to the conductors.
- Pull the conductors apart or cut between them.
- Slide on both 3 mm shrink tubings and then the 9 mm shrink tubing, following the illustration provided. The 9 mm shrink tubing should be 15 mm long.
- Heat the shrink tubings with a hot air gun, and then squeeze them together between the conductors using a flat plier.
- Strip 6 mm off the conductors.
- Repeat steps 2 to 9 with the other cable.
- Splice the cables together using the insulated shrink-tubing terminals. Heat the splice with a hot air gun so that the shrink tubings shrink and the adhesive is pressed out.
- Pull 9 mm of shrink tubing over the splice and heat it. Use a piece of 9 mm shrink tubing with a length of 110 mm.
- Insulation test the cable, ensuring a minimum of 10 M resistance.
- Always heat the shrink tubings until the adhesive is pressed out. Do not lay a spliced cable inside a water pipe.
- Wrap electrical tape over the splice to make it even.
- Pull 12 mm of shrink tubing over the splice and heat it. Use a piece of 12 mm shrink tubing with a length of 180 mm.
For further assistance or inquiries, you can contact Ebeco at:
- Phone: +46 (0)31-707 75 50
- Fax: +46 (0)31-707 75 60
- Email: info@ebeco.se
- Website: ebeco.com.
Package Contents
- 1 pc 12 mm shrink tubing, L=180 mm
- 1 pc 9 mm shrink tubing, L=110 mm
- 2 pc 9 mm shrink tubings, L= 15 mm
- 4 pc 3 mm shrink tubings, L= 25 mm
- 2 pc insulated crimp terminals 1,5 mm²
- 2 pc uninsulated terminals 1,5 mm²
Mounting Instructions
- Slide both shrink tubings on the cables.
- 1 pc 12 mm L = 180 mm
- 1 pc 9 mm L = 110 mm
- Strip off 60 mm of the outer sheath, and cut away the earth leaving a maximum of 10 mm.
- Twist the earth, and squeeze in place an uninsulated terminal.
- Strip away 30 mm of the inner insulation
- Make 2 cuts in the semi-con-ductor material leading to the conductors.
- Pull the conductors apart or cut between the conductors.
- Slide on both 3 mm shrink tubings and then the a 9 mm skrink tubing, 15 mm long according to the illustration.
- Heat with a hot air gun, and then squeeze together between the conductors with a flat pliers.
- Strip 6 mm off the conductors.
- Repeat the step 2 to 9 with the other cable.
- Splice the cables together with the insulated shrink tubing terminals. Heat with a hot air gun so that the shrink tubings shrink and the adhesive is pressed out.
- Pull 9 mm of shrink tubing over the splice, and heat.
- 1 pc 9 mm L = 110 mm
- Splice the earth together with a 1.5 mm² piece of insulating cable.
- Wrap electrical tape over the splice to make it even.
- Pull 12 mm of shrink tubing over the splice, and heat.
- 1 pc 12 mm L = 180 mm
- Insulation tests the cable, min 10 MΩ.
Always heat the shrink tubings until the adhesive is pressed out. Do not lay a spliced cable inside a water pipe.