S S REGELTECHNIK ALTM2-EtherCAT P Surface Contact Temperature Measuring Transducer Pipe Instruction Manual
- June 12, 2024
- S S REGELTECHNIK
Table of Contents
6000-3840-0000-1XX 38400-2022 V101 05 ⁄ 2022
THERMASGARD® ALTM2 – EtherCAT P
Operating Instructions, Mounting & Installation
Surface-contact temperature measuring transducer ⁄ pipe surface-contact sensor, with detached sensor, incl. strap, Bluetooth-enabled, with EtherCATP port
Dimensional drawing
M8-plug-in connector
EtherCATP-encoded
High-performance encapsulation against vibration, mechanical stress and
humidity
PERFECT SENSOR PROTECTION
Networkable surface-contact temperature measuring transducer (detached version) THERMASGARD® ALTM2 – EtherCATP with M8 plug-in connector (EtherCATP- encoded), Bluetooth-enabled, in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without display and bar graph, cable sensor with pipe feeder, incl. strap. The pipe surface-contact sensor is used to detect the temperature on lines, pipes (e.g. cold and warm water) or on heating sections for heating control. The sensor is factory-calibrated. EtherCATP-enabled measuring transducer for industrial requirements with maximum reliability: includes easy PLC integration using the device’s ESI configuration file, diagnostics (such as communication failure counter), advanced settings options, access to historical data (min / max) and estab- lishing the sensor’s service interval. Optionally with large illuminated display (3-line, customised programming in the 7-segment and dot-matrix range) and bar graph (7-digit, LEDs freely configurable) for graphical display, e.g., as a traffic light indicator.
TECHNICAL DATA
Power supply: | 24V DC via EtherCATP (Us) |
---|---|
Power consumption: | < 3W |
Bus protocol: | EtherCAT |
Radio technology: | Bluetooth (LE) |
Sensor: | Pt1000, DIN EN 60751, class B (Perfect Sensor Protection at IP68) |
Measuring range: | —50…+150°C |
Deviation in temperature: | typically ± 0.2 K at +25°C |
Medium: | clean air and non-aggressive, non-combustible gases |
Sensor protection: | pipe feeder made of stainless steel V4A (1.4571), 0=6mm, |
L=50mm
Sensor cable:| silicone, SiHF, 2 x0.25 mm2; cable length (KL) =1.5m (other
lengths and jacket materials, e.g. PTFE or glass fibre with steel mesh,
available on request)
Housing:| Plastic, UV-resistant, polyamide material, 30% glass-globe
reinforced, with quick-locking screws (slotted/Phillips head combination),
colour traffic white (similar to RAL 9016), housing cover for display is
transparent!
Dimensions:| 126 x 90 x 50mm (Tyr 2)
Cable connection:| M8 plug-in connector, EtherCATP-encoded
Process connection:| Endless strap with metal tightener (included in delivery
scope), 0=13-92mm 0/4-31, L=300mm
Ambient temperature:| Measuring transducer —30~70°C
Permitted humidity:| <95% r. H., non-precipitating air
Protection class:| III (according to EN 60730)
Protection type housing:| IP54 (according to EN 605291
Protection type sensor:| IP65 (according to EN 60529) sleeve humidity-tight
(standard) IP68 (according to EN 60529) sleeve water-tight (optional)
Standards:| CE conformity, according to EMC Directive 2014/30/EU, according to
RED 2014/53/EU
Equipment:| Display with illumination, 3-line, customised programming, cutout
approx. W51 x H29mm, to display the actual temperature or a customised display
value.
Bar graph, 7-digit, LEDs freely configurable, to graphically display the
reading.
Surface-contact temperature measuring transducer with detached sensor, with EtherCATP port
Type/WG02| Measuring Range Temperature| Sensor| Output|
Bar graph Item No. Display
---|---|---|---|---
ALTM2•ECATP xx| | | |
ALTM2-ECATP| -50…-1-150°C| Pt1000| EtherCATP| 2001-2171-9100-001
ALTM2-ECATP LCD| -50…-1-150°C| Pt1000| EtherCATP| 2001-2172-9100-001
Extra charge: Protection type IP 68 (sensor sleeve watertight compound- filled) per running metre of connecting lead (silicone / PTFE / glass fibre) on request
ACCESSORIES
WLP-1 | Heat-conductive paste, silicone-free | 7100-0060-1000-000 |
---|
Use the EtherCAT interface to program the LCD display.
With only one output value selected, the display is static; with several
values selected, the display is cyclical with one after the other. In the
first line the value is displayed and in the second line the corresponding
unit. The third line is empty by default if there are no customised inputs.
The entire display in the 7-segment range as well as in the dot-matrix range
can be customised.
When the supply voltage is applied, the device performs a function test for
the display and bar graph.
This takes approximately 30 seconds, after which the device is ready for
operation.
In the absence of a bus connection to the device, the message “ERR no link”
appears in the display.
Ether CAT P | LED status display |
---|---|
1. LED | IN |
off | no connection to upstream EtherCAT module |
illuminated | LINK: connection to upstream EtherCAT module |
blinking | ACT: communication with upstream EtherCAT module |
2. LED | OUT |
off | no connection to downstream EtherCAT module |
illuminated | LINK: connection to downstream EtherCAT module |
blinking | ACT: communication with downstream EtherCAT module |
3. LED | RUN |
off | EtherCAT module is in “Init” state |
quickly blinking | EtherCAT module is in “Pre-Operational” state |
slowly blinking | EtherCAT module is in “Safe-Operational” state |
illuminated | EtherCAT module is in “Operational” state |
The status LEDs are next to the cable connection.
Installation and Commissioning
Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations
andstandards applicable for the place of measurement (e.g. such as
weldinginstructions, etc.). Particularly the following shall be regarded:
– VDE ⁄ VDI directive technical temperature measurements, measurement set – up
for temperature measurements.
– The EMC directives must be adhered to.
– It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with the shielding being attached at one
side to the DDC ⁄ PLC.
Before mounting, make sure that the existing thermometer‘s technicalparameters
comply with the actual conditions at the place of utilization, in particular
in respect of:
– Measuring range
– Permissible maximum pressure, flow velocity
– Oscillations, vibrations, shocks are to be avoided (< 0.5 g)
– Ensure not to kink or squash the sensor element
SAFETY REGULATIONS
These devices shall only be used for their intended purpose. Respective safety
regulations issued by the VDE, the states, their control authorities, the TÜV
and the local energy supply company must be observed. The buyer has to ensure
adherence to the building and safety regulations and has to avoid all dangers
of any kind. We do not assume any warranty for faults or damages arising or
resulting from improper use of our equipment or from non-observance of
operating instructions. These instruments must be installed by authorised
specialists only!
Preferably shielded cables should be used in order to prevent damages ⁄
errors. It is imperative to avoid laying parallel with current-carrying lines.
EMC directives must be adhered to.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions.
When operating under deviating conditions, we recommend performing an initial
manual adjustment on-site during commissioning and subsequently at regular
intervals.
Commissioning is mandatory and may only be performed by qualified personnel!
If the sensor element’s admissible load limits are exceeded, ensure to use an
adequate support structure.
Important notes
Our “General Terms and Conditions for Business“ together with the “General
Conditions for the Supply of Products and Services of the Electrical and
Electronics Industry“ (ZVEI conditions) including supplementary clause
“Extended Retention of Title“ apply as the exclusive terms and conditions.
In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation
and all notes provided therein are to be regarded!
– A suitable weather and sun protection hood must be used when installed
outdoors.
– Devices must only be connected to safety extra-low voltage and under dead-
voltage condition.
To avoid damages and errors the device (e.g. by voltage induction) shielded
cables are to be used, laying parallel with current-carrying lines is to be
avoided, and EMC directives are to be observed.
– This device shall only be used for its intended purpose. Respective safety
regulations issued by the VDE, the states, their control authorities, the TÜV
and the local energy supply company must be observed.
The purchaser has to adhere to the building and safety regulations and has to
prevent perils of any kind.
– No warranties or liabilities will be assumed for defects and damages arising
from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from
warranty or liability.
– These devices must be installed and commissioned by authorised specialists.
– The technical data and connecting conditions of the mounting and operating
instructions delivered together with the device are exclusively valid.
Deviations from the catalogue representation are not explicitly mentioned and
are possible in terms of technical progress and continuous improvement of our
products.
– In case of any modifications made by the user, all warranty claims are
forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or
be exposed to their heat flow.
Direct sun irradiation or heat irradiation by similar sources (powerful lamps,
halogen spotlights) must absolutely be avoided.
– Operating this device close to other devices that do not comply with EMC
directives may influence functionality.
– This device must not be used for monitoring applications, which serve the
purpose of protecting persons against hazards or injury, or as an EMERGENCY
STOP switch for systems or machinery, or for any other similar safety-relevant
purposes.
– Dimensions of housing or housing accessories may show slight tolerances on
the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing
will be accepted.
These instructions must be read before installation and commissioning and all
notes provided therein are to be regard!
© Copyright by S+S Regeltechnik GmbH
Subject to errors and technical changes. All statements and data herein
represent our best knowledge at date of publication. They are only meant to
inform about our products and their application potential, but do not imply
any warranty as to certain product characteristics. Since the devices are used
under a wide range of different conditions and loads beyond our control, their
particular suitability must be verified by each customer and/or end user
themselves. Existing property rights must be observed. We warrant the
faultless quality of our products as stated in our General Terms and
Conditions.
S+S REGELTECHNIK GMBH
THURN-UND-TAXIS-STR. 22
90411 NÜRNBERG ⁄ GERMANY
FON +49 (0) 911 ⁄ 5 19 47-0
mail@SplusS.de
www.SplusS.de
Documents / Resources
| S S
REGELTECHNIK ALTM2-EtherCAT P Surface Contact Temperature Measuring Transducer
Pipe
[pdf] Instruction Manual
ALTM2-EtherCAT P Surface Contact Temperature Measuring Transducer Pipe,
ALTM2-EtherCAT P, Surface Contact Temperature Measuring Transducer Pipe,
Temperature Measuring Transducer Pipe, Measuring Transducer Pipe, Transducer
Pipe
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>