ICM CONTROLS ICM493 Programmable Single-Phase Voltage Monitor Installation Guide
- June 12, 2024
- ICM CONTROLS
Table of Contents
ICM CONTROLS ICM493 Programmable Single-Phase Voltage Monitor Installation
Guide
INSTALLATION
-
Remove cover by extracting the screw from the bottom of the enclosure.
-
Remove desired size knock-outs for conduit from the enclosure (1/2” or 3/4”).
-
Mount the enclosure to the desired surface.
-
Attach input and output conduit, apply strain relief.
-
Tilt front panel diagonally and insert the panel into the enclosure, as shown in Figure 1.
-
Lay the front panel horizontally in the enclosure and align the holes on the side, as shown in Figure 2.
-
Using the two larger screws, included in the kit, and a screwdriver, attach the front panel to the enclosure.
-
Wire L1 and L2 directly to the contactor input and output, as shown in Figure 3.
-
Close the hinged plate and secure the upper right corner into the bracket with the small screw provided in kit.
-
Once settings have been configured, attach cover and secure with screw.
CALIBRATION FEATURE
The ICM493 can be calibrated to match the reading from a true RMS meter.
- Measure input voltage from T1 to T2 using a true RMS meter.
- Hold buttons simultaneously until line voltage starts to flash.
- Adjust voltage using buttons to match measured voltage from step 1.
- Push button to lock values into memory.
SPECIFICATIONS
Input:
- 180-264 VAC
- 50/60 Hz
Contact Ratings:
- Voltage: 240 VAC
- FLA: 40A
- LRA: 240A
Control Operating Temperature:
- Operating Temperature: -40°F to 167°F (-40°C to 75°C)
- Storage Temperature: -40°F to 185°F (-40°C to 85°C)
- LCD Operating Temperature: -4°F to 167°F (-20°C to 75°C)
Mechanical:
- Mounting: Four mounting holes in back of enclosure
- Enclosure: NEMA/Type 3R, rain-tight enclosure rated for outdoor installation
- Dimensions: 8”L x 8.25”W x 4.37”H
Parameters:
- Line Voltage: 200-240 VAC, adjustable
- Over/under voltage setting: 5%-10%, adjustable
- Anti-short cycle time delay: 0.5-10 minutes
- Number of trials: 1-5, Auto
- Number of movistors: 0-5
SETTING THE PARAMETERS
- Press the button to scroll through various user-configurable settings.
- Use the buttons to change the set point.
- When the last parameter has been set, you will return to the read screen.
BUTTON FUNCTIONS
- Press to enter setup mode, and to toggle through user-configurable settings.
- Press at any time to return to the Read screen, which will display any faults, the current line voltage, and the number of remaining MOVs.
- Press to scroll through past recorded faults. Hold for 5 seconds to clear fault memory.
- Press to adjust settings & . Hold for 2 seconds to enter line voltage calibration.
- Hold for 2 seconds to reset unit.
Parameter | Description | Range | Default | Recommended |
---|---|---|---|---|
Line Voltage | The expected line voltage | 200-240 | 240 | Nameplate Voltage** |
Over/Under Voltage | The allowed percentage over and under the set line | |||
voltage | 5% to 10% | 10% | 10% Over/Under | |
Anti-Short Delay | The amount of time delay between the end of a fault, and | |||
closing of the contactor | 0:30 to 10:00 | 0:30 | 4 minutes | |
Reset Mode Retries | The number of retries after a fault has occurred. Auto has | |||
unlimited retries. | 1 to 5, Auto | Auto | Auto | |
Allowed MOV Fail | The number of surge devices allowed to fail while |
maintaining operation. Setting to “5” will allow operation, even when surge protection has been exhausted.| 0 to 5| 5| Set to “5” for ensured operation. Set to “4” for max. operation while ensuring surge protection.
7313 William Barry Blvd., North Syracuse, NY 13212
Phone: 315-233-5266
Fax: 315-233-5276
www.icmcontrols.com
800.365.5525 LIAF209-6