CP electronics EBDSPIR-PRM Ceiling Mounted PIR Presence Detectors Installation Guide

June 12, 2024
CP electronics

CP Electronics EBDSPIR-PRM Ceiling Mounted PIR Presence Detectors

CP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-Presence-Detectors-
PRODUCT

Product Information

Product Name: EBDSPIR-PRM
Model Number: WD930
Issue: 6
Product Type : PRM Switching PIR Presence Detector
Manufacturer : CP Electronics
Installation Guide:cpelectronics.co.uk/cp/930

Product Usage Instructions

  1. This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.
  2. To use absence detection, a retractive (momentary) switch must be connected between the 2 terminals on the diagram. Note that this will be switching the mains voltage.
  3. The unit ships with presence detection as default.
  4. Cut a 64mm diameter hole in the ceiling for installation.
  5. Strip the wires as shown in the diagram.
  6. Wire in plug/s, using the wiring diagram on page 3 as a guide. Connect the plug/s to the detector.
  7. Continue tightening the screws to secure the device in place.

Note: The above adjustments can also be made using the optional UHS5 or UNLCDHS handsets.

Warning

This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations.

Dimensions (mm)

CP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-1

Detection pattern

CP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-
Presence-Detectors-FIG-3

Wiring

CP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-4

Key

  1. Neutral
  2. Live
  3. Switched output
  4. 10A circuit protection if required
  5. Load
  6.  Momentary push-to-make switch, 230V (for absence detection) The switching channel is L-Out

Presence or absence detection

  • The unit ships with presence detection as default.
  • To change over to absence detection, press and release the external switch 5 times within the first minute of power up.
  • The LED will turn on red for 30 seconds to indicate absence mode has been selected.
  • To change back to presence detection, repeat the above procedure – the LED will flash red for 30 seconds to indicate presence mode has been selected.
  • To use absence detection a retractive (momentary) switch must be connected between the 2 terminals on the diagram. Note that this will be switching mains voltage.
  • Note: the above adjustments can also be made using the optional UHS5 or UNLCDHS handsets.

Installation

  • This device is designed to be flush ceiling-mounted.
  • Do not site the unit where direct sunlight might enter the sensor.
  • Do not site the sensor within 1m of any lighting, forced air heating, or ventilation.
  • Do not fix the sensor to an unstable or vibrating surface.
  • Occupancy is best detected when the ambient temperature is different from that of the human body, thus, use within -20 to 35ºC ambient temperature

Create cut out

  • Cut a 64mm diameter hole in the ceiling

Wire stripping

  • Strip the wires as shown opposite. The presence detector does not require an earth conductor

Wire in plugs & connect to the detector

  • Wire in plug/s, using the wiring diagram on page 3 as a guide. Connect the plug/s to the detector.

Clamp cable

  • Continue tightening the screws until the clamp bar snaps out and is tightly engaged against the cable/s. The cable clamp must clamp the outer sheath only

Install detectorCP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-9

  • Bend the springs up and push the detector through the hole in the ceiling. When fully inserted the springs snap back to hold the device in place.
  • To avoid injury, take care when bending springs.

Default Settings

  • Time out: 20 minutes.
  • LUX on level: 999
  • LUX off level: 999
  • Sensitivity on: 9
  • Sensitivity off: 9
  • Detection: Presence
  • Adjustments can be made using the optional UHS5 or UNLCDHS handsets.

Testing

Presence Detection

  1. Power up the sensor. The load should come on immediately.
  2. Vacate the room or remain very still and wait for the load to switch off (this should take less than 20 minutes).
  3. Enter the room or make some movement and check that the load switches on.

Absence Detection

  1. Power up the sensor. Switch the load on.
  2. Vacate the room and wait for the load to switch off (this should under than 20 minutes).
  3. Enter the room, the load will remain off until you switch it on again.

Technical Data

CP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-Presence-
Detectors-FIG-12

Accessories

Part Number/ DescriptionCP-electronics-EBDSPIR-PRM-Ceiling-Mounted-PIR-
Presence-Detectors-FIG-13

  • Surface mounting box
  • Surface mount back box extender
  • Pre-drilled 64mm hole IP65 detector enclosure
  • Extended wiring housing
  • Masking shields for the EBDSPIR range
  • Compact, programming/commissioning handset
  • Compact, user handset
  • Universal LCD IR handset/commissioning handset
  • CP Electronics
  • Brent Crescent, London NW10 7XR
  • t. +44 (0)333 900 0671
  • enquiry@cpelectronics.co.uk
  • www.cpelectronics.co.uk Connect with us
  • Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
  • cpelectronics.co.uk/cp/pa

Documents / Resources

| CP electronics EBDSPIR-PRM Ceiling Mounted PIR Presence Detectors [pdf] Installation Guide
EBDSPIR-PRM Ceiling Mounted PIR Presence Detectors, EBDSPIR-PRM, Ceiling Mounted PIR Presence Detectors, Mounted PIR Presence Detectors, PIR Presence Detectors, Presence Detectors, Detectors
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

CP electronics User Manuals

Related Manuals