Danfoss 475-4 Compressor Range Installation Guide

June 1, 2024
Danfoss

**Danfoss 475-4 Compressor Range Installation Guide

**

About these instructions

Read these instructions before assembly and before using the compressor. This will avoid misunderstandings and prevent damage. Improper assembly and use of the compressor can result in serious or fatal injury.
Observe the safety instructions contained in these instructions.
These instructions must be passed onto the end customer along with the unit in which the compressor is installed.

Safety

Identification of safety instructions:

DANGER Indicates a dangerous situation which, if not avoided, will cause immediate fatal or serious injury.

WARNING Indicates a dangerous situation which, if not avoided, may cause fatal or serious injury.

CAUTION Indicates a dangerous situation which, if not avoided, may cause fairly severe or minor injury.

Note IconATTENTION Indicates a situation which, if not avoided, may cause property damage.

INFO Important information or tips on simplifying work.

Qualifications required of personnel

WARNING Inadequately qualified personnel poses the risk of accidents, the consequence being serious or fatal injury. Work on compressors is therefore reserved for personnel which is qualified to work on pressurized refrigerant systems:

  • For example, a refrigeration technician, refrigeration mechatronic engineer. As well as professions with comparable training, which enables personnel to assemble, install, maintain and repair refrigeration and air-conditioning systems. Personnel must be capable of assessing the work to be carried out and recognising any potential dangers.

General safety instructions

WARNING Risk of accidents.
Refrigerating compressors are pressurised machines and as such call for heightened caution and care in handling.
The maximum permissible overpressure must not be exceeded, even for testing purposes.

Risk of burns!

  • Depending on the operating conditions, surface temperatures of over 60°C on the discharge side or below 0°C on the suction side can be reached.
  • Avoid contact with refrigerant necessarily.
    Contact with refrigerant can cause severe burns and skin damage.

Intended use

WARNING The compressor may not be used in potentially explosive environments!

These assembly instructions describe the standard version of the compressor named in the title manufactured by Bock. Bock refrigerating compressors are intended for installation in a machine (within the EU according to the EU Directives 2006/42/EC Machinery Directive, 2014/68/EU Pressure
Equipment Directive).

Commissioning is permissible only if the compressor has been installed in accordance with these assembly instructions and the entire system into which it is integrated has been inspected and approved in accordance with legal regulations.

The compressors are intended for use in refrigeration systems in compliance with the limits of application.

Only the refrigerant specified in these instructions may be used.

Any other use of the compressor is prohibited!

Safety instructions for use of flammable refrigerants

Safety instructions

DANGER

  • Explosion and fire risk! Synthetic HFO refrigerants are colorless, combustible gases which occur naturally and which are explosive in a certain blend!

  • HFO refrigerants are classified into the safety group A2L (hardlyinflammable refrigerant) according to EN 378.
    As they are heavier than air, the operating location must be above ground level to allow unrestricted discharge of the gas.

  • By means of a risk and hazard analysis, appropriate technical measures are to be identified in order to achieve sufficient risk reduction. If necessary, a classification of the hazardous areas according to EN60079-10-1 should be carried out. If the refrigerant concentration exceeds the value of 25% of the lower flammability limit (LEL), all equipment in the hazardous area which is not permitted for operation in hazardous areas must be immediately switched off without any voltage.

  • Use only suitable equipment approved for flammable refrigerants.

  • Observe the national regulations.

Note IconINFO Semi-hermetic compressors are to be classified as “technically tight” (see e.g. TRBS 2152 part 2 / TRGS 722).

Qualifications required of personnel

WARNING Inadequately qualified personnel poses the risk of accidents, the consequence being serious or fatal injury. Work on compressors is therefore reserved for personnel which is qualified in handling flammable refrigerants.

Product description

Short description

  • Semi-hermetic four-cylinder reciprocating compressor with oil pump lubrication.
  • Flange-mounted drive motor on the compressor case.
  • Specially or deep cooling with air-cooled motor and direct suction at the cylinder.

Short Description
Short Description

Dimension and connection values can be found in Chapter 12.

Name plate (example)

Name Plate

  1. Type designation

  2. Machine number

  3. maximum operating current

  4. Starting current (rotor blocked) Y: Part winding 1 YY: Part windings 1 and 2

  5. ND (LP): max. admissible operating pressure Low pressure side
    HD (HP): max. admissible operating pressure High pressure side
    Note IconObserve the limits of application diagrams!

  6. Voltage, circuit, frequency

  7. Nominal rotation speed

  8. Displacement

  9. Voltage, circuit, frequency

  10. Nominal rotation speed

  11. Displacement

  12. Oil type filled at the factory

  13. Protection class
    Note IconElectrical accessories can change the IP protection class!

Type key (example)
Type Key

  1. HA – Hermetic Air-cooled for deep-freezing
  2. X – Ester oil charge (HFC refrigerant, e.g. R404A/R507)

Typ key LG compressor (example)

LG Compressor

  1. HA – Hermetic Air-cooled for deep-freezing
  2. X – Ester oil charge

Areas of application

Refrigerants

  • HFKW / HFC: R404A/R507
  • (H)FCKW / (H)CFC: R22

Oil charge

The compressors are filled at the factory with the following oil type:

  • for R404A/R507 BOCK lub E55
  • for R22 BOCK lub A46

Compressors with ester oil charge (BOCK lub E55) are marked with an X in the type designation (e.g. HAX34e/315-4).

Note IconINFO For refilling, we recommend the above oil types. Alternatives: see chapter 9.5

ATTENTION The oil level must be in the visible part of the sight glass; damage to the compressor is possible if overfilled or underfilled!

Limits of application

ATTENTION Compressor operation is possible within the operating limits.
These can be found in Bock compressor selection tool (VAP) under vap.bock.de. Observe the information given there.

  • Max. permissible ambient temperature 45°C.
  • Max. permissible discharge end temperature 140°C.
  • Max. permissible switching frequency 12x /h.
  • A minimum running time of 3 min. steady-state condition (continuous operation) must be achieved.

For operation with capacity regulator:

  • Continuous operation, when the capacity regulator is activated, is not permissible and can cause damage to the compressor.
  • The suction gas superheat temperature may need to be reduced or set individually when operating near to the threshold.
  • When the capacity regulator is activated, the gas velocity in the system can not under certain circumstances ensure that sufficient oil is transported back to the compressor.

For operation with frequency converter:

  • The maximum current and power consumption must not be exceeded. In the case of operation above the mains frequency, the application limit can therefore be limited.
    (For more on the subject of frequency converters, see chapter 7.14, p. 27)

When operating in the vacuum range, there is a danger of air entering on the suction side. This can cause chemical reactions, a pressure rise in the condenser and an elevated compressed-gas temperature. Prevent the ingress of air at all costs!

Areas of application

Maximum permissible operating pressure (LP/HP)1): 19/28 bar

  1. LP = Low pressure HP = High pressure

Areas of application at LG compressors

Refrigerants

  • HFO refrigerants: R455A, R454C

Oil charge

The compressors are factory-charged with the following oil type:

LG Compressors: BOCK lub E55

Limits of application

ATTENTION Compressor operation is possible within the operating limits. These can be found in Bock compressor selection tool (VAP) under vap.bock.de. Observe the information given there and the following notes:

  • Min. pressure gas temperature ≥ 50°C (min. 20K over condensing temperature). Suction gas superheating on compressor entrance should be min. 7 – 10 K, must be increased if necessary
  • Min. oil temperature ≥ 30°C.
  • Operation in the vacuum range is not permitted.

During operation in the vacuum range, there is a danger of air entering on the suction side. This can cause chemical reactions, pressure rise in the condenser and an excessive pressure gas temperature as well as shifting of the refrigerant ignition limit into the critical range. Avoid absolutely any entry of air!
Use a low pressure switch! Select a shut-off point min. 50 Pa higher than the prevailing surrounding pressure! 

Maximum permissible operating pressure (LP/HP)1): 19/32 bar

  1. LP = Low pressure HP = High pressure

Compressor assembly

Note IconINFO New compressors are factory-filled with inert gas. Leave this service charge in the compressor for as long as possible and prevent the ingress of air. Check the compressor for transport damage before starting any work.

Storage and transport

  • Storage at (-30°C) – (+70°C), maximum permissible relative humidity 10% – 95%, no condensation
  • Do not store in a corrosive, dusty, vaporous atmosphere or in a combustible environment.
  • Use transport eyelet.
  • Do not lift manually!
  • Use lifting gear!

Setting up

ATTENTION Attachments (e.g. pipe holders, additional units, fastening parts, etc.) directly to the compressor are not permissible!

  • Provide adequate clearance for maintenance work.

  • Ensure adequate compressor ventilation.
    The compressor must not be in the air stream to another component of the refrigeration system (e.g. condenser).
    The cooling of the drive motor must be reliable guaranteed.

  • Do not use in a corrosive, dusty, damp atmosphere or a combustible environment.

  • Setup on an even surface or frame with sufficient loadbearing capacity.

  • Single compressor preferably on vibration damper.

  • Duplex and parallel circuits always rigid.

  • Sun protection: If the compressor is set up outdoors, it has to be protected from direct sunlight.
    Direct Sunlight

Pipe connections

ATTENTION Damage possible.
Superheating can damage the valve.
Remove the pipe supports from the valve for soldering.
Only solder using inert gas to inhibit oxidation products (scale).

Fig. 5: graduated internal diameter

Pipes

  • Pipes and system components must be clean and dry inside and free of scale, swarf and layers of rust and phosphate. Only use air-tight parts.
  • Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being cracked and broken by severe vibrations.
  • Ensure a proper oil return.
  • Keep pressure losses to an absolute minimum.

Laying suction and pressure lines

ATTENTION Improperly installed pipes can cause cracks and tears, the result being a loss of refrigerant.

Note IconINFO Proper layout of the suction and discharge lines directly after the compressor is integral to the system’s smooth running and vibration behaviour.

A rule of thumb: Always lay the first pipe section starting from the shut-off valve downwards and parallel to the drive shaft.
Drive Shaft

Operating the shut-off valves

Operating Shut Valves
Operating Shut Valves

  • Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn
    counter-clockwise.

  • After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.

Operating mode of the lockable service connections

Opening the shut-off valve:
Spindle: turn to the left (counter-clockwise) as far as it will go.
—> Shut-off valve completely opened / service connection closed.
The connection which cannot be shut off is intended for safety devices.
Service Connections

Opening the service connection
Spindle: Turn ½ – 1 turn to the right clockwise.
—> Service connection opened / shut-off valve opened.
The connection which cannot be shut off is intended for safety devices
Opening       Service Connection

After activating the spindle, generally fit the spindle protection cap again and tighten with 14-16 Nm.
This serves as a second sealing feature during operation.

Suction pipe filter and filter drier

For systems with long pipes and higher degree of contamination, a filter on the suction-side is recommended. The filter has to be be renewed depending on the degree of contamination (reduced pressure loss).
Moisture in the refrigeration circuit can lead to crystal and hydrate formation. For this reason, we recommend using a filter drier and a sight glass with a moisture indicator.

Electrical connection

DANGER Risk of electric shock! High voltage! Only carry out work when the electrical system is disconnected from the power supply!

ATTENTION When attaching accessories with an electrical cable, a minimum bending radius of 3 x the cable diameter must be maintained for laying the cable.

Note IconINFO Connect the compressor motor in accordance with the circuit diagram (see inside of terminal box).

  • Use suitable cable entry point of the correct protection type (see name plate) for routing cables into the terminal box. Insert the strain reliefs and prevent chafe marks on the cables.
  • Compare the voltage and frequency values with the data for the mains power supply.

Only connect the motor if these values are the same.

Information for contactor and motor contactor selection

All protection equipment, switching and monitoring devices must comply with the local safety regulations and established specifications (e.g. VDE) and regulations as well as the manufacturer’s specifications. Motor protection switches are required! Motor contactors, feed lines, fuses and motor protection switches must be rated according to the maximum operating current (see name plate).
For motor protection, use a current-independent, time-delayed overload protection device for monitoring all three phases. Adjust the overload protection device so that it must be actuated within 2 hours at 1.2 times the maximum working current.

Standard motor, design for direct or partial winding start

Designation on the name plate
Y/YY

Compressors with this marking are suitable for direct or partial winding start. The motor winding is
subdivided into two parts: Part winding 1 = 50% and part winding 2 = 50%. This winding division

Note IconINFO A mechanical unloaded start with bypass solenoid valve is not required.

Basic circuit diagram for partial winding start with standard motor

Standard Motor

BP2 High pressure safety monitor
BP3 Safety chain (high/low pressure monitoring)
BT1 Cold conductor (PTC sensor) motor winding
BT2 Thermal protection thermostat (PTC sensor)
BT3 Oil temperature sensor
BT4 Release switch (thermostat)
DELTA-P II Oil differential pressure sensor DELTA-P II (accessorie)
EB1 Oil sump heater
EC1 Compressor motor

Standard Motor

FC1.1/1.2 Motor protection switch
FC2 Control power circuit fuse
GQ1 Fan motor
INT69 G Electronic trigger unit INT69 G
KF1 Delay relay for contactor switchover
QA1 Main switch
QA2 Mains contactor (part winding 1)
QA3 Mains contactor (part winding 2)
SF1 Control voltage switch

Electrical connection

The motor is wired for direct start (YY) at the factory. For part winding start Y / YY, the bridges must be removed and the motor feed line connected according to the circuit diagram:
Circuit Diagram

ATTENTION Failure to do this results in opposed rotary fields and results in damage to the motor. After the motor starts up via partial winding 1, partial winding 2 must be switched on after a maximum delay of one second . Failure to comply can adversely affect the service life of the motor.

Special motor: design for direct or star-delta start

A mechanical unloaded start with bypass solenoid valve (accessories) is required for the star-delta start.

Designation on the name plate
∆ / Y

Star-delta start-up is only possible for 230 V power supply. Example:

Power Supply

Basic circuit diagram for star-delta start with special motor

Special Motor

BP2 High pressure safety monitor
BP3 Safety chain (high/low pressure monitoring)
BT1 Cold conductor (PTC sensor) motor winding
BT2 Thermal protection thermostat (PTC sensor)
BT3 Oil temperature sensor
BT4 Release switch (thermostat)
DELTA PII Oil differential pressure sensor DELTA-P II (accessories)
EB1 Oil sump heater
EC1 Compressor motor
FC1.1/1.2 Motor protection switch

Special Motor

FC2 Control power circuit fuse
GQ1 Fan motor
INT69 G Electronic trigger unit INT69 G
KF1 Delay relay for contactor switchover
QA1 Main switch
QA2 Mains contactor
QA3 Δ-contactor
QA4 Y-contactor
SF1 Control voltage switch

Electronic trigger unit INT69 G

The compressor motor is fitted with cold conductor temperature sensors (PTC) connected to the electronic trigger unit INT69 G in the terminal box. In case of excess temperature in the motor winding, the INT69 G deactivates the motor contactor. Once cooled, it can be restarted only if the electronic lock of the output relay (terminals B1+B2) is released by interrupting the supply voltage.

The hot gas side of the compressor can also be protected against overtemperature using thermal protection thermostats (accessory).

The unit trips when an overload or inadmissible operating conditions occur. Find and remedy the cause.

Note IconINFO The relay switching output is executed as a floating changeover contact. This electrical circuit operates according to the quiescent current principle, i.e. the relay drops into a the idle position and deactivates the motor contactor even in case of a sensor break or open circuit.

Connection of the trigger unit INT69 G

Note IconINFO Connect the trigger unit INT69 G in accordance with the circuit diagram. Protect the trigger unit with a delayed-action fuse (FC2) of max. 4 A. In order to guarantee the protection function, install the trigger unit as the first element in the control power circuit.

ATTENTION
Measure circuit BT1 and BT2 (PTC sensor) must not come into contact with external voltage.
This would destroy the trigger unit INT69 G and PTC sensors.

Terminal      Box

Function test of the trigger unit INT69 G

Before commissioning, after troubleshooting or making changes to the control power circuit, check the functionality of the trigger unit. Perform this check using a continuity tester or gauge.

Gauge state Relay position
Deactivated state 11-12
INT69 G switch-on 11-14
Remove PTC connector 11-12
Insert PTC connector 11-12
Reset after mains on 11-14

Relay position INT69 G

Electronic trigger unit INT69 G at LG compressors

The supplied INT69 G must be connected according to the wiring diagram shown here in a separate control cabinet, which must be installed outside each danger zone.

ATTENTION Install heat protection thermostats and cold conductor motor winding in series!

Motor Winding

BT1 Cold conductor (PTC sensor) motor winding
BT2 Heat protection thermostat (PTC sensor)
BT3 Oil temperature sensor
EB1 Oil sump heater

Oil sump heater (accessories)

When the compressor is at a standstill, refrigerant diffuses into the lubricating oil of the compressors housing, depending on pressure and ambient temperature. This reduces the lubricating capacity of the oil. When the compressor starts up, the refrigerant contained in the oil evaporates out throught the reduction in pressure. The consequences can be foaming and migration of the oil, causing oil shocks under certain circumstances.

Operation: The oil sump heater operates when the compressor is at a standstill. When the compressor starts up, the oil sump heater switches off again automatically.

Connection : The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary contact) of the compressor contactor to a seperate electric circuit. El. data: 230 V – 1 – 50/60 Hz, 160 W.
Compressor Contactor

ATTENTION Connection to the current path of the safety control chain is not permitted.

Oil sump heater on LG compressors

As the solubility of HFO refrigerants in oil can be very high, especially at high suction pressures, the compressor must be equipped with an oil sump heater. For this reason, a pump-down circuit is recommended during standstill to reduce the suction-side standstill pressures.
Electrical data: 230 V – 1 – 50/60 Hz, 160 W.

ATTENTION The oil sump heater must generally be connected and operated!

  • In a TT- or TN system, a residual current protection device (RCD) must be used.
  • In an IT system, an insulation monitoring device must be used.

National standards and regulations must be observed.

Capacity regulator (Accessories)

ATTENTION A fuse (max. 3xlB in accordance with IEC 60127-2-1) corresponding to the rated current must be placed in front of every magnetic coil of the capacity regulator as short-circuit protection. The rated voltage of the fuse must be equal to or greater than the rated voltage of the magnetic coil. The ability of the fuses to switch off must be greater than or equal to the maximum assumable shortcircuit current at the installation location.

Capacity regulator DCR14 is not approved for digital capacity regulation for LG compressors.

Fan motor

The fan motor for cooling the compressor is already wired in the terminal box. The power supply as well as triggering of the compressor contactor should be made in accordance with the basic circuit diagram (in the terminal box). The fan motor is protected by an internal temperature monitor.
Electrical data: 230 V – 1 – 50/60 Hz, 140 W – 0,71 A, IP44

Selection and operation of compressors with frequency converters

For safe operation of the compressor, the frequency converter must be able to apply an overload of at least 140% of the compressor’s maximum current (I-max.) for at least 3 seconds.

When using frequency converters, the following things must also be observed:

  1. The maximum permissible operating current of the compressor (I-max) (see type plate or technical data) must not be exceeded.
  2. If abnormal vibrations occur in the system, the affected frequency ranges in the frequency converter must be blanked out accordingly.
  3. The maximum output current of the frequency converter must be greater than the maximum current of the compressor (I-max).
  4. Carry out all designs and installations in accordance with the local safety regulations and common rules (e.g. VDE) and regulations as well as in accordance with the specifications of the frequency converter manufacturer

The permissible frequency range can be found in the technical data chapter 11.

Rotational speed range 0 – f-min -min – f-max
Start-up time < 1 s ca. 4 s
Switch-off time immediately

Commissioning

Preparations for start-up

INFO To protect the compressor against inadmissible operating conditions, high pressure and low pressure pressostats are mandatory on the installation side.

The compressor has undergone trials in the factory and all functions have been tested. There are therefore no special running-in instructions.

Check the compressor for transport damage!

Pressure integrity test

The compressor has been tested in the factory for pressure integrity. If however the entire system is to be subjected to a pressure integrity test, this should be carried out in accordance with EN 378-2 or a corresponding safety standard without the inclusion of the compressor.

Leak test

DANGER
Risk of bursting!

The compressor must only be pressurised using nitrogen (N2).Never pressurise with oxygen or other gases!
The maximum permissible overpressure of the compressor must not be exceeded at any time during the testing process (see name plate data)! Do not mix any refrigerant with the nitrogen as this could cause the ignition limit to shift into the critical range.

Carry out the leak test on the refrigerating plant in accordance with EN 378-2 or a corresponding safety standard, while always observing the maximum permissible overpressure for the compressor.

Evacuation

ATTENTION Do not start the compressor if it is under vacuum. Do not apply any voltage – even for test purposes (must only be operated with refrigerant).

Under vacuum, the spark-over and creepage current distances of the terminal board connection bolts shorten; this can result in winding and terminal board damage.

  • First evacuate the system and then include the compressor in the evacuation process.
  • Relieve the compressor pressure.
  • Open the suction and pressure line shut-off valves.
  • Evacuate the suction and discharge pressure sides using the vacuum pump.
  • At the end of the evacuation process, the vacuum should be < 1.5 mbar when the pump is switched off.
  • Repeat this process as often as is required.
  • For LG compressors suitable equipment approved for flammable refrigerants must be used.

Refrigerant charge

CAUTION Wear personal protective clothing such as goggles and protective gloves!

  • Make sure that the suction and pressure line shut-off valves are open.
  • With the compressor switched off, add the liquid refrigerant directly to the condenser or receiver, breaking the vacuum.
  • If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour form on the suction side, or, taking suitable precautions, also in liquid form at the inlet to the evaporator.

ATTENTION

  • Avoid overfilling the system with refrigerant!
  • To avoid shifts in concentration, zeotropic refrigerant blends must always only be filled into the refrigerating plant in liquid form.
  • Do not pour liquid coolant through the suction line valve on the compressor.
  • It is not permissible to mix additives with the oil and refrigerant.

Start-up

WARNING Ensure that both shut-off valves are open before starting the compressor!

  • Check that the safety and protection devices (pressure switch, motor protection, electrical contact protection measures, etc.) are all functioning properly.
  • Switch on the compressor and let it run for at least 1 minute at a frequency of at least 50 Hz.
  • Only then may the speed of the compressor be reduced.
  • Check the oil level by: The oil must be visible in the sightglass.

ATTENTION If larger quantities of oil have to be topped up, there is a risk of oil hammer effects.
If this is the case check the oil return!

Avoiding slugging

ATTENTION Slugging can damage the compressor and cause refrigerant to leak.

To prevent slugging:

  • The complete refrigeration system must be properly designed.
  • All components must be compatibly rated with each other with regard to output (particularly the evaporator and expansion valves).
  • Suction gas superheat at the compressor input should be min. 7 – 10 K. (check the setting of the expansion valve). For LG compressors see chapter 5.3.
  • The system must reach a state of equilibrium.
  • Particularly in critical systems (e.g. several evaporator points), measures are recommended such as replacement of liquid traps, solenoid valve in the liquid line, etc.

There should be no movement of coolant whatsoever while the compressor is at a standstill.

The use of a check valve is strongly recommended. Otherwise, there is a risk of reverse condensation which may damage the compressor.

Connection of oil level regulator

Oil level regulation systems have proven themselves with parallel circuits of several compressors.
The connection “0” is provided for installing an oil level regulator (see dimensions drawing). All common oil level regulators from AC&R, ESK and Carly as well as the OM3 TraxOil oil level regulation system from Alco can be connected directly without adapters (see Fig. 17). A sight glass on the oil level regulator is not required.

Mechanical oil level regulator at the “O” connection

Mechanical Oil

3  hole connection diagramm for AC&R und CARLY
3-Loch-Anschlussbild für TraxOil

Maintenance

Preparation

WARNING

Before starting any work on the compressor:

  • Switch off the compressor and secure it to prevent a restart.
  • Relieve compressor of system pressure.
  • Prevent air from infiltrating the system!

After maintenance has been performed:

  • Connect safety switch.
  • Evacuate compressor.
  • Release switch lock.

Work to be carried out

In order to guarantee optimum operational reliability and service life of the compressor, we recommend carrying out servicing and inspection work at regular intervals:

  • Oil change:

    • not mandatory for factory-produced series systems.
    • for field installations or when operating near the application limit: for the first time after 100 to 200 operating hours, then approx. every 3 years or 10,000 – 12,000 operating hours.
      Dispose of used oil according to the regulations; observe national regulations.
  • Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of auxiliary devices such as oil sump heater, pressure switch.

Condensate drainage

The terminal box has the option for Condensate drainage (see Fig. 18).

ATTENTION When the condensate drain is used, the protection rating of the terminal box is reduced from IP65 to IP32!

Condensate Drainage

Spare parts recommendation/accessories

Available spare parts and accessories can be found on our compressor selection tool under vap.bock.de as well as at bockshop.bock.de.

Only use genuine Bock spare parts!

Lubricants / oil

The oil type filled as standard in the factory is marked on the name plate, and this should always be used, even in the case of maintenance units. Alternative oil types can vary significantly in quality due to additives or inferior raw materials by the manufacturer. Validation within the compressors entire operating limits can not be guaranteed, if such alternative oil types are used. It is for this reason, that we only recommend the use of oil from Bock! Bock assumes no liability for any damage arising from alternative oil types.

  • Refrigerants: Bock standard oil types
  • HFC (e.g. R134a, R407C): BOCK lub E55
  • HFO (e.g. R455A, R454C): BOCK lub E55
  • HCFC (e.g. R22): BOCK lub A46

Decommissioning

Close the shut-off valves on the compressor. Drain the refrigerant (it must not be discharged into the environment) and dispose of it according to the regulations. When the compressor is depressurised, undo the fastening screws of the shut-off valves. Remove the compressor using an appropriate hoist. Dispose of the oil inside in accordance with the applicable national regulations.

Additional information when using flammable refrigerants

WARNING

  • During maintenance and repair, it must be noted that HFO refrigerants residues may dissolve in the oil. Therefore, electrical tests must not be conducted while oil remains in the compressor.
  • If the compressor is to be removed from the system for maintenance or repair, the remaining refrigerant must be suctioned out and the compressor evacuated. The compressor must then be filled with nitrogen (max. 0.5 bar) and sealed gas-tight.

Capacity regulator

ATTENTION If the capacity regulator is installed at the factory, it is subsequently installed and connected by the customer.

Delivery condition 1 (from the factory):
Cylinder cover prepared for capacity regulator.
Capacity Regulator

Before commissioning, the blind flange with screws must be removed and replaced by the new set capacity regulator with O-ring joints and screws. Observe position and construction of the capacity regulator.
**Attention! Compressor is under pressure! Depressurize the compressor first.

**

Delivery condition 2 (from the factory):
Connect capacity regulator in terminal box or switch cabinet.

WARNING Several capacity regulators cannot switch at the same time during compressor operation! Otherwise the sudden change in load can damage the compressor! Comply with the switching interval of 60 s.
Comply with the switching sequence:
Swiching on LR1 60s LR2
Swiching off LR2 60s LR1

Accessories

ATTENTION

  • Capacity-regulated operation alters the gas speeds and pressure ratios of the refrigerating plant: Adjust the suction line routing and dimensioning accordingly, do not set the control intervals too close and do not let the system switch more than 12 times per hour (refrigerating plant must have reached a state of equilibrium).
    Continuous operation in the control stage is not recommended as the gas velocity in the plant system under certain circumstances does not guarantee sufficient oil return to the compressor with activated capacity regulator.
    We recommend switching to unregulated operation (100% capacity) for at least 5 minutes per capacity-regulated operating hour. An assured oil return can also be realised by a 100% capacity requirement after each compressor restart.

  • Electrical actuation of the solenoid valve: Normally open, (corresponds to 100 % compressor capacity).

Special accessories are only premounted in the factory if ordered specially by customer. Retrofitting is possible in full compliance with the safety instructions and repair instructions enclosed with the kits. Information about the use, operation, maintenance and servicing of the components is available in the printed literature or on the internet under www.bock.de.

For the capacity regulator a step protection is optional available, Art-Nr. 097B81449.

Please note that the legacy BOCK ref. numbers are without 097B.

Technical data

Table

  • The technical data for LG compressors are identical to the standard compressors. Therefore, these designations are not included in the compressor type specification.

    1. Tolerance (± 10%) relative to the mean value of the voltage range.
      Other voltages and types of current on request.

    2. The specifications for max. power consumption apply for 50Hz operation.
      For 60Hz operation, the specifications have to be multiplied by the factor 1.2. The max. working current remains unchanged.

      • Take account of the max. operating current / max. power consumption for design of fuses, supply lines and safety devices.
        Fuse: Consumption category AC3
    3. All specifications are based on the average of the voltage range

    4. For solder connections

Dimensions and connections

HA44e (Dimensions and connections for LG compressors are identical to the standard compressors)

Dimensions Connections

SV DV| Suction line Discharge line| see technicla data, Chapter 11|
---|---|---|---
A| Connection suction side, not lockable| 1 /8“ NPTF
A1| Connection suction side, lockable| 7/16″ UNF
B| Connection discharge side, not lockable| 1/8″ NPTF
B1| Connection discharge side, lockable| 1/16″ UNF
D| Connection oil pressure switch LP| 1/16″ UNF
D1| Connection oil return from oil separator| 1/4″ NPTF
E| Connection oil pressure gauge| 1/8″ NPTF
F| Oil drain| M12 x 1,5
H| Oil charge plug| 1/4″ NPTF
1| Connection hot gas temperature sensor| 1/8″ NPTF
J| Connection oil sump heater| 3/8″ NPTF
K| Sight glass| 3 x M6
L| Connection thermal protection thermostat| 1/8″ NPTF
M| Oil strainer| M12 x 1,5
0| Connection oil level regulator| 3 x M6
P| Connection oil pressure differential sensor| M20 x 1,5
0| Connection oil temperature sensor| 1/8″ NPTF

Declaration of incorporation

Applications

Applications

Danfoss A/S
Climate Solutions danfoss.com +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals. catalogues descriptions, advertisements, etc. and whether mode available in writing, wally, electronically online or via downloads, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order conformation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material Danfoss reserves the right to amber its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo ane trademarks of Danfoss A/S. All rights nowered

AQ452839384735en-000301

© Danfoss | Climate Solutions | 2024.03

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals