CP Electronics EBDSPIR-KNX-MR KNX Presence Detectors Installation Guide
- June 12, 2024
- CP electronics
Table of Contents
CP Electronics EBDSPIR-KNX-MR KNX Presence Detectors
Attention
To be installed by competent technician with good understanding of network
devices.
Dimensions (mm)
Detection pattern
Wiring
Key
- Switches, as configured in the ETS software.
- Low voltage only.
- KNX bus
Presence or absence detection
The unit requires configuration by an appropriate software.
Absence detection activation and switches configurations are set using the ETS
KNX software supplied by others.
It is designed to work with other KNX devices such as other detectors and
switches from other manufacturers.
Installation
This device is designed to be flush ceiling-mounted.
- Do not site the unit where direct sunlight might enter the sensor.
- Do not site the sensor within 1m of any lighting, forced air heating or ventilation.
- Do not fix the sensor to an unstable or vibrating surface.
- Occupancy is best detected when the ambient temperature is different to that of the human body, thus, use within -20 to 35ºC ambient temperature.
Create cut out
Cut a 64mm diameter hole in the ceiling.
Wire in plugs & connect to detector
Wire in plug/s, using wiring diagram on page 2 as a guide. Connect the
plug/s to the detector.
Clamp cable
Continue tightening the screws until the clamp bar snaps out and is tightly
engaged against the cable/s. The cable clamp must clamp the outer sheath only.
Install detector
Bend the springs up and push detector through hole in ceiling. When fully
inserted the springs snap back to hold the device in place.
To avoid injury, take care when bending springs.
Technical Data