COZY DVCF403C-H Direct Vent Counterflow Wall Furnace Instruction Manual

June 4, 2024
Cozy

DVCF403C-H Direct Vent Counterflow Wall Furnace
Instruction Manual

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace

Installation and Operating Instructions

NATURAL GAS – DVCF403C-H, DVCF553C-H, DVCF407C-H, DVCF557C-H
PROPANE GAS – DVCF404C-H, DVCF554C-H, DVCF408C-H, DVCF558C-H

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

  • Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
  • WHAT TO DO IF YOU SMELL GAS
    • Do not try to light any appliance.
    • Do not touch any electrical switch; do not use any phone in your building.
    • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
    • If you cannot reach your gas supplier, call the fire department.
  • Installation and service must be performed by a qualified installer, service agency, or gas supplier.

INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.

WARNING: This product can expose you to chemicals including epichlorohydrin which is known to the State of California to cause cancer and birth defects and/or other reproductive harm. For information go to www.p65warnings.ca.gov. 

WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for proper installation. For assistance or for additional information consult a qualified installer, service agency, or gas supplier.

  • The coating selected to provide longer life to the heat exchanger may smoke slightly upon initial firing. Please provide adequate ventilation if this occurs.
  • Installation, maintenance, service, troubleshooting & repairs must be performed by a qualified service agency. DO NOT attempt any of these procedures if you are not qualified as this could expose you to property damage, personal injury, or loss of life and will invalidate all warranties.
  • This unit is for residential use only and is not approved for installation in greenhouses, or environments involving dusty, wet, corrosive, or explosive conditions. Such conditions will invalidate the warranty and may create unsafe conditions.
  • The appliance may be installed in an aftermarket permanently located, manufactured home (the USA only), or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.

WARNING: Operation of this furnace without the properly installed, furnished vent system and vent cap could result in Carbon Monoxide (CO) poisoning and possible death.  For your safety, this furnace and the vent system should be inspected at least annually by a qualified service technician.

READ CAREFULLY BEFORE INSTALLING UNIT

These installation instructions are a general guide and do not supersede applicable local codes and ordinances. Before planning or making the installation be sure it complies with all phases of the local heating code. (Or, in the absence of local codes, with the latest edition of the National Fuel Gas Code, ANSI.Z223.1, or CAN1-B149).

The appliance, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, with the latest edition of National Electrical Code  ANSI / NFPA 70, or Canadian Electrical Code CSA-C22.1.

All of the ANSI and NFPA standards referred to in this installation instructions are the ones that were applicable at the time the design of this appliance was certified.

NFPA Standards:
NATIONAL FIRE PROTECTION
ASSOCIATION
1 Batterymarch Park
Quincy, Massachusetts | USA 02169-7471

ANSI & Canadian Standards:
CSA GROUP
178 Rexdale Boulevard,
Toronto, Ontario | Canada M9W 1R3

The design of this appliance was certified to comply with the latest edition of ANSI Z21.86 and CSA 2.32.

The installer must leave these instructions with the consumer, have them complete, and return the warranty card.

The State of Massachusetts requires that the installation and service of a gas appliance be performed by a plumber or gas fitter licensed in the Commonwealth of Massachusetts. See page 18.

SPECIFICATIONS & DIMENSIONS

Your Direct Vent Counterflow Wall Furnace is shipped in two cartons. One carton contains the furnace, thermostat, thermostat wire, and insulated staples. The second carton will have the vent tube, air intake tube, and vent cap assembly. After the furnace has been removed from the carton check the rating plate to verify that the model number is correct and that the wall furnace is equipped with the type of gas you intend to use.

MODEL NUMBERS| DVCF403C-H DVCF407C-H
DVCF553C-H DVCF557C-H| DVCF404C-H DVCF408C-H
DVCF554C-H DVCF558C-H
---|---|---
Gas Type| Natural| Propane
Height
Width
Depth| 78 – 5/8”
14 – 5/16”
11 – 3/4”| 87 – 5/16”
14 – 5/16”
11 – 3/4”| 78 – 5/8”
14 – 5/16”
11 – 3/4”| 87 – 5/16”
14 – 5/16”
11 – 3/4”
Input (BTU / HR)
Gas Inlet
CFM| 40,000
1/2”
320| 55,000
1/2”
440| 40,000
1/2”
320| 55,000
1/2”
440
Type Control
Blower Speed
Approx. Shipping Weight| 24 Volt
1
130 lbs| 24 Volt
1
144 lbs| 24 Volt
1
130 lbs| 24 Volt
1
144 lbs
Amps
Intermittent
Ignition
(IID)| 1.95

2.2
IID|  3.05

3.3
IID| 1.95

2.25
IID| 3.05

3.35
IID

INTRODUCTION

READ THIS INSTALLATION AND OPERATING INSTRUCTIONS CAREFULLY BEFORE YOU INSTALL OR ATTEMPT TO USE THIS DIRECT VENT  COUNTERFLOW WALL FURNACE. IF YOU DO NOT UNDERSTAND ANY PART OF THE INSTRUCTIONS, CONSULT LOCAL AUTHORITIES, A QUALIFIED INSTALLER, A SERVICE TECHNICIAN, OR A GAS SUPPLIER. FAILURE TO READ OR UNDERSTAND THESE INSTRUCTIONS CAN RESULT  IN MALFUNCTION, INEFFICIENT OPERATION, PROPERTY DAMAGE, SERIOUS INJURY, OR DEATH.

SAFETY

  1. This appliance must be installed in accordance with local codes if any; if not, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane  Installation Code, CSA-B149.1.

  2. Follow all applicable local codes and ordinances. If there are none, follow the latest edition of the National Fuel Gas Code, ANSI Z21.86. A copy may be obtained from the  National Fire Protection Association; 1 Batterymarch Park; Quincy, MA, 02269. In Canada, see the current CAN1-B149 installation code, available from the CSA Group; 178  Rexdale Boulevard; Toronto, Ontario; Canada M9W 1R3.

  3. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical  Code, ANSI/NFPA70.
    In Canada, see the current CSA C22.2 Canadian Electrical Code, available from International Approval Services, 178 Rexdale Boulevard, Etobicoke, Ontario, Canada M9W 1R3.

  4. Do not install this furnace in a recreational vehicle or trailer.

  5. Do not operate this furnace unless it is connected to the supplied vent system with a vent cap in place. Do not attempt to extend vent pipes. 12 inches is the maximum length.

  6. Never use a match, candle, flame, or another source of ignition to check for gas leaks. Use only soapy water or liquid detergent.

  7. Before cleaning or servicing, turn off the gas and allow the furnace to cool.

  8. Do not operate the furnace without grilles and the front panel in place.

  9. Due to high temperatures, locate the furnace out of traffic and away from furniture and drapes.

  10. Children and adults should be alerted to the hazard of high surface temperature and should be kept away to avoid burns or clothing ignition.

  11. Young children should be carefully supervised when they are in the same room as the furnace.

  12. Do not place clothing or other flammable material on or near the furnace.

  13. Installation and repair should be done by a qualified service technician. The furnace should be inspected before use and at least annually by a professional service technician. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners, and circulating air passageways of the furnace be kept clean.

  14. Do not put anything around the furnace or vent cap that will obstruct the flow of combustion and ventilation air.

  15.  When installing the furnace allow adequate accessibility clearances for servicing and proper operation. (See figure 1 on page 5).

  16. The wall furnace should be located near the center of the area to be heated for optimal heat distribution. If the wall furnace is installed directly on carpeting, tile, or any combustible material other than wood flooring, the wall furnace shall be installed on a metal plate or wood panel secured to the floor, extending the full width and depth of the wall furnace. If a side register kit is to be installed, see Page 16.

  17. Do not use this heater if any part has been underwater.
    Immediately call a qualified service technician to inspect the heater and to replace any part of the control system which has been under water.

  18. For your safety, this furnace is equipped with a manual reset auxiliary limit switch. In case of failure by the primary limit switch, this switch will shut the valve down completely before unsafe temperatures are reached. After a cool-down period, the switch must be manually reset. If outages persist, call a qualified service person.

  19. Side discharge kit boots must not exceed 10 inches.

  20. Locate the auxiliary limit switch and push in the red reset button. This will reset the switch in case it accidentally opened during shipping.

VENTING

WARNING: CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:

  1. Seal any unused openings in the venting system.

  2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane  Installation Code, CSA B149.1, and these instructions. Determine that there is no blockage or restriction, leakage, corrosion, and other deficiencies which could cause an unsafe condition.

  3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other
    spaces of the building.

  4. Close fireplace dampers.

  5. Turn on clothes dryers and any appliances not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

  6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so the appliance is operating continuously.

  7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle.

  8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI  Z223.1/NFPA 54 and/or Natural Gas and Propane Installation Code, CSA B149.1.

  9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans,  fireplace dampers and any other gas-fired burning appliance to their previous conditions of use.

CLEARANCES

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
1

REFERENCE LETTER TO DRAWING| CANADIAN
**INSTALLATIONS*| U.S. INSTALLATIONS**
DVCF40 DVCF55**
---|---|---
A Clearance above grade, veranda, porch, deck, or balcony| 12 Inches (30 cm)| 12 Inches (30 cm)
B Clearance to window or door that may be opened| 12 Inches (30 cm)| 9″ (23 cm)| 12″ (30 cm)
C Clearance to the permanently closed window| 12 Inches (30 cm)| 9″ (23 cm)| 12″ (30 cm)
D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 Feet (61 cm) from the center line of the terminal| 18 Inches (46 cm)| 18 Inches (46 cm)
E Clearance to unventilated soffit| 24 Inches (61 cm)| 24 Inches (61 cm)
F Clearance to the outside corner| 12 Inches (30 cm)| 12 Inches (30 cm)
G Clearance to the inside corner| 12 Inches (30 cm)| 12 Inches (30 cm)
. .
H Clearance to each side of the center line extended above the meter/regulator assembly| 3 Feet (91 cm) within a
15 Feet (4.5m) above the
meter/regulator assembly| Clearance in accordance
with local installation codes &
requirements of the gas supplier
I Clearance to service regulator vent outlet| 3 Feet (91 cm)|
J Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance.| 12 Inches (30 cm)| 9″ (23 cm) I| 12″ (30 cm)
K Clearance to a mechanical air supply inlet| 6 Feet (1.83 m)| 3 Feet (91 cm) above if within 10 Feet (3 m) horizontally
L Clearance above the paved sidewalk or paved driveway located on public property| 7 Feet (2.13m) A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-family dwellings and serves both dwellings.| Clearance in
accordance with local
installation codes &
M Clearance under veranda, porch, deck, or balcony| 12 Inches (30 cm)
permitted only if the veranda, porch, deck, or balcony is fully open on a minimum of two sides.| requirements of the gas supplier

*In accordance with the current CSA-B149.1
Natural Gas and Propane Installation Code
**In accordance with the current ANSI
Z223.1 / NFPA 54 National Fuel Gas Code

MINIMUM CLEARANCES

  • Side Wall: Min. Clearance = 4”
    (See Fig. 1) NOTE: The unit may be recessed and rest directly against side studs and the inside surface of the rear wall.

  • Ceiling: Min. Clearance = 4”
    (See Fig. 1)

  • Floor: Min. Clearance = 0”
    (See Fig. 1)

  • From the Side of the Vent Cap to Any Protruding Obstructions or Corners: Min. Clearance = 12”
    (See Fig. 2b)

  • From any Window to the Side of the Vent Cap
    DVCF403, 404, 407, & 408C
    Min. Clearance = 9”
    (See Figure 2)
    DVCF553, 554, 557 & 558C
    Min. Clearance = 12” (See Figure 2b)

  • From any Overhanging Projection to the Top of the Vent Cap
    Min. Clearance = 24”
    (See Figure 2)

RESIDENTIAL GARAGE INSTALLATION:
Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18 inches (46 cm) above the floor. Such
equipment shall be located or protected so it is not subject to damage by a moving vehicle. Use care in selecting a good location within the garage.

  • DO NOT locate the appliance where heated air will be directed onto a nearby parked vehicle.
  • Paint may discolor or rubber may harden and crack.
  • DO NOT allow heated discharge air to blow directly onto open or closed containers of paint, gasoline or other liquids having flammable vapors.

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
2

LOCATIONS

  1. This furnace must be installed on an outside wall and vented to the outside. If possible, this wall should be on the side of the house that receives the least amount of wind since strong gusting winds could cause a pilot outage.
  2. For the most efficient performance, locate the furnace as centrally as possible in the area to be heated.
  3. The furnace can be installed flush against a wall or recessed up to 10” maximum. For proper combustion, make sure the unit is level front-to-back and side-to-side.
  4. Do not install the furnace in a closet, alcove, or small hallway where the furnace could be isolated from the space to be heated by closing a door.
  5. Be sure the vent cap will have the proper clearances. (See Figure 2a)
  6. Check inside the wall to make sure there are no obstacles such as water pipes, electric wiring, etc. which could interfere with the installation of the furnace or vent tubes.
  7. Be sure to maintain adequate accessibility clearances for servicing and proper operation.
  8. If the furnace is installed in a basement, a 12” clearance must be maintained between ground level and the bottom of the vent cap. Do not install a furnace where the vent cap will terminate in a window well or any other opening below ground level.

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
3

INSTALLATION

ELECTRICAL ROUGH-IN
For convenience, this furnace is equipped with a three-prong power cord located on the top left of the heater. The 115V wiring should be brought in on the left side terminating in a receptacle box (not provided). Consult local codes or ordinances. (For Amps, see Page 3 / Specifications and Dimensions).

ROUGH-IN GAS SUPPLY
Install a 1/2-inch diameter gas supply line. The gas line can enter the cabinet through the right side or bottom (See Figure 3). The gas line must have an individual manual shut-off valve. Also, you must install a drip leg and provide a 1/8” N.P.T. plugged tapping, accessible for test gauge connection, immediately upstream of the gas supply connection
to the furnace (See Figure 4).
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½  psig (3.5kPa). The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply
the piping system at test pressures equal to or less than ½ psig (3.5kPa).

LOCATE VENT OPENING
After the location of the heater has been determined, the opening for the vent pipe should be cut. If the heater is to be recessed, cut out the opening for the heater between studs on the interior wall and cut out the floor plate between the studs, so the heater will be set flat on the floor as all dimensions are given from a finished floor. The height of the cutout for a 40,000 BTU model is 78-5/8”, for the 55,000 models the cutout height is 87-5/16”. NOTE: This dimension may be increased to allow more room for installation and making the wiring connection, then refinished.

Next, cut out a 9-1/4” opening in the exterior wall for the vent tubes to pass through. The center of opening for the 40,000 BTU furnace is 59”, and the center opening for the 55,000  BTU furnace is 68-1/2”. See Figure 5, on Page 6.

If the heater is to be surfaced mounted, cut out a 9-1/4” opening through the interior and exterior wall. The center of cut out will be 59” for 40,000 BTU and 68-1/2” for 55,000  BTU models. Be sure both cutouts are level with each other.

INSTALLING THE FURNACE
The vent system supplied with this furnace will accommodate walls ¾” (when recessed) up to 12” thick. Use only the exhaust tube, air intake tube, and vent cap supplied with the heater. Do not attempt to lengthen the exhaust or air intake tubes, this could cause an imbalance in the heater resulting in poor performance and pilot outage (See Figure 6).
Measure the exact distance “X” between the surface on which the back of the cabinet will rest (inside of the recessed cavity or face of the wall when freestanding) and the outside wall surface (see  Figure 6).

INLET AIR TUBE “A” – Measuring from gasket surface, mark and cut pipe same as dimension “X”.  Remove any burrs.

VENT EXHAUST TUBE “B” – Measuring from gasket surface, mark and cut pipe 1-3/4” greater than dimension “X”. Remove any burrs.

Fasten vent exhaust tube “B” to heat exchanger collar and Inlet AirTube “A” to flange on the back of furnace using 16 # 3/8 screws (“C”)provided. Be sure gaskets are in place and not damaged. Anytime the vent pipes are removed check and replace gaskets (if necessary). Failure to replace missing or damaged gaskets may expose homeowners to life-threatening conditions.
Secure the furnace in place using 2 holes provided in the bottom of the casing.NOTE: Make sure both tubes are centered in cut out. Slide the vent cap onto the pipes extending from the back of the furnace. A rotating or twisting motion will ease this installation. Secure the vent cap and vent cap spacer plate to the wall causing the vent tubes to have a slight downward pitch. This will prevent water from entering. Anchors (not provided) may be required. Caulk around vent cap spacer plate with caulking provided.
NOTE: Some framing may be necessary to provide a flat surface against the vent cap spacer plate and to prevent rain from entering the wall opening.

GAS CONNECTION
Make the gas connection between the manual shut-off valve and the furnace gas control valve with approved ½” connectors. Compounds used on threaded joints of gas piping shall be approved for use with Propane gas. The gas lines must be checked for leaks by the installer with soapy water or liquid detergent, never use an open flame. If connections are not exposed, a pressure test must be run. Be sure to disconnect the gas supply line from the appliance valve before pressure testing. The manifold pressure is pre-set at the factory and should be 3.5” w.c. for Natural Gas and  10” w.c. for Propane Gas. The minimum inlet pressure for Natural Gas is 4.5” w.c. and 11” w.c. for Propane  Gas, “for purpose of input adjustment”. The maximum inlet pressure should never exceed 7.0” w.c. on Natural Gas or 14” w.c. on Propane Gas.

THERMOSTAT INSTALLATION
Follow the instructions included with the thermostat. Select a location for the thermostat on an inside wall approximately 5 feet above the floor where it won’t be affected by heat or cold sources such as direct sunlight, televisions, fireplaces, hidden hot or cold water pipes, drafts, etc., and minimum of 4’ from the heater. The thermostat must never be placed in an adjacent room. Connect thermostat wires to the thermostat and mount them to the wall. Run a wire to the furnace and make connections to thermostat wires coming out of the top of the furnace. Use insulated staples (provided) to secure the wire to the wall.

OPERATION
This heater is equipped with a slow-opening gas control. On a call for heat, the gas valve does not snap open to full manifold pressure but opens with a gradual increase to normal manifold pressure. The time-lapse from the call for heat to normal operating pressure is two to five seconds. The slow-open feature assures a safe, less noisy ignition.
After the heat exchanger has warmed sufficiently, the fan will automatically come on to efficiently transfer the heat into the room.

LIGHTING INSTRUCTIONS

MODELS: DVCF403C-H / DVCF404C-H / DVCF553C-H / DVCF554C-H

WARNING:
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life. 

FOR YOUR SAFETY READ BEFORE LIGHTING

A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:

  • DO NOT try to light any appliance.
  • DO NOT touch any electric switch.
  • DO NOT use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician.
Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

  1. STOP! Read the information on the safety label.

  2. Set the thermostat to the lowest setting.

  3. Turn off all electric power to the appliance.

  4. Remove the lower front panel.

  5. Push in the gas control knob slightly and turn clockwise to “OFF”.
    NOTE:
    The knob cannot be turned from “PILOT” to “OFF” unless the knob is pushed in slightly. Do not force.

  6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the information on the safety label. If you don’t smell gas, go to the next step.

  7. Open sight glass cover.

  8. Locate the red piezo ignitor button on side of the gas control.
    Locate the pilot behind the sight glass. (Follow metal pilot tube from gas control).

  9. Turn the gas control knob counterclockwise to “PILOT”.

  10. Push in the pilot control knob and hold in. Immediately begin a series of pushing and releasing the red piezo ignitor button, while observing the pilot through the sight glass.  Continue to spark until the pilot is lit. Continue to hold the pilot control knob in for about one (1) minute after the pilot is lit. Release the pilot control knob and it will pop back up. The pilot should remain lit. If the pilot goes out, repeat steps 4 thru 9.
    – If the knob does not pop up when released, STOP and immediately call your service technician or gas supplier.
    – If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.

  11. Close-sight glass cover.

  12. Turn the gas control knob counterclockwise to “ON.”

  13. Replace the lower front panel.

  14. Turn on all electricity to the appliance.

  15. Set the thermostat to the desired setting.

TURNING OFF THE GAS TO THE APPLIANCE

  1. Turn the thermostat to its lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. Remove the lower front panel.
  4. Push in the gas control knob slightly and turn clockwise to “OFF”. Do not force.
  5. Replace the lower front panel.

LIGHTING INSTRUCTIONS

MODELS: DVCF407C-H / DVCF408C-H / DVCF557C-H / DVCF558C-H

WARNING:
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

FOR YOUR SAFETY READ BEFORE LIGHTING

A. This appliance is equipped with an ignition device that automatically lights the pilot.
Do not try to light the pilot by hand.
B. BEFORE OPERATING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

  • DO NOT try to light any appliance.
  • DO NOT touch any electric switch.
  • DO NOT use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.

  1. STOP! Read the information on the safety label.

  2. Set the thermostat to the lowest setting.

  3. Turn off all electric power to the appliance.

  4. This appliance is equipped with an ignition device that automatically lights the pilot. DO NOT try to light the pilot by hand.

  5. Remove the lower front panel.

  6. Push in the gas control knob slightly & turn clockwise to “OFF”.

  7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the information on the safety label. If you don’t smell gas, go to the next step.

  8. Turn the gas control knob counterclockwise to “ON”.

  9. Replace the lower front panel.

  10. Turn on all electric power to the appliance.

  11. Set the thermostat to the desired setting.

  12. If the appliance will not operate, follow the instructions
    “TO TURN OFF GAS TO APPLIANCE” and call your service technician or gas supplier.

TURNING OFF THE GAS TO APPLIANCE

  1. Turn the thermostat to its lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed.
  3. Remove the lower front panel.
  4. Push in the gas control knob slightly and turn clockwise to “OFF”. Do not force.
  5. Replace the lower front panel.

MAINTENANCE

WARNING: This is a gas-fired appliance. Keep the area clear of gasoline and other flammable vapors and liquids. All combustible material must be kept clear of this area to avoid fire or explosion.

For proper and safe operation, keep the furnace and furnace area clean. At regular intervals turn the control valve off, let it cool, and clean the inside control compartment. To clean the cabinet,  use only a damp cloth. Do not use any kind of solvent or cleaning fluid that could leave a residue or invisible coating that would burn or give off fumes when the furnace is turned on. Have the furnace checked, cleaned, and repaired by a qualified service technician, including the vent system, pilot, and burner operation prior to use each year. The bearings of the fan motor should be oiled every twelve (12) months with S.A.E. 20 oil.
(See Figure 7).
Follow a regular service and maintenance schedule for safe and efficient operation.
Examine the venting system as a routine part of the safety performance check on an annual basis.

PILOT ADJUSTMENT

  1. Locate the pilot adjustment screw on the valve.
  2. The pilot flame should surround at least the top 3/8” of the power pole (pilot generator) or flame sensor (see Figure 8).
    The pilot is unregulated so it will be operating at inlet line pressure (Max. 7” w.c. for Natural Gas and 11” w.c. for Propane).

TO DECREASE
THE PILOT FLAME
Turn the screw clockwise.
(Approximately six full turns to the bottom of the pilot light channel) until you produce a sufficient flame at the minimum noise level.

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
11

MANUAL RESET SWITCH

For your safety, this furnace is equipped with a manual reset limit switch. In case of failure by the primary limit switch, this switch will shut the valve down completely before unsafe temperatures are reached. After a cool-down period, the switch must be manually reset. If outages persist, call a qualified service person.

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
12

TO REMOVE THE MAIN BURNER FOR INSPECTION & CLEANING

  1. Turn the thermostat to the lowest setting and allow the furnace to cool.

  2. Turn off all electric power to the furnace.

  3. Remove the lower grille.

  4. Disconnect the gas supply to the valve.

  5. Disconnect wires from the gas valve.

  6. Remove 15 screws holding the burner door to the burner box. Pull the door forward to remove the complete burner, and gas valve assembly.

  7. After inspecting and cleaning, place the burner assembly back into the burner box and tighten15 screws.
    NOTE: Be sure the door gasket is not damaged and will affect a proper seal or a pilot outage will occur.

  8. Connect wires back to the valve.

  9. Connect the gas supply back to the valve.

  10. Turn on the electricity to the furnace.

  11. Follow lighting instructions, and replace the lower grille.

It is recommended that the furnace and all components be inspected at least annually by a qualified service technician. This should include the burner, pilot, heat exchanger, and vent system. Be sure that the flow of combustion and ventilation air is not obstructed.

IMPORTANT: Keep burner & control compartment clean. Vacuum control compartment at the start of the heating season and as often as needed.

PROPER BURNER FLAME

The burner flame may be observed by raising the sight glass cover. A proper flame will have a dark blue inner mantle that sits right on top of the burners with a lighter blue outer mantle rising above the burner (See Figure 9 on page 11).
There may be some yellow where the pilot flame and burner flame meet. There is no primary air adjustment on the burner, and the proper flame is assured since the correct manifold pressure and orifice has been done at the factory. NOTE: It is advised that the burner flames be checked at least twice during the heating season for any changes in burner flame characteristics.
The appliance area must be kept clear and free from combustible materials, gasoline, and other flammable vapors and liquids. This appliance is equipped only for altitudes 0- 2,000 feet. Heaters installed above 2,000 feet must be derated 4% for every 1,000 feet. For the proper orifice size, find the Model Number and elevation on the orifice chart.  Replace burner orifice. Orifice change must be completed by a qualified installer or service technician.
FIG 10: Orifice Chart for Specific Elevations

Model Number| 0 to
2,000′| 2,000′ –
4,000′| 4,000′ –
6,000′| 6,000′ –
8,000′| 8,000′ –
10,000′
---|---|---|---|---|---
NATURAL GAS| | | |
DVCF403C   32| 34| 35| 36| 40
DVCF407C   32| 34| 35| 36| 40
DVCF553C   3.6mm| 29| 30| 30| 31
DVCF557C   3.6mm| 29| 30| 30| 31
PROPANE GAS| | | |
DVCF404C  49| 50| 51| 52| 52
DVCF408C  49| 50| 51| 52| 52
DVCF554C  44| 45| 47| 48| 49
DVCF558C  44| 45| 47| 48| 49
ORDER KIT #49840 2287-1 High Altitude Kit

TERMINAL BLOCK WIRING DIAGRAMS

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper & dangerous operation. Verify proper operation after servicing.

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
13| COZY DVCF403C-H Direct Vent
Counterflow Wall Furnace - fig 14
---|---

WIRING SCHEMATICS

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
15

14-PEK: 14’ PLUG EXTENSION KIT (For Non-Recessed Installations Only)

CAUTION: These kits must be installed by a qualified installer or service technician.

Units with Terminal Board

  1. Turn the heater off following Section 3 in the Lighting Instructions and allow to cool.
  2. Turn off all electricity to the heater.
  3. Remove the top louver assembly, fan shroud, and fan blade.
  4. Loosen two screws on the Romex connector.
  5. Remove the junction box cover plate.
  6. Disconnect three power cord terminals and pull the power cord out of the top of the heater.
  7. Insert the power cord provided in the kit through the Romex connector and plug it onto the terminal board following the wiring diagram found in the lighting and operating instructions.
  8. Tighten two screws on the Romex connector.
  9. Replace junction box cover plate.
  10. Replace the fan blade, fan shroud, and top louver assembly.
  11. Snap a 90-degree outside corner (Ref. 1) onto a 3-foot section (Ref. 2) plastic raceway. Insert the power cord and remove the blue backing from the adhesive strip on the raceway and apply it to the side of the heater.
  12. Insert the power cord into a second 3-foot section of the raceway (Ref. 3) and remove the blue backing and apply it to the side of the heater, butting up against the bottomof the other section.
  13. Cut a 14-inch long bottom section to the required length (see chart), insert the power cord, remove the backing and apply it to the side of the heater.
  14. Plug the power cord into the wall receptacle.
  15. Light the heater following lighting instructions.

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
16 MODEL NO.
DVCF40
DVCF55
LENGTH OF BOTTOM SECTION (Ref. 4) PLASTIC RACEWAY
5-5/16 Inches NOTE: Lengths terminate approximately 2 inches above floor.
14 Inches NOTE: Lengths terminate approximately 2 inches above floor.
31300-A: CABINET TRIM KIT
CAUTION:
These kits must be installed by a qualified installer or service technician.
COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
17

PART DESCRIPTION QUANTITY PART NO.
48” Long Side Flange Qty. 4 31310
15-1/2” Wide Top Flange Qty. 1 31320
#8 Phillips Head Screws Qty. 10 50134

Units with Terminal Board

  1. Install top flange and secure with two (2) screws.

  2. Select one of the remaining side flanges and position as shown in Figure 12-B (below), making sure that the side with holes is held against the side of the furnace (and that the flange is flush with the bottom of the top trim piece).
    Mark these holes and removed side flange. Drill the marked holes with No. 30 drill bit. Re-position flange and secure with screws provided.

  3. Measure from the bottom of the side flange you have just installed to the floor. Cut one of the remaining side flanges to the measurement and install as in step 2.
    Repeat steps 2 and 3 for opposite side of furnace.

306SR & 30SRB: SIDE DISCHARGE KITS (Optional Accessories)

CAUTION: These kits must be installed by a qualified installer or service technician.
306SR-A
Side Discharge on Casing

  1. Cut out and remove embossed area on casing side.
  2. Remove knockout from inner liner.
  3. Place 1-1/2” boot from kit through opening, matching flanges of boot to knockout on inner liner.
  4. Mark screw holes and remove boot.
  5. Drill holes with a 1/8” drill.
  6. Attach inner boot with screws provided.
  7. Place grille into position, drill holes into casing, and attach with screws provided.

30SRB-A
Side Discharge with Extension Boot

  1. Cut opening in drywall as shown in figure 11, below.
  2. Position plaster ground as shown in figure 11, below. (Optional).
  3. Cut out and remove embossed section on casing side.
  4. Remove knockout on inner liner.
  5. Put heater into position.
  6. Place inner boot into position, mark and cut boot flush with wall. Place outer boot into position, mark and cut boot flush with wall.
  7. Place boot trim into position, slide INNER BOOT through wall from adjacent room and attach to inner liner. Slide OUTER BOOT through wall from adjacent room and attach to casing side.
  8. Place grill in position and secure to wall.

NOTE: Maximum boot length is 10”
COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
21 ROUGH-INS FOR
SIDE DISCHARGE KITS
Install plaster grounds as shown to the left.
NOTE: When side discharge Kit No. 30SRB is being used, furnace should be set exactly 4” from side wall.
TROUBLESHOOTING CHART ( For Qualified Service Technician ) – MAIN BURNER
Please follow the following corrective actions in order.

SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION

Flame Too
Large| 1. Defective operator section of valve.
2. Burner orifice too large.
3.  If installed above 2,000 feet.| 1. Replace valve.
2. Check with local gas company for proper orifice size and replace.
3. See orifice chart, (Fig. 10 on page 12).
Yellow Burner
Flame| 1.  Clogged burner ports.
2.  Obstructions around vent cap.| 1.  Remove main burner and check for obstructions in throat, ports, and orifices. Clean – but do not enlarge ports or rifices.
2.  Make sure area around vent cap is clear, be sure vent system is sealed.
Gas Odor| 1.  Gas leak.| 1.  See page 1.
Delayed
Ignition| 1.  Pilot flame too small.
2.  Burner ports clogged at pilot.
3.  Low gas pressure.
4.  Pilot decreases in size when main burners come on.| 1.  Adjust pilot flame.
2.  Clean burner ports (do not enlarge).
3.  Check gas supply pressure.
4.  Supply piping is too small. Consult local gas company or competent installer.
Failure
to Ignite| 1.  Main gas off.
2.  Thermostat not set high enough to call for heat.
3.  Clogged burner orifice.
4.  Thermostat wired wrong or defective.| 1.  Open all manual gas valves.
2.  Set thermostat to higher temperature.
3.  Clean burner orifice (do not enlarge).
4.  Check wiring, jump across thermostat terminals at valve, if valve open, re-check wires,  replace thermostat.
Burner Won’t
Turn Off| 1.  Defective or damaged
thermostat wire, or thermostat.
2.  Thermostat location.
3.  Defective or sticking valve.
4.  Excessive gas pressure.| 1.  Can be checked by removing wire from valve terminal. If valve goes off, replace wire or thermostat.
2.  Follow instructions, check location.
3.  Replace valve.
4.  Contact utility supplying gas.
Incorrect
Gas Input| 1.  Gas input not checked.
2.  Clogged orifice.| 1.  Re-check gas input.
2.  Clean orifice with a smooth wood toothpick, do not enlarge.
Not Enough
Heat| 1.  Furnace undersized.
2.  Thermostat set too low.
3.  Incorrect supply pressure.| 1.  This is especially true when a dwelling or room is enlarged. Have the heat loss calculated and compare to furnace output. Your gas company can supply you with this information. If furnace is undersized, replace with correct size unit.
2.  Raise temperature setting.
3.  Check supply pressure.
Too Much
Heat| 1.  Thermostat set too high.
2.  Combination control valve stuck open.| 1.  Lower temperature setting.
2.  Replace combination control valve.
Pilot and
Main Burner
go out During
Normal
Operation| 1.  Weak thermocouple.
2.  Input too high.
3.  Cover around pilot lighter hole not air tight.
4.  Vent tubes not properly installed or sealed.| 1.  Check millivoltage and replace if low.
2.  Check input rate.
3.  Tighten wing nuts securing cover and sight glass. Check and replace gasket if needed.
4.  Follow instructions. Check both exhaust and air intake tubes, and vent cap. Be sure all gaskets are in place and properly sealed. Use only tubes and vent cap supplied. Do not
alter vent tubes or cap.
**Burner Won’t Turn On| ** 1.   Gas valve not turned on.
2.   No voltage to valve.| 1.    Turn gas valve to “on” position.
2.   Check for 24 Volts to valve from transformer.
---|---|---
| 3. Defective thermostat.| 3. Check wall thermostat.
| 4. No 115 V. Line voltage.| 4. Provide line voltage.
| 5. Gas valve defective.| 5. Replace gas valve.
| 6. Manual reset switch not engaged.| 6. Depress red button on switch.
**
Pilot Won’t Light, or Won’t Stay Lit| ** 1.   Air in line.
2.   Defective thermocouple
3.   Pilot flame too low.| 1.   Bleed line.
2.   Replace thermocouple.
3.   Adjust pilot flame.
Standing Pilot| 4. Manual reset switch not engaged.| 4. Depress red button on switch.
**
Pilot Won’t Light
**I.I.D. Pilot| 1.   Sparker won’t work.
2.   Sparker won’t light pilot.
3.   Manual reset switch not engaged.| **** 1.   Check wire connections, provide adequate ground.
2.   a. Pilot flame too small.
b. Turn valve to “on” position.
c. Check for pilot restriction.
3.   Depress red button on switch.

INSTALLATIONS IN THE STATE OF MASSACHUSETTS

All installations in the State of Massachusetts must use the following requirements when installing, maintaining or operating direct-vent propane or natural gas-fired space heaters.
For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:

  1. If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and alarm shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).

  2. A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall:
    a. Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the appliance and the carbon monoxide detector.
    b. Have battery back-up power;
    c. Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
    d. Have been approved and listed by a Nationally  Recognized Testing Laboratory as recognized under 527 CMR.
    A CARBON MONOXIDE DETECTOR SHALL:
    a. Be located in the room that houses the appliance or equipment;
    b. Be either hard-wired or battery powered or both; and
    c. Shall comply with NFPA 720 (2005 Edition).

  3. A product-approved vent terminal must be used, and if applicable, a product-approved air intake must be used. Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.

  4. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.

TROUBLESHOOTING CHART ( Specifically for Intermittent Ignition System ) –

IID

Please follow the following corrective actions in order.

GREEN LED FLASH
CODE (XxY)ª| INDICATES| NEXT SYSTEM ACTION| RECOMMENDED SERVICE ACTION
---|---|---|---
OFF| No Call for Heat| Not Applicable| None
Flash Fast| Startup – Flame
Sense Calibration| Not Applicable| None
Heartbeat| Normal Operation| Not Applicable| None
2| 5 min. Retry Delay
Pilot flame not
detected during
trial for ignition| Initiate new trial for ignition after retry
delay completed.| If system fails to light on next trial for ignition check gas supply, pilot burner, spark and flame sense wiring, flame rod contaminated or out of position, burner ground connection.
3| Recycle
Flame failed
during run| Initiate new trial for ignition. Flash code
will remain through the ignition trial until
flame is proved.| If system fails to light on next trial ignition, check gas supply, pilot burner, flame sense wiring, contamination of flame rod, burner ground connection.
4| Flame sensed
out of sequence| If situation self corrects within 10
seconds, control returns to normal
sequence. If flame out of sequence
remains longer than 10 seconds, control
goes to Flash code 6+4 (see below).| Check for pilot flame. Replace gas valve if pilot flame present. If no pilot flame, cycle “Call for Heat”. If error repeats, replace control.
7| Flame sense
leakage to ground| Control remains in wait mode. When the
fault corrects, control resumes normal
operation after a one minute delay.| Check flame sense lead wire for damage or shorting. Check that flame rod is in proper position. Check flame rod ceramic for cracks, damage or tracking.
8| Low secondary
voltage supply –
(below 15.5 Vac)| Control remains in wait mode. When the
fault corrects, control resumes normal
operation after a one minute delay.| Check transformer and AC lines for proper input voltage to the control. Check with full system load on the transformer.
6 + 2| 5 minute Retry
Delay – On every
third retry on the
same “Call for Heat”| Initiate new trial for ignition after retry
delay completed.| Check gas supply, pilot burner, spark and flame sense wiring,  flame rod contaminated or out of position, burner ground connection.
6 + 3| On every 6th
flame failure during
run on the same
“Call for Heat”| 5 minute retry delay, then initiate new trial
for ignition.| Check gas supply, pilot burner, flame sense wiring,
contamination of flame rod, burner ground connection.
6 + 4| Flame sensed out
of sequence – longer
than 10 seconds| Control waits until flame is no longer
sensed and then goes to soft lockout.
Flash code continues. Control auto resets
from soft lockout after one hour.| Check for pilot flame. Replace gas valve if pilot flame present. If no pilot flame, cycle “Call for Heat”. If error repeats, replace control.
ON| Soft lockout due
to error detected
during self check
sequences| Control auto resets from soft lockout after
one hour.| Reset by cycling “Call for Heat”. If error repeats, replace the control.

DIRECT VENT COUNTERFLOW WALL FURNACE PARTS LIST

Natural Gas: DVCF403C-H, DVCF553C-H, DVCF407C-H, DVCF557C-H
Propane Gas: DVCF404C-H, DVCF554C-H, DVCF408C-H, DVCF558C-H
COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
22 ATTN: CONTRACTORS AND
QUALIFIED SERVICE TECHNICIANS:
We only sell parts through our wholesalers. For prompt parts service, contact the wholesaler from which you purchased your Cozy heater.
HOW TO PROPERLY ORDER PARTS:
In addition to the part description and numbers, please be prepared to provide:
– Model Number
– Serial Number
– Type of Gas Used
This information can be found on the rating plate that is attached to the heater.

Natural Gas Model Numbers DVCF404C-H DVCF407C-H DVCF553C-H DVCF557C-H
Propane Gas Model Numbers DVCF403C-H DVCF408C-H DVCF554C-H DVCF558C-H
REF. # PART DESCRIPTION PART NO. PART NO. **PART
NO.**

PART NO.

---|---|---|---|---|---
1A| Casing Side , Right| 34065| 34065| 34560| 34560
1B| Casing Side , Left| 34055| 34055| 34550| 34550
1C| Center Front Panel Assembly| 34104| 34104| 30534| 30534
1D| Top Assembly| 34050| 34050| 34050| 34050
1E| Upper Back Assembly| 34080| 34080| 34080| 34080
1F| Lower Back Assembly| 34090| 34090| 34575| 34575
1G| Bottom Assembly| 34070| 34070| 34070| 34070
N/A| Casing Mounting Brackets| 30260| 30260| 30260| 30260
2| Liner Assembly| 34115| 34115| 34600| 34600
3| Fan Shroud Assembly| 34140-10| 34140-10| 34140-10| 34140-10
4| Top Louver| 34100| 34100| 34590| 34590
6| Bottom Louver Assembly| 30100| 30100| 30100| 30100
7| Upper Front Shield| 30250| 30250| 30250| 30250
8| Switch Box| 30252| 30252| 30252| 30252
9| Switch Box Cover| 30253| 30253| 30253| 30253
10| Lower Front Shield| 30256| 30256| 30256| 30256
11| Motor Mounting Bracket| 34088| 34088| 34579| 34579
16| Fan Motor| 72108| 72108| 72110| 72110
17| Fan Blade , Dynacone| 72111| 72111| 72111| 72111
18| Rubber Grommet (Requires 4)| 78010| 78010| 78010| 78010
19| Limit Switch , 60T11-L220F| N/A| N/A| 72160| 72160
19| Limit Switch , 60T11-L180F| 78065| 78065| N/A| N/A
20| Fan Switch , 60T12 F110 Degree| 78064| 78064| 78064| 78064
22| Aux. Limit Switch , 60T15-L350| 78086| 78086| 78086| 78086
24| Transformer| 78069| 78069| 78069| 78069
N/A| Transformer Plate| 34089| 34089| 34089| 34089
26| Cozy Handle| 84003| 84003| 84003| 84003
30| Wiring Harness| 72251| 72252| 72253| 72250
35| Terminal Board| 78300| 78300| 78300| 78300
36| Flue Outlet Pipe Gasket – 7” Circle| 72055| 72055| 72055| 72055
37| Air Intake Pipe Gasket – 9-1/2” Circle| 72054| 72054| 72054| 72054
38| Heat Exchanger Cover Plate Gasket – 7×6”| 72053| 72053| 72053| 72053
39| Burner Box Inlet Gasket – 11-1/2×5” (Air Box)| 72052| 72052| 72052| 72052
40| Exhaust Pipe Gasket – 7” Circle| 72051| 72051| 72051| 72051
44| Heat Exchanger Kit| 34805| 34805| 34815| 34815
45 & 46| Vent Cap Assy. w/ Spacer Plate Complete| 34250| 34250| 34250| 34250
47| Vent Cap Mounting Kit| 34330| 34330| 34330| 34330
48| Air Intake Pipe Assembly| 34280| 34280| 34280| 34280
49| Vent Exhaust Pipe Assembly| 34290| 34290| 34290| 34290
50| Slip Joint Assembly w/Gaskets| 34220| 34220| 34220| 34220
51| Air Drop Assembly| 34201| 34201| 34630| 34630
52| Heat Exchanger Cover Plate| 34195| 34195| 34195| 34195
61| Slip Joint Ring Gasket – 9-1/2” Circle| 72056| 72056| 72056| 72056
N/A| Slip Joint Gasket – 3-1/2×7| 72057| 72057| 72057| 72057
N/A| Slip Jt. Ring Gsk. (2 pc. Graphite) 3-3/4×7-1/2”| 72058| 72058| 72058| 72058

COZY DVCF403C-H Direct Vent Counterflow Wall Furnace - fig
23 ATTN: CONTRACTORS AND
QUALIFIED SERVICE TECHNICIANS:
We only sell parts through our  wholesalers. For prompt parts service, contact the wholesaler from which you purchased your Cozy heater.
HOW TO PROPERLY ORDER PARTS:
In addition to the part description and numbers, please be prepared to provide:
– Model Number
– Serial Number
– Type of Gas Used
This information can be found on the rating plate that is attached to the heater.

Natural Gas Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . .

Propane Gas Model Numbers . . . . . . . . . . . . . . . . . . . . . . . .

| DVCF403C-H DVCF404C-H| DVCF407C-H DVCF408C-H| DVCF553C-H DVCF554C-H| DVCF557C-H DVCF558C-H
---|---|---|---|---
REF. #| PART DESCRIPTION| PART NO.| PART NO.| PART NO.| PART NO.
12| Burner| 72107| 72107| 72107| 72107
13| Valve, VR8200H-1004 , Nat. W/78089 Dis. Bushing| 78090| N/A| 78090| N/A
13| Valve, VR8200H-1103 , L.P. w/78089 Dis. Bushing| 78091| N/A| 78091| N/A
13b| Valve, VR8204H-1006 , Nat. w /78089 Dis. Bushing 13b| N/A| 78092| N/A| 78092
13b| Valve, VR8204H-1006 (Conv.) , L.P. w/78089 Bushing| N/A| 78093| N/A| 78093
N/A| Disappearing Bushing , 1/2×3/8| 78089| 78089| 78089| 78089
14| Manifold| 72103| 72103| 72103| 72103
15| Burner Orifice , Natural Gas| 72147| 72147| 72140| 72140
15| Burner Orifice , L.P. Gas| 72149| 72149| 72141| 72141
23| Thermostat , 24 Volt| 78355| 78355| 78355| 78355
25| Pilot 0.140.512 , Natural Gas (w/Electrode)| 72020| N/A| 72020| N/A
25| Pilot 0.140.502 , L.P. Gas (w/Electrode)| 72021| N/A| 72021| N/A
25b / 28b| Pilot Assy. Electronic w /Flame Ignitor Nat.| N/A| 78098| N/A| 78098
25b / 28b| Pilot Assy. Electronic w /Flame Ignitor L.P.| N/A| 78099| N/A| 78099
27| Thermostat Wire| 74518| 74518| 74518| 74518
28| Thermocouple Q309A1954| 78095| N/A| 78095| N/A
29| Insulated Staples| 74209| 74209| 74209| 74209
N/A| Power Cord| 78213| 78213| 78213| 78213
31| Sight Glass Assy. (Includes Cover & Gasket)| 43252| 43252| 43252| 43252
32| Sight Glass Cover| 43258| 43258| 43258| 43258
33| Sight Glass Gasket – 1-3/8×3”| 72067| 72067| 72067| 72067
34| Burner Box Gasket| 72059| 72059| 72059| 72059
41| Piezo Igniter| 80016| N/A| 80016| N/A
42| Igniter Wire 0.028.508| 72022| N/A| 72022| N/A
43| Ignition ControlBox S8600B, Honeywell| N/A| 78097| N/A| 78097
N/A| Elbow 3/8×90 Degree| 84501| 84501| 84501| 84501
53| Pilot Bracket| 34440| 34440| 34440| 34440
55| Manifold Gasket – 2×2”| 72068| 72068| 72068| 72068
56| Burner Access Door| 34425| 34425| 34425| 34425
57| Burner Access Gasket – 4×13”| 72065| 72065| 72065| 72065
58| Burner Box Bottom Assembly| 34400| 34400| 34400| 34400
N/A| 90 Deg. Pilot Fitting| N/A| 70352| N/A| 70352
59| Pilot Tube Gasket – 2-1/2×3/4”| 72063| 72063| 72063| 72063
60| Pilot Tube Bracket| 34475| 34475| 34475| 34475
N/A| Vent Terminal Shield| 34950| 34950| 34950| 34950
N/A| Pilot Tubing w/Fittings – 16”| 78452| 78452| 78452| 78452
N/A| Lighting Instructions DVCF| 91260| 91261| 91260| 91261

NOTE: Parts & schematic drawings on current models are shown at: cozyheaters.com | Specifications subject to change without notice.

LIMITED WARRANTY

The manufacturer, Williams Comfort Products, warrants this Cozy wall furnace or heater to the original purchaser under the following conditions: ANY WARRANTY  ONSIDERATIONS ARE CONTINGENT ON INSTALLATION BY A QUALIFIED INSTALLER (CONTRACTOR). SELF-INSTALLATION IS PROHIBITED AND WILL INVALIDATE YOUR WARRANTY.
LIMITED ONE-YEAR WARRANTY

  1. Any part thereof which proves to be defective in material or workmanship within one year from date of original purchase for use will be replaced at the Manufacturer’s option, FOB to its factory.
  2. No liability is assumed by the Manufacturer for removal or installation labor costs, nor for freight or delivery charges.

LIMITED EXTENDED WARRANTY

  1. In addition to the above limited one year warranty on the complete unit, any combustion chamber which burns out or rusts under normal installation, use and service conditions during a period of nine years following expiration of the one-year warranty period will be exchanged for a like or functionally similar part.
  2. No liability is assumed by the Manufacturer for removal or installation labor costs, nor for freight or delivery charges.

LIMITATIONS

  1. THIS LIMITED WARRANTY IS THE ONLY WARRANTY MADE BY THE MANUFACTURER, IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE ARE LIMITED TO THE SAME ONE YEAR TERM AS THE EXPRESS WARRANTY. UNDER NO IRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, SPECIAL OR CONTINGENT DAMAGES OR EXPENSES ARISING DIRECTLY OR INDIRECTLY FROM ANY DEFECT IN THE PRODUCT OR ANY COMPONENT OR FROM THE USE THEREOF. THE REMEDIES SET  FORTH HEREIN ARE THE EXCLUSIVE REMEDIES AVAILABLE TO THE USER AND ARE IN LIEU OF ALL OTHER REMEDIES.
    Some states do not allow limitation on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you.

  2. This warranty does not include any charge for labor or installation.

  3. This warranty does not extend to painted surfaces or to damage or defects resulting from accident, alteration, misuses or abuse or improper installation.

  4. This warranty does not cover claims which do not involve defective workmanship or materials.

DUTIES OF THE CONSUMER

  1. The heating equipment must be installed by a qualified installer and operated in accordance with the installation and homeowner’s instructions furnished with the equipment.
  2. Any travel, diagnostic costs, service labor, and labor to repair the defective unit will be the responsibility of the owner.
  3. A bill of sale, canceled check, payment record or permit should be kept to verify purchase date to establish the warranty period.
  4. Have the installer enter the requested information in the space below.

GENERAL

  1. The manufacturer neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with said equipment.
  2. Service under this warranty should be obtained by contacting your dealer. Provide the dealer with the model number, serial number, and purchase date verification.
  3. If, within a reasonable time after contacting your dealer, satisfactory service has not been received, contact: Customer Service Department, 250 West Laurel Street, Colton, CA 92324 for assistance.
  4. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.

TO REGISTER YOUR FURNACE: GO ONLINE TO THE COZY HEATERS WEBSITE AT:
www.cozyheaters.com/warranty-registration/
COZY HEATING SYSTEMS
250 WEST LAUREL STREET – COLTON, CA 92324

Documents / Resources

| COZY DVCF403C-H Direct Vent Counterflow Wall Furnace [pdf] Instruction Manual
DVCF403C-H, DVCF553C-H, DVCF407C-H, DVCF557C-H, Direct Vent Counterflow Wall Furnace
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals