COZY CDV155C Direct Vent Wall Furnace Installation Guide

June 13, 2024
Cozy

COZY CDV155C Direct Vent Wall Furnace

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death. Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance.
  • Do not touch any electrical switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.

INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference. The coating selected to provide longer life to the heat exchanger may smoke slightly upon initial firing. Please provide adequate ventilation if this occurs.

The appliance may be installed in an aftermarket permanently located, manufactured home (USA only), or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.

WARNING: Operation of this furnace without the properly installed, furnished vent system and vent cap could result in Carbon Monoxide (CO) poisoning and possible death. For your safety, this furnace and the vent system should be inspected at least annually by a qualified service technician. This unit is for residential use only and is not approved for installation in greenhouses, or environments involving dusty, wet, corrosive, or explosive conditions. Such conditions will invalidate the warranty and may create unsafe conditions. Installation, maintenance, service, troubleshooting, and repairs must be performed by a qualified service agency. Mr./Mrs. Homeowner, DO NOT attempt any of these procedures yourself as this could expose you to property damage, personal injury, or loss of life and will invalidate all warranties.

The State of Massachusetts requires that the installation and service of a gas appliance be performed by a plumber or gas fitter licensed in the Commonwealth of Massachusetts.

INTRODUCTION

THIS IS A GAS-FIRED, DIRECT VENT WALL FURNACE THAT WILL OPERATE SAFELY AND PROVIDE AN EFFICIENT SOURCE OF HEAT WHEN INSTALLED, OPERATED, AND MAINTAINED AS RECOMMENDED IN THIS INSTALLATION AND OPERATING INSTRUCTIONS. READ THESE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING, SERVICING, OR USING THE APPLIANCE. IF YOU DO NOT UNDERSTAND ANY PART OF THESE INSTRUCTIONS CONSULT LOCAL AUTHORITIES, OTHER QUALIFIED INSTALLERS, THE SERVICE TECHNICIAN, THE GAS SUPPLIER, OR THE MANUFACTURER

SPECIFICATIONS AND DIMENSIONS
Your Direct Vent Wall Furnace is shipped complete in one carton. This carton contains the furnace, vent cap, vent tube, air inlet tube, template with rough-in dimensions, installation and operating instructions, and the thermostat with thermostat wire.
NOTE: There will be two cartons if an optional vent kit or blower is purchased

MODEL NO.| INPUT BTU/HR.|

WIDTH

|

DEPTH

|

HEIGHT

| GAS CONN.| TYPE GAS| MAX. WALL THICKNESS| MIN. WALL THICKNESS
---|---|---|---|---|---|---|---|---

CDV155C

|

15,000

|

18”

|

9-3/4”

|

29-3/4”

|

½”

|

NAT.

|

24”

|

5 ”

CDV156C| 15,000| 18”| 9-3/4”| 29-3/4”| ½”| L.P.| 24”| 5 ”
CDV255C| 25,000| 34-1/2”| 9-3/4”| 31-3/4”| ½”| NAT.| 24”| 5 ”
CDV256C| 25,000| 34-1/2”| 9-3/4”| 31-3/4”| ½”| L.P.| 24”| 5 ”
CDV335C| 33,000| 34-1/2”| 9-3/4”| 31-3/4”| ½”| NAT.| 15”| 5 ”
CDV336C| 33,000| 34-1/2”| 9-3/4”| 31-3/4”| ½”| L.P.| 15”| 5 ”

SAFETY RULES

  1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, bodily injury, or death.
  2. Use in other than a residential application may result in unsatisfactory performance and may void the warranty.
  3. This appliance must be installed in accordance with local codes, if any; if not, follow the National Fuel Gas Code ANSI Z223.1/NFPA 54 or the National Gas and Propane Installation Code CSA-B149.1.
  4. Do not install this wall furnace in a recreational vehicle or trailer.
  5. Do not operate wall furnace unless it is connected to the factory-supplied vent system with vent cap in place.
  6. Check the rating label attached to the wall furnace to be sure it is equipped for the type gas you intend to use.
  7. Never use a match, candle, flame or other source of ignition to check for gas leaks. Use only soapy water or liquid detergent.
  8. Have your wall furnace and vent system inspected at least annually by a qualified service technician.
  9. Before cleaning or servicing, turn off the gas and allow the furnace to cool.
  10. Do not operate wall furnace without the outer casing in place.
  11. Due to high temperatures, the wall furnace should be located out of traffic and away from furniture and drapes.
  12. Children and adults should be alerted to the hazard of high surface temperature and should be kept away to avoid burns or clothing ignition.
  13. Young children should be carefully supervised when they are in the same room with the wall furnace.
  14. Do not place clothing or other flammable material on or near the furnace.
  15. Installation and repair should be done by a qualified service technician.
  16. The wall furnace should be inspected before use and at least annually by a professional service technician.
  17. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc.
  18. It is imperative that control compartments, burner, and circulating air passageways of the furnace be kept clean.
  19. Do not install in a closet, alcove, or small hallway where the furnace could be isolated from the space to be heated by closing a door.
  20. Do not put anything around the furnace or vent cap that will obstruct the flow of combustion and ventilation air.
  21. The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the latest edition of the National Electrical Code, ANSI/NFPA 70. In Canada, use CSA C22.1 Canadian Electrical Code.
  22. Never operate this furnace without the sight glass in place or with the glass broken or missing.
  23. If it is suspected that rising water may enter the furnace, turn off the gas immediately. Do not use this appliance if any part has been underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.
  24. It is necessary to replace damaged gaskets or sealing material within the vent or air intake system. Failure to do so may result in property damage, personal injury or loss of life.
  25. Any safety screen or guard removed for servicing must be replaced prior to operating the heater.
  26. A gas appliance must not be connected to a chimney flue serving a separate solid-fuel-burning appliance.

CLEARANCES

  1. If the wall furnace is installed directly on carpeting, tile or any combustible material other than wood flooring, the wall furnace shall be installed on a metal plate or wood panel secured to the floor, extending the full width and depth of the wall furnace.
  2. RESIDENTIAL GARAGE INSTALLATION: Gas utilization equipment in residential garages shall be installed so that all burners and burner ignition devices are located not less than 18 inches (46cm)
    above the floor. Such equipment shall be located, or protected so it is not subject to damage by a moving vehicle. Use care in selecting a good location within the garage. DO NOT locate the appliance where heated air will be directed onto a nearby parked vehicle. Paint may discolor or rubber may harden and crack. DO NOT allow heated discharge air to blow directly onto open or closed containers of paint, gasoline or other liquids having flammable vapors.

VENT TERMINAL CLEARANCES


REFERENCE LETTERTO DRAWING

| CANADIAN INSTALLATIONS 1| ****

U.S. INSTALLATIONS 2

---|---|---
A = Clearance above grade, veranda,

porch, deck, or balcony

| 12 Inches (30 cm)| 12 Inches (30 cm)
B = Clearance to window or door that may be opened| 12 Inches (30 cm)| 9 Inches (23 cm)
C = Clearance to permanently closed

window

| 12 Inches (30 cm)| 9 Inches (23 cm)
D = Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 Feet (61 cm)

from the center line of the terminal

| 18 Inches (46 cm)| 18 Inches (46 cm)
E = Clearance to unventilated soffit| 18 Inches (46 cm)| 18 Inches (46 cm)
F = Clearance to outside corner| 12 Inches (30 cm)| 12 Inches (30 cm)
G = Clearance to inside corner| 12 Inches (30 cm)| 12 Inches (30 cm)
H = Clearance to each side of center line extended above meter/regulator

assembly

| 3 Feet (91 cm) within a height 15 Feet (4.5m) above the meter/

regulator assembly

| Clearance in accordance with local installation codes and the

requirements of the gas supplier

I = Clearance to service regulator vent outlet| 3 Feet (91 cm)| Clearance in accordance with local installation codes and the

requirements of the gas supplier

J = Clearance to nonmechanical air supply inlet to building or the combustion

air inlet to any other appliance

| 12 Inches (30 cm)| 12 Inches (30 cm)
K = Clearance to a mechanical air supply inlet| 6 Feet (1.83 m)| 3 Feet (91 cm) above if within 10 Feet (3 m) horizontally
L = Clearance above paved sidewalk or

paved driveway located on public property

| 7 Feet (2.13m) A vent shall not

terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and

serves both dwellings

| Clearance in accordance with

local installation codes and the requirements of the gas supplier

M = Clearance under veranda, porch, deck, or balcony| 12 Inches (30 cm) permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides| Clearance in accordance with local installation codes and the requirements of the gas supplier

  1. In accordance with the current CSA-B149.1 Natural Gas and Propane Installation Code
  2. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code

LOCATION

  1. The wall furnace must be installed on an outside wall.
  2. For optimal heat distribution, locate the furnace as centrally as possible in the area to be heated and where occupants may move about freely without coming into contact with the grille.
  3. If the furnace is installed in a basement, a 12” clearance must be maintained between ground level and the bottom of the vent cap. Do not install a furnace where vent cap will terminate in a window well or any other opening below ground level.

INSTALLATION

Failure to follow these instructions carefully could result in poor performance, property damage, personal injury or death.

STEP 1. LOCATE VENT OPENING. Locate wall studs and center 9” vent opening a minimum of 22” for CDV15 or 24-1/8” for CDV25/33 above the floor. To locate furnace at minimum clearance from floor, remove the template from carton and set on floor at the location desired. On model CDV15, position template no closer than 1” from either side wall. For model CDV25/33, position template 1” minimum from a left side wall or 0” from a right side wall. Check outside wall to be sure there is proper clearance around the vent cap. See Figure 3. Next, mark and cut out the vent openings on both the inside and outside walls (be sure to keep the holes level). See Figure 5. If a higher location on the wall is desired, raise bottom of the template to the desired height, make sure template is level and centered between studs, mark and cut out vent openings.

STEP 2. ROUGH-IN GAS SUPPLY . Install a ½” diameter gas supply line. This line can enter through the floor, side, or rear wall. For location of gas connection to valve, see Fig. 4. The gas supply line must have an individual manual shut-off valve located outside the cabinet, accessible from the room where the heater is installed. Install a drip leg immediately ahead of the gas valve and provide a 1/8” N.P.T. plugged tapping, accessible for test gauge connection, immediately upstream of the gas supply connection. The furnace and the individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2” psig (3.5kPa). The furnace must be isolated from the gas supply piping system by closing the individual manual shut off valve during any pressure testing of the gas piping system at test pressures equal to or less than 1/2” psig (3.5kPa).

STEP 3. INSTALLING FURNACE – 5” TO 9” WALLS. Use only the exhaust tube, air intake tube, wall thimble extension, and vent terminal provided with furnace. Do not attempt to lengthen the exhaust or air intake tubes, this could cause an imbalance in the furnace resulting in poor performance and pilot outage, see Figure 6. Extend the telescoping wall thimble extension (surrounding the wall thimble assembly) to approximately 9 inches. Center the wall thimble assembly in the 9 inch opening and attach to inside wall using eight (8) screws. The wall thimble extension should extend through the opening and be adjusted so end of wall thimble extension is even with outside wall. Install furnace flush to wall by sliding exhaust tube and air intake tube through the wall thimble assembly.

Secure the furnace to the wall with screws through each of the four holes in the mounting brackets located on the back of the furnace. These holes are spaced so as to allow the screws to enter into studs that are on 16 inch centers. On certain types of wall, anchors (not provided) may be required. Slide the vent terminal onto the exhaust tube and the air intake tube. Secure vent terminal and vent terminal spacer plate to wall providing a slight downward slope to the vent tubes. This will prevent water from entering. Anchors (not provided) may be required. Caulk around vent terminal spacer plate with putty provided. See Figure NOTE: Some framing may be necessary to provide a flat surface for the vent terminal spacer plate to butt against, so rain cannot enter through cut out.

INSTALLING FURNACE – 9 TO 15” WALLS (CDV15/CDV25-C)

For 9” to 15” wall use Vent Kit No. VK1525/9-15-B. Do not attempt to lengthen the exhaust tube, air intake tube, or wall thimble extension provided with a furnace or the VK1525/9-15-B Vent Kit. Disconnect the air intake tube, and the exhaust tube from the back of the furnace and discard. See Figure 6. Replace with exhaust tube and air intake tube from Kit No. VK1525/9-15-B. Discard the 5” telescoping wall thimble extension that surrounds the wall thimble assembly. Center the wall thimble assembly in the 9” opening and attach to the inside wall using eight (8) screws. Install furnace flush to wall by sliding exhaust tube and air intake tube through the wall thimble assembly. Secure the furnace to the wall with screws through each of the four holes in the mounting brackets located on the back of the furnace

These holes are spaced so as to allow the screws to enter into studs that are on 16-inch centers. On certain types of wall, anchors (not provided) may be required. From outside the building install the thick wall thimble extension, Part No. 43835, supplied in Vent Kit No. VK1525/9-15-B by sliding it through the cut out and over the wall thimble assembly. The wall thimble extension should be even with the outside wall (some trimming may be necessary). Slide the vent terminal onto the exhaust tube and the air intake tube. Secure vent terminal and vent terminal spacer plate to wall providing a slight downward slope to the vent tubes. This will prevent water from entering. Anchors (not provided) may be required. Caulk around the vent terminal spacer plate with putty provided. See Figure 7.
NOTE: Some framing may be necessary to provide a flat surface for the vent terminal spacer plate to butt against, so rain cannot enter through cut out.

INSTALLING FURNACE – 15” TO 24” WALLS (CDV15/CDV25-C).
For 15” to 24” wall use only Vent Kit No. VK1525/15-24-B. Do not attempt to lengthen the exhaust tube, air intake tube, or wall thimble extension provided with furnace. The VK1525/15-24-B Vent Kit has a one inch restrictor in the exhaust tube which is necessary for proper and safe operation of this furnace. Do not use any other vent kit. Disconnect the air intake tube and the exhaust tube from the back of the furnace and discard, see Figure 6. Install the exhaust tube and air intake tube from Vent Kit No. VK1525/15-24-B. Discard the 5” telescoping wall thimble extension that surrounds the wall thimble assembly.

Center the wall thimble assembly in the 9” opening and attach to inside wall using eight (8) screws. Install furnace flush to wall by sliding exhaust tube and air intake tube through the wall thimble assembly. Secure the furnace to the wall with screws through each of the four holes in the mounting brackets located on the back of the furnace. These holes are spaced so as to allow the screws to enter into studs that are on 16-inch centers. On certain types of walls, anchors (not provided) may be required. From outside the building install the wall thimble extension, Part No. 43730, supplied in Vent Kit No. VK1525/15-24-B by sliding it through the cut out and over the wall thimble extension. For walls 15” to 19” the wall thimble extension, air intake tube, and the exhaust tube must be trimmed even with the outside wall. Slide the vent terminal onto the exhaust tube and into the air intake tube.

Secure vent terminal and vent terminal spacer plate to wall providing a slight downward slope to the vent tubes. This will prevent water from entering. Anchors (not provided) may be required. Caulk around the vent terminal spacer plate with putty provided, see Figure 7.
NOTE: Some framing may be necessary to provide a flat surface for the vent terminal spacer plate to butt against, so rain cannot enter through the cut out.

INSTALLING FURNACE – 9 TO 15” WALLS (CDV33-C)
For 9” to 15” wall use Vent Kit No. VK33/9-15-B. Do not attempt to lengthen the exhaust tube, air intake tube, or wall thimble extension provided with furnace or the VK33/9-15-B Vent Kit. Disconnect the air intake tube, and the exhaust tube from the back of the furnace and discard. See Figure 6. Replace with exhaust tube and air intake tube from Kit No. VK33/9-15-B. Discard the 5” telescoping wall thimble extension that surrounds the wall thimble assembly. Center the wall thimble assembly in the 9” opening and attach to inside wall using eight (8) screws.

Install furnace flush to wall by sliding exhaust tube and air intake tube through the wall thimble assembly. Secure the furnace to the wall with screws through each of the four holes in the mounting brackets located on the back of the furnace. These holes are spaced so as to allow the screws to enter into studs that are on 16-inch centers. On certain types of wall, anchors (not provided) may be required. From outside the building install the thick wall thimble extension, Part No. 43835, supplied in Vent Kit No. VK33/9-15-B by sliding it through the cut out and over the wall thimble assembly. The wall thimble extension should be even with the outside wall (some trimming may be necessary).

Slide the vent terminal onto the exhaust tube and the air intake tube. Secure vent terminal and vent terminal spacer plate to wall providing a slight downward slope to the vent tubes. This will prevent water from
entering. Anchors (not provided) may be required. Caulk around the vent terminal spacer plate with putty provided. See Figure 7. NOTE: Some framing may be necessary to provide a flat surface for the vent terminal spacer plate to butt against, so rain cannot enter through cut out.

GAS CONNECTION

Make gas connection between manual shut-off valve and furnace valve with approved connectors. Compounds used on threaded joints of gas piping shall be approved for use with L.P gas. The gas lines must be checked for leaks by the installer with soapy water or liquid detergent, never an open flame. If connections are not exposed, a pressure test must be run. Be sure to disconnect the gas supply line from the appliance valve before pressure testing. The manifold pressure is pre-set at the factory and should be 3.5” w.c. for Natural Gas and 10” w.c. for L.P. Gas. The minimum inlet pressure for Natural Gas is 4.5” w.c. and 11” w.c. for L.P. Gas, “for purpose of input adjustment”. The maximum inlet pressure should never exceed 7.0” w.c. on Natural Gas or 14” w.c. on L.P. Gas.

LIGHTING INSTRUCTIONS / MILLIVOLT (SELF GENERATING)
MODELS: CDV155C, CDV156C, CDV255C, CDV256C, CDV335C, CDV336C

FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing damage, personal injury or loss of life.

  • This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.
  • BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance.
  • Do not touch any electric switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.
  • Use only your hand to push in or turn the gas control knob. Never use tools.
  • If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
  • Do not use this appliance if any part has been underwater.
  • Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water.

LIGHTING INSTRUCTIONS

  1. STOP! Read the information on the safety label.
  2. Set the thermostat to lowest setting.
  3. Turn off all electric power to the appliance”.
  4. Remove cabinet.
  5. Push in gas control knob slightly and turn clockwise to “OFF”
  6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas,
  7. STOP! Follow “B” in the safety information on the safety label. If you don’t smell gas, go to the next step. Open-sight glass cover.
  8. Locate red piezo ignitor button inside gas control compartment. Locate pilot behind sight glass. (Follow metal pilot tube from gas control).
  9. Turn gas control knob counterclockwise to “PILOT”.
  10. Push in gas control knob and hold in. Immediately begin a series of pushing and releasing the red piezo ignitor button, while observing the pilot through the sight glass. Continue to spark until pilot is lit. Continue to hold the gas control knob in for about one (1) minute after the pilot is lit. Release the gas control knob and it will pop back up. Pilot should remain lit. If pilot goes out, repeat steps 4 thru 9.
    • If the knob does not pop up when released, STOP and immediately call your service technician or gas supplier.
    • If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
  11. Close-sight glass cover.
  12.  Turn gas control knob counterclockwise to “ON”.
  13. Replace cabinet.
  14. Turn on all electric power to the appliance”.
  15. Set the thermostat to the desired setting

TO TURN OFF THE GAS TO THE APPLIANCE

  1. Set the thermostat to it’s lowest setting.
  2. Turn off all electric power to the appliance if service is to be performed”.
  3. Open cabinet door.
  4. Push in gas control knob slightly and turn clockwise to “OFF”. Do not force.
  5. Close cabinet door

PILOT ADJUSTMENT
Locate pilot adjustment cap on valve and remove. See Figure 8. Pilot flame should surround the top 3/8 to ½ inch of power pile or thermocouple, see Figure 9. To increase pilot flame, turn pilot adjustment screw, see Figure 8, counterclockwise. To decrease pilot flame, turn screw clockwise. After a proper pilot flame is established replace pilot adjustment cap, be sure gasket located on the bottom of cap head is in place. The gas supply to the pilot is unregulated. When line pressure exceeds 7” w.c. Natural Gas, 11” w.c. L.P. Gas, pilot adjustment must be made.

TO REMOVE THE MAIN BURNER FOR
INSPECTION AND CLEANING

  1. Remove outer casing.
  2. Disconnect gas supply to valve.
  3. Remove 11 screws holding burner door to heat exchanger and lift out complete burner, valve assembly.
  4. After inspecting burner, place back into heat exchanger. Be sure door gasket is not damaged and will effect a proper seal or pilot outage will occur.
  5. Tighten screws holding burner door to heat exchanger.
  6. Connect gas supply back to valve.
  7. Install front panel and follow lighting instructions.
    NOTE : The furnace and all components must be inspected at least annually by a qualified service technician. This should include the burner, heat exchanger, and vent system. Be sure that the flow of combustion and ventilation air are not obstructed.

BURNER ORIFICE
This appliance is equipped only for altitudes 0 – 2,000 ft. If installed above 2,000 ft., the BTU input must be reduced 4% per 1,000 ft. See the following orifice chart for the proper orifice for a specific elevation.
Orifice change must be completed by a qualified installer or service technician.

NATURAL GAS

SPECIFIC ELEVATIONS

MODEL NUMBER| 0 TO

2,000’

| 2,000’

4,000’

| 4,000’

6,000’

| 6,000’

8,000’

| 8,000’

10,00’

---|---|---|---|---|---

CDV155C

|

4 8

|

4 9

|

5 0

|

5 1

|

5 2

CDV255C| 2.45mm| 4 1| 4 2| 4 3| 4 4
CDV335C| 2.75mm| 3 7| 3 8| 4 0| 4 2

L.P. GAS
SPECIFIC ELEVATIONS

MODEL NUMBER| 0 TO

2,000’

| 2,000’

4,000’

| 4,000’

6,000’

| 6,000’

8,000’

| 8,000’

10,00’

---|---|---|---|---|---

CDV156C

|

1.2mm

|

5 6

|

5 7

|

5 9

|

6 0

CDV256C| 1.55mm| 5 4| 5 4| 5 5| 5 5
CDV336C| 1.65mm| 5 1| 5 2| 5 2| 5 3

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operations. Verify proper operation after servicing

PROPER BURNER FLAME
The burner flame may be observed by raising the sight glass cover. A proper flame will have a dark blue inner mantle that sits right on top of the burner with a lighter blue outer mantle rising over the burner, see Figure 10. There may be some yellow where the pilot flame and burner flame meet. There is no primary air adjustment on the burner, and the proper flame is assured since the correct manifold pressure and orificing has been done at the factory.

THERMOSTAT INSTALLATION
FOR CDV155C, CDV156C, CDV255C, CDV256C, CDV335C, CDV336C MODELS ONLY Follow the instructions included with the thermostat. If the thermostat is to be wall mounted, select a location in the
same room as the heater, approximately five feet above the floor on an inside wall where it won’t be affected by heat or cold sources such as direct sunlight, televisions, fireplaces, hidden hot or cold water pipes, drafts, etc. The thermostat must not be placed in an adjacent room. The furnace is equipped with a self-generating control system; never connect to a 24-volt transformer or household electric system. Do not splice or attempt to use more thermostat wire than is supplied. Connect thermostat wires to the thermostat and mount thermostat to wall, run wire to the furnace, securing with insulated staples provided, and connect to valve terminals marked TH, see Figure 8.

MODEL DVB-3 OPTIONAL BLOWER KIT

INSTALLATION INSTRUCTIONS
INSTALL ONLY ON CDV15-C / CDV25-C / CDV33 –C SERIES

  • STEP 1. REMOVE THE OUTER CASING.

  • STEP 2. REMOVE THE FLOOR SHIELD FROM THE BOTTOM OF THE HEATER AND DISCONNECT THE PIEZO WIRE.

  • STEP 3. REMOVE AND DISCARD COVER SHIELD. SAVE SCREWS.

  • STEP 4. ATTACH THE BLOWER TO THE BOTTOM OF THE FLOOR SHIELD USING SCREWS SAVED IN STEP 3. NOTE: THE BLOWER MOTOR SHOULD BE ON THE OPPOSITE END FROM PIEZO.

  • STEP 5. FOR MODELS CDV25/33-C, SECURE P/N 43625 BLOWER SHIELD TO BOTTOM OF HEAT SHIELD USING TWO (2) #8X1/2” SCREWS PROVIDED. SEE FIGURE 11.

  • STEP 6. CONNECT PIEZO WIRE AND ATTACH FLOOR SHIELD TO HEATER. SLIDE THE WHITE CABLE CLAMP
    (PROVIDED) OVER BOTH MOTOR LEAD WIRES AND THE POWER CORD. SECURE TO LEFT SIDE OF HEATER WITH THE FRONT SCREW USED TO SECURE THE FLOOR SHIELD.

  • STEP 7. ATTACH THE JUNCTION BOX TO LEFT SIDE OF THE WRAPPER USING THE FOUR #8X1/2” SCREWS PROVIDED.

  • STEP 8. PLUG POWER CORD INTO A 115-VOLT GROUNDED OUTLET.

  • STEP 9. REPLACE THE OUTER CASING AND FOLLOW LIGHTING INSTRUCTIONS TO PLACE HEATER IN OPERATION.

THE UNIT MUST BE ELECTRICALLY GROUNDED ACCORDING TO THE NATIONAL ELECTRICAL CODE ANSI/NFPA NO. 70-1987. THIS APPLIANCE IS EQUIPPED WITH A THREE-PRONG GROUNDING PLUG. FOR YOUR PROTECTION AGAINST SHOCK HAZARDS, THIS APPLIANCE SHOULD BE PLUGGED DIRECTLY INTO A PROPERLY GROUNDED THREE-PRONG RECEPTACLE. DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG.

NOTE: THIS BLOWER ASSEMBLY IS EQUIPPED WITH A TEMPERATURE-ACTIVATED FAN SWITCH THAT WILL AUTOMATICALLY CYCLE THE BLOWER ON WHEN THE HEAT EXCHANGER HAS REACHED A PREDETERMINED TEMPERATURE. ONCE THE BURNER SHUTS OFF, THIS SWITCH WILL CYCLE THE BLOWER OFF AFTER THE HEAT EXCHANGER COOLS TO THE FAN SWITCH DIFFERENTIAL SETTING. THIS BLOWER WILL NOT OPERATE UNLESS THE MAIN BURNER IS IN USE.

MODEL DVB-3 OPTIONAL BLOWER KIT (Cont’d.)
INSTALLATION INSTRUCTIONS
INSTALL ONLY ON CDV15-C / CDV25-C / CDV33 –C SERIES

PART
PART DESCRIPTION NO.
Blower Housing w/Motor 70201

Blower

  • Junction Box 43610
  • Junction Box Cover 43620
  • Fan Switch 120 Degree 70110
  • Cord Set 80202
  • Cover Shield 43078
  • Blower Shield CDV25/33-C 43625

If any of the original wires supplied with this appliance has to be replaced, it must be replaced with type 105-degree C wire or its equivalent

OPTIONAL BBSK INSTALLATION INSTRUCTIONS

  • STEP 1) LOCATE DIMPLE AT THE RIGHT REAR OF THE CABINET TOP. SEE FIGURE A.
  • STEP 2) USING DIMPLE AS A LOCATOR, DRILL A ½” HOLE.
  • STEP 3) STRAIGHTEN THE CAPILLARY TUBE. DO NOT KINK THE CAPILLARY TUBE OR SENSING BULB. SEE FIGURE B.
  • STEP 4) FROM THE TOP OF THE HEATER, INSTALL THE SENSING BULB DOWN AND UNDER THE GAS CONTROL VALVE SO THAT THE CAPILLARY TUBE IS BETWEEN THE BACK OF THE HEATER AND THE WALL. SLIDE WHITE CABLE CLAMP (PROVIDED) ONTO THE SENSING BULB AND SECURE TO THE BOTTOM OF THE GAS VALVE USING THE 10-24X3/8” SCREW PROVIDED.
  • STEP 5) SECURE THE CONTROL SWITCH (SEE FIGURE B) TO THE RIGHT SIDE OF THE INNER WRAPPER USING PREPUNCHED HOLES AND TWO #8 SCREWS PROVIDED. SEE FIGURE C. NOTE: SWITCH MUST BE INSTALLED TO BE OUTSIDE THE WRAPPER.
  • STEP 6) RUN THE TWO CONTROL WIRES FROM THE SWITCH DOWN THE RIGHT OUTSIDE OF WRAPPER. CONNECT ONE WIRE TO THE “TH” TERMINAL AND ONE TO THE “THPP” TERMINAL ON THE GAS VALVE. SEE FIGURE D. SLIDE A WHITE CABLE CLAMP (PROVIDED) OVER BOTH WIRES AND SECURE TO WRAPPER USING SCREW THAT SECURES THE FLOOR SHIELD.
  • STEP 7) IF THE HEATER IS NOT INSTALLED TO THE WALL, FOLLOW THE INSTRUCTIONS TO DO SO.
  • STEP 8) REMOVE AND DISCARD THE LIGHTING INSTRUCTIONS SUPPLIED WITH HEATER. REPLACE WITH LIGHTING INSTRUCTION SUPPLIED IN THE BBSK KIT.
  • STEP 9) PLACE THE CABINET ONTO THE HEATER, THE CONTROL ROD SHOULD EXTEND UP THROUGH THE ½” HOLE IN THE TOP OF THE CABINET.
  • STEP 10) PLACE THE CONTROL KNOB ONTO THE CONTROL ROD AND SECURE BY PUSHING DOWN.
  • STEP 11) FOLLOW THE LIGHTING INSTRUCTIONS TO PLACE THE HEATER IN OPERATION

LIGHTING INSTRUCTIONS for Optional BBSK

WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.

  • This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly.
  • BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS

  • Do not try to light any appliance.
  • Do not touch any electric switch; do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions

you cannot reach your gas supplier, call the fire department. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. Do not use this appliance if any part has been underwater. Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system and any gas control that has been underwater

LIGHTING INSTRUCTIONS

  1. STOP! Read the information on the safety label.
  2. Set the temperature control knob located on top of the cabinet to the lowest setting.
  3. Turn off all electric power to the appliance.
  4. Remove the temperature control knob by pulling it straight up.
  5. Remove cabinet.
  6. Push in gas control knob slightly and turn clockwise
  7. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information on the safety label.
  8. If you don’t smell gas, go to the next step.
  9. Open-sight glass cover.
  10. Locate red piezo ignitor button inside gas control compartment. Locate pilot behind sight glass. (Follow metal pilot tube from gas control
  11. Turn gas control knob counterclockwise to “PILOT”.
  12. Push in gas control knob and hold in. Immediately begin a series of pushing and releasing the red piezo ignitor button, while observing the pilot through the sight glass.
  13. Continue to spark until pilot is lit. Continue to hold the gas control knob in for about one (1) minute after the pilot is lit.
  14. Release the gas control knob and it will pop back up. Pilot should remain lit. If pilot goes out, repeat steps 4 thru 9.
  15. If knob does not pop up when released, STOP and immediately call your service technician or gas supplier.
  16. If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service technician or gas supplier.
  17. Close-sight glass cover.
  18. Turn gas control knob counterclockwise to “ON”.
  19. Replace cabinet.
  20. Replace the temperature control knob.
  21. Turn on all electric power to the appliance.
  22. Set the temperature control knob to the desired setting

TO TURN OFF THE GAS TO THE APPLIANCE

COZY DIRECT VENT WALL FURNACE – CDV15-C

HOW TO PROPERLY ORDER PARTS
In addition to part description and part number, please give the model number, serial number, and type of gas used. This information can be found on the rating plate located in control compartment.

COZY DIRECT VENTWALL FURNACE – CDV25-C / CDV33-C

MODEL NUMBERS L.P. CDV156C

REF. PART LIST

  • PART DESCRIPTION NO. NUMBER PRICE
  • Heat Exchanger 1 42565
  • Vent Exhaust Tube Gasket – 5-3/8″ Circle 3 70062
  • Wrapper Assembly w/Comb. Air Pan 4 43051
  • Cabinet 5 42555
  • Front Heat Shield 9 43081
  • Bottom Heat Shield 10 43075
  • Vent Cap & Spacer Plate 11 & 12 43145
  • Air Intake Tube Assy. (5-9″ Wall) 6-3/4″ Dia. 14 43200
  • Air Intake Tube Assembly (9-15″ Wall) 15 43810
  • Air Intake Tube Assembly (15-24″ Wall) 49 43705
  • Air Intake Tube Gasket – 8-1/2″ Circle 16 70061
  • Vent Exhaust Tube Assy. (5-9″ Wall) 4-3/16″ Dia. 17 43206
  • Vent Exhaust Tube Assembly (9-15″ Wall) 18 43820
  • Vent Exhaust Tube Assembly (15-24″ Wall) 52 43717
  • Wall Thimble Assembly (5 – 9″ Wall) 20 43230
  • Wall Thimble Extension (5-9″ Wall) 21 43236
  • Wall Thimble Extension (9-15″ Wall) 22 43835
  • Wall Thimble Extension (15-24″ Wall) 53 43730
  • Wall Thimble Gasket – 11×11″ 23 70066
  • Burner Access Door 25 43247
  • Heat Exchanger Door Gasket – 11-3/8×5-1/2″(Burner Gasket) 26 70060
  • Main Burner 27 70005
  • Manifold 28 70031
  • Manifold Gasket – 2×2″ 29 70065
  • Main Burner Orifice, Natural Gas 30 70040
  • Main Burner Orifice, L.P. Gas 31 70041
  • Sight Glass Assy. (Glass, Cover & Gasket included) 32 43252
  • Sight Glass Cover 33 43258
  • Sight Glass/Pilot Burner, Gasket – 3-1/2×2-3/4″ 34 70064
  • Pilot Burner Q350A2493, Natural Gas 35 70007
  • Pilot Burner Q350A2501, L.P. Gas 36 70008
  • Electrode 37 70052
  • Electrode Wire 38 70051
  • Piezo Sparker 39 80016
  • Piezo Sparker Bracket 40 43263
  • Valve, MV, Dexen 6003, Natural Gas for CDV155 41 84085
  • Valve, MV, Dexen 6003LP, L.P. Gas for CDV156 41 84086
  • Generator, Q313A1014 for CDV155 / CDV156 43 70098
  • Pilot Tubing w/fittings 44 70012
  • Thermostat 45 74592
  • Thermostat Wire N/A 74518
  • Insulated Staples N/A 74209
  • Air Pan Assembly w/Gasket for CDV15 N/A 43059
  • 90 Degree Elbow 56 70352
  • Vent Terminal Shield N/A 34950
  • Blower Housing w/Motor & Blower 46 70201
  • Junction Box 47 43610
  • Junction Box Cover 48 43620
  • Fan Switch 120 Degrees 50 70110
  • Cord Set 51 80202
  • Cover plate N/A 43078

ATTN: CONTRACTORS and SERVICE TECHNICIANS, we only sell parts through our wholesalers, b$u t t h e p r i -ceslisted above are for your convenience. For prompt parts service, contact the wholesaler from which you purchased your Cozy heater. NOTE: parts and schematic drawings on current models are shown at www.cozyheaters.com.

HOW TO PROPERLY ORDER PARTS
In addition to part description and part number, please give model number, serial number, and type of gas used. This information can be found on the rating plate located in the control compartment.

| NAT.| CDV255C| CDV335C
---|---|---|---
MODEL NUMBERS| L.P.| CDV256C| CDV336C
 | REF.| PART| LIST| PART| LIST
PART DESCRIPTION| NO.| NO.| PRICE| NO.| PRICE
Heat Exchanger Kit, INCLUDES| 1| 42770|  | 42770|
Wrapper (Ref. # 2), Right and Left Leg (Ref. # 6 & 7), AND Comb. Air Pan Assembly w/Gaskets (Ref. # 63)
Cabinet| 3| 42755|  | 42755|
Leg, Right| 6| 43495|  | 43495|
Leg, Left| 7| 43494|  | 43494|
Front Heat Shield Assembly| 9| 43481|  | 43481|
Bottom Heat Shield Assembly| 10| 43473|  | 43473|
Vent Cap with Spacer Plate| 11 & 12| 43145|  | 43145|
Air Intake Tube Assy. (5-9″ Wall) 6-3/4″Dia.| 15| 43200|  | 43200|
Air Intake Tube Assy. (9-15″ Wall)| 16| 43810|  | 43810|
Air Intake Tube Assy. (15-24″ Wall)| 58| 43705|  | N/A|
Air Intake Tube Gasket – 8-1/2″ Circle| 17| 70061|  | 70061|
Vent Exhaust Tube Assy. (5-9″ Wall) 4-3/16″ dia.| 18| 43530|  | 43538|
Vent Exhaust Tube Assy. (9-15″ Wall)| 19| 43820|  | 43828|
Vent Exhaust Tube Assy. (15-24″ Wall)| 59| 43717|  | N/A|
Vent Exhaust Tube Gasket (Requires 4) 5-3/8″ Circle| 20| 70062|  | 70062|
Wall Thimble (5-9″ Wall)| 21| 43552|  | 43552|
Wall Thimble Extension (5-9″ Wall)| 22| 43236|  | 43236|
Wall Thimble Extension (9-15″ Wall)| 23| 43835|  | 43835|
Wall Thimble Extension (15-24″ Wall)| 60| 43730|  | N/A|
Wall Thimble Gasket – 11×11″| 24| 70066|  | 70066|
Burner Access Door| 25| 43247|  | 43247|
Burner Access Door Gasket – 5-1/2×11-3/8″| 26| 70060|  | 70060|
Burner| 27| 70006|  | 70006|
Manifold| 28| 70032|  | 70032|
Manifold Gasket – 2×2″| 29| 70065|  | 70065|
Main Burner Orifice (Nat. Gas)| 30| 70048|  | 70047|
Main Burner Orifice (L.P. Gas)| 30| 70039|  | 70049|
Sight Glass Assy. (Glass, Cover & Gasket Included)| 31| 43252|  | 43252|
Sight Glass Cover| 32| 43258|  | 43258|
Sight Glass/Pilot Burner, Gasket – 3-1/2×2-3/4″| 33| 70064|  | 70064|
Pilot Burner Q350A2493 (Nat. Gas)| 34| 70007|  | 70007|
Pilot Burner Q350A2501 (L.P. Gas)| 34| 70008|  | 70008|
Electrode| 35| 70052|  | 70052|
Electrode Wire| 36| 70051|  | 70051|
Piezo Sparker| 37| 80016|  | 80016|
Piezo Sparker Bracket| 38| 43263|  | 43263|
Valve, M V, Dexen 6003, Natural Gas| 39| 84085|  | 84085|
Valve, M V, Dexen 6003LP, L.P. Gas| 39| 84086|  | 84086|
Pilot Generator, Q313A1014 Millivolt| 40| 70098|  | 70098|
Pilot Tubing w/fittings| 41| 70012|  | 70012|
Thermostat, Millivolt| 42| 74592|  | 74592|
Thermostat Wire| N/A| 74518|  | 74518|
Insulated Staples| N/A| 74209|  | 74209|
Gasket, Air Pan Top & Bottom (15-1/4×1)| 61| 70074|  | 70074|
Gasket, Air Pan Sides (25×1)| 62| 70073|  | 70073|
90 Degree Elbow| 56| 70352|  | 70352|
Vent Terminal Shield| N/A| 34950|  | 34950|
Blower Housing w/M otor & Blower| 46| 70201|  | 70201|
Junction Box| 47| 43610|  | 43610|
Junction Box Cover| 48| 43620|  | 43620|
Fan Switch 120 degree| 50| 70110|  | 70110|
Cord Set| 51| 80202|  | 80202|
Cover Plate| N/A| 43078|  | 43078|
Blower Shield| N/A| 43625|  | 43625|
Left Air Intake Baffle| N/A| 43528|  | 43528|
Right Air Intake Baffle| N/A| 43526|  | 43526|
ATTN: CONTRACTORS and SERVICE TECHNICIANS , we only sell parts through our wholesalers, but the prices listed above are for your convenience. For prompt parts service, contact the wholesaler from which you purchased your

Cozy heater. NOTE : Parts & schematic drawings on current models are shown at www.cozyheaters.com.

TROUBLESHOOTING CHART
For use by a qualified installer or service technician.

SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION
Flame too large 1.        Defective operator section of valve.

2.          Burner orifice too large.


3.       If installed above 2,000 ft.

| 1.   Replace valve.

2.    Check with local gas company for proper oriifce

– size and replace.

3.   See burner orifice section, Page 10.

Yellow burner flame| 1.    Clogged burner ports.



2.    Obstruction around vent cap.

| 1.    Remove main burner and check for obstructions in

throat, ports, and orifices. Clean – but do not enlarge ports or orifices.

2.    Make sure area around vent cap is clear, be sure

vent system is sealed.

Gas odor| 1. Gas leak.| 1. See Page 1.
Delayed Ignition| 1.    Pilot flame too small.

2.    Burner ports clogged at pilot.

3.    Low gas pressure.

4.    Pilot decreases in size when main burners come on.

| 1.    Adjust pilot flame.

2.    Clean burner ports (do not enlarge).

3.    Check gas supply pressure.

4.    Supply piping is too small. Consult local gas company or competent installer.

Failure to Ignite| 1.    Main gas off.

2.    Thermostat not set high enough to call for heat.

3.    Clogged burner orifice.

4.    Thermostat wired wrong or defective.



5.    Defective valve.

| 1.    Open all manual gas valves.

2.    Set thermostat to higher temperature.


3.    Clean burner orifice, (do not enlarge).

4.    Check wiring, jump across thermostat terminals at valve, if valve opens – re-check wires, replace thermostat.

5.    Replace valve.

Burner won’t

turn off

| 1.    Defective or damaged thermostat

wire, or thermostat.


2.     Thermostat location.

3.    Defective or sticking valve.

4.    Excessive gas pressure.

| 1.    Can be checked by removing wire from valve

terminal. If valve goes off, replace wire or thermostat.

2.    Follow instructions, check location.

3.    Clean or replace valve.

4.    Contact utility supplying gas.

Incorrect gas

input

| 1.    Gas input not checked.

2.    Clogged orifice.

| 1.    Re-check gas input.

2.    Clean orifice with a smooth wood toothpick, do not enlarge.

Not enough heat| 1.     Furnace undersized.





2.    Thermostat set too low.

3.    Incorrect supply pressure.

| 1.    This is especially true when a dwelling or room

is enlarged. Have the heat loss calculated and compare to furnace output. Your gas company can supply you with this information. If furnace is undersized, replace with correct size unit.

2.    Raise temperature setting.

3.    Check supply pressure.

Too much heat| 1.    Thermostat set too high.

2.    Combination control valve stuck open.

| 1.    Lower temperature setting.

2.    Replace combination control valve.

Pilot and main

burner go out during normal operation

| 1.          Weak powerpile or thermocouple.

2.          Input too high.

3.          Cover around pilot lighter hole not air tight.

4.          Vent tubes not properly installed or sealed.




5.          Incorrect vent tubes.

| 1.          Check millivoltage and replace if low.

2.          Check input rate.

3.          Tighten wing nuts securing cover and sight glass. Check and replace gasket if needed.

4.          Follow instructions. Check both exhaust and air intake tubes, and vent cap. Be sure all gaskets are in place and properly sealed. Use only tubes and vent cap supplied. Do not alter vent tubes or cap.

5.         Replace with correct tubes.

MAINTENANCE INSTRUCTIONS

For proper and safe operation keep the furnace and furnace area clean. At regular intervals turn the control valve to off, let cool and clean inside control compartment and under heater. To clean front panel use only a damp cloth, do not use any kind of solvent or cleaning fluid that could leave a residue or invisible coating that would burn or give off fumes when furnace is turned on. Have the furnace checked, cleaned, and repaired by a qualified service technician. Check venting system, pilot, and burner operation prior to use each year.

Follow a regular service and maintenance schedule for safe and efficient operation. Do not obstruct combustion and ventilation air. Examine the venting system as a routine part of the safety performance check on an annual basis. If the air intake tube or the exhaust tube is removed, follow Step 3 of the installation section for re-assembly. Be sure to check gaskets and replace if there is any sign of damage. If the heat exchanger is removed, check the heat exchanger intake gasket and replace if there is any sign of damage. Be sure the gasket is in place when the heat exchanger is replaced. Failure to replace any gasket that has been damaged may result in property damage, personal injury or loss of life.

WARNING
THIS IS A GAS-FIRED APPLIANCE. KEEP THE AREA CLEAR OF GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS. ALL COMBUSTIBLE MATERIAL MUST BE KEPT CLEAR OF THIS AREA TO AVOID FIRE OR EXPLOSION.

LIMITED WARRANTY

Cozy Heating Systems LLC warrants to the original user the accompanying product for the period specified herein, provided said product is installed, operated, maintained, serviced, and used according to
the instructions and specifications accompanying the product. AS OUTLINED IN OUR INSTRUCTIONS, ANY WARRANTY CONSIDERATIONS ARE CONTINGENT ON INSTALLATION BY A QUALIFIED INSTALLER (CONTRACTOR). SELF-INSTALLATION IS PROHIBITED AND WILL INVALIDATE YOUR WARRANTY.

If within a period of one year from the date of installation of the product, any part supplied by the manufacturer proves to be defective due to workmanship or material, it will replace such part, provided parts have not been subjected to misuse, alteration, neglect, or accidents. The term of the warranty for the heat exchanger and burners is covered in Table A below. Any claim not made within ten (10) days after the expiration of the warranty period shall be deemed waived by the user. The manufacturer shall have no liability or be required to perform any obligation under this warranty unless, when requested, the user returns, at the user’s expense, the component or product claimed defective, to the manufacturer for inspection, to enable the manufacturer to determine if the claimed defect is
covered by this warranty.

No charges for freight, labor or other expenses incurred in the repair, removal, or replacement of any product or component claimed to be defective, will be paid by the manufacturer to the user, and the manufacturer will not be liable for any expenses incurred, by the user, in remedying any defect in the product. Service under this warranty is the responsibility of the installer. In the event service under this warranty is needed, the user of the product shall request such service directly from the installer. If the user is unable to locate the installer, the user should write directly to the manufacturer, and the name of an alternative service source will be supplied. The product safety registration card (packed inside the appliance) must be completed and returned to the factory.

THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED (WHETHER WRITTEN OR ORAL). ANY IMPLIED WARRANTY OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR PURPOSE IS EXPRESSLY LIMITED TO THE DURATION OF THE MANUFACTURER’S EXPRESS, WRITTEN WARRANTY UNDER NO CIRCUMSTANCES SHALL

THE MANUFACTURER BE LIABLE FOR ANY SPECIAL, INDIRECT OR CONSEQUENTIAL DAMAGES OR EXPENSES ARISING DIRECTLY OR INDIRECTLY FROM ANY COMPONENT OR FROM THE USE THEREOF. THE REMEDIES SET FOURTH HEREIN SHALL BE THE EXCLUSIVE REMEDIES AVAILABLE TO THE USER AND ARE IN LIEU OF ALL OTHER REMEDIES. SOME STATES DO NOT ALLOW
LIMITATIONS ON HOW LONG AN IMPLIED THE WARRANTY LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU.

SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY TO YOU. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS, WHICH VARY, FROM STATE TO STATE

TABLE A
Warranty Period
Product Heat Exchanger/Tubes Burners

  • Cozy Gas-Fired Floor Furnace 10 Years 10 Years
  • Cozy Gas-Fired Wall Furnace 10 Years 10 Years
  • Cozy Gas-Fired Vented Console Heater 10 Years 10 Years
  • Cozy Gas-Fired Direct Vent Heater 10 Years 10 Years
  • Cozy Gas-Fired Counterflow Furnace 10 Years 10 Years
  • Cozy Gas-Fired Counterflow Direct Vent Furnace 10 Years 10 Years
  • Cozy Gas-Fired Mobile Home Direct Vent Furnace 10 Years 10 Years
  • Cozy Gas-Fired Hi-Efficient Direct Vent Wall Furnace 10 Years 10 Years
  • Cozy Gas-Fired Direct Vent Baseboard Heater 10 Years 10 Years
  • Cozy Fan-Type, Direct Vent Through-The-Wall Gas Heater 10 Years 10 Years
  • Cozy Blue Flame Vent Free Heater N/A 10 Years
  • Cozy Infra-Red Vent Free Heater N/A N/A