YORK HMCG2 ACC STD ECM High-Efficiency Horizontal Discharge Modulating Air Conditioner User Guide
- October 30, 2023
- YORK
Table of Contents
Quick Reference Guide
High-Efficiency Horizontal Discharge Modulating Air Conditioner
HMCG2 ACC STD ECM High-Efficiency Horizontal Discharge Modulating Air
Conditioner
Interfacing the indoor unit with the outdoor unit
Note: A contractor supplied filter/drier must be field-installed at the
indoor coil.
Low-voltage wiring Figure 1: Wiring diagram – HMCG2 ACC STD ECM Figure 2: Wiring Diagram – HMCG2 ACC VS ECM
CAUTION
This equipment uses an inverter drive that stores hazardous energy up to 5
min after power is removed. Wait for more than 5 min before performing
electrical work after power is removed.
Clearance
During installation, maintain the required clearance from walls and adjacent
equipment. See Figure 3. When installing multiple units, be careful to avoid
intake of discharged air from adjacent units. Figure 3: Minimum clearance
NOTICE
It is imperative to fasten this equipment to a sturdy base for protection
against vibration, strong breeze, or earthquake. Use anchors and a base
adequate to protect the unit against tipping or dislocation.
Connection and access points
Figure 4:
Connection and access points
Note: Refer to the Tabular Data Sheet provided with the unit for detailed
unit dimensions.
CAUTION
The indoor coil is under inert gas pressure. Relieve pressure from the coil by
depressing the Schrader core at the end of the suction manifold stub out.
Dry nitrogen must always be supplied through the tubing while it is being
brazed, because the temperature required is high enough to cause oxidation of
the copper unless an inert atmosphere is provided. The flow of dry nitrogen
must continue until the joint has cooled. Always use a pressure regulator and
safety valve to ensure that only low pressure dry nitrogen is introduced into
the tubing. Only a small flow is necessary to displace air and prevent
oxidation.
If a refrigerant leak is discovered after the system is charged, the system
must be evacuated to repair the leak. Attempting to braze a line under
refrigerant pressure can cause the line to rupture. A rupture can propel hot
solder and oil causing injury to the technician attempting to braze the line.
CAUTION
Avoid personal injury and/or equipment damage. Carefully follow the brazing,
charging, and other instructions in the Installation Manual provided with the
unit.
Operating limit conditions
Table 1: Minimum and maximum operating limit conditions
Air temperature | Outdoor coil °F (°C) | Indoor coil °F (°C) |
---|---|---|
DB cool | WB cool | |
Minimum | 50 (10)* | 57 (14) |
Maximum | 122 (50)* | 72 (22) |
Note: *Refer to the notice in the Reduced capacity conditions section in the Installation Manual.
Standard refrigeration piping
The maximum allowable equivalent line length for this product is 131 ft for 2
ton and 3 ton and 164 ft for 4 ton and 5 ton. The maximum allowable vertical
lineset varies depending on the vertical separation between the indoor and
outdoor section. See Table 2 for allowable lineset lengths and sizing.
Table 2: Allowable vertical refrigeration piping
Model| Maximum pipe length ft (m)| Maximum height difference ft (m)|
Additional refrigerant exceeding 25 ft (7.62 m) oz/ft (g/m)
---|---|---|---
HMCG22B241S| 131 (40)| 65.5 (20)| 0.38 (11)
HMCG22B361S| 131 (40)| 65.5 (20)| 0.38 (11)
HMCG22B481S| 164 (50)| 98 (30)| 0.38 (11)
HMCG22B601S| 164 (50)| 98 (30)| 0.38 (11)
Refrigeration piping
Keep the connecting pipe as short as possible to ensure optimum performance.
Table 3: Piping requirements
Model | Outdoor diameter of pipe – in. (mm) |
---|---|
Gas | Liquid |
HMCG22B241S | 5/8 (15.88) |
HMCG22B361S | 5/8 (15.88) |
HMCG22B481S | 7/8 (19.05) |
HMCG22B601S | 7/8 (19.05) |
Electrical connection
Figure 5:
Electrical connection for HMCG22B24 and HMCG22B36 models Figure 6: Electrical connection for HMCG22B48 and
HMCG22B60 models
Unit charging and startup
It is important to be aware of the following:
- Correct charging of the equipment is essential for correct operation.
- The unit is pre-charged with refrigerant. Add refrigerant as appropriate for the length of the lineset. Refer to the Tabular Data Sheet for more information.
- You cannot use subcool or superheat methods to charge the unit. Recover and weigh in if you have any concerns about the unit charge.
- Perform start-up and verify operation in cooling mode. Refer to the Installation Manual and the Service Data Application Guide for instructions on manual operation.
Subject to change without notice. Published in U.S.A.
Copyright © 2022 by Johnson Controls. All rights reserved.
6255355-URG-A-0722
Supersedes: Nothing
York International Corp.
5005 York Drive
Norman, OK 73069
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>