YMAE Application Guide
YMAE Air to Water Inverter Scroll Heat Pumps
YMAE Air-to-Water Inverter Scroll Heat Pumps
Introduction
The YORK YMAE air-cooled full DC inverter modular chiller and heat pump provides chilled and hot water for all air conditioning applications using an air handling or terminal unit. The unit is completely self-contained and designed for outdoor installation at roof or ground level. Each packaged unit includes hermetic scroll compressors, liquid heat exchanger, air-cooled condensers, R-454B refrigerant, and a weather-resistant microprocessor control center, all mounted in a sheet metal frame. Units are suitable for single or multiple unit installation with the possibility to connect up to 32 modules together in one control group network. Up to four modules can be provided as a factory package with single point electrical connection. The unit is available as either a two-pipe reversible heat pump or four-pipe simultaneous heating and cooling machine, with load balancing capability enabled by the air-source heat exchanger.
Control principles
Air-to-water heat pump unit modes of operation
The YMAE two-pipe heat pump has two operation modes: cooling only or heating
only. A reversing valve changes the function of the heat exchangers to provide
either heated or cooled liquid as required. A third operating mode, defrost
cycle, is enabled automatically as necessary to remove ice build-up when the
unit is in heating operation.
The YMAE four-pipe heat pump has three operation modes: cooling only, heating
only, and simultaneous heating and coolingIntelligent control logic of
operation mode can meet dynamic cooling and heating load in one building,
offering an integrated cooling and heating solution . A fourth operating mode,
defrost cycle, is enabled automatically as necessary to remove ice buildup
when the air source heat exchanger is functioning as an evaporator.
Cooling mode
Low-pressure liquid refrigerant enters the heat exchanger and ievaporated and
superheated by the heat energy absorbed from the chilled liquid. Low-pressure
vapor enters the compressor through the four-way reversing valve and
accumulator, where pressure and superheat are increased. The high-pressure
vapor is fed to the ambient coils and fans through the four-way reversing
valve, where heat is removed. The fully condensed and subcooled liquid passes
through the expansion valve where pressure is reduced and further cooling
takes place before returning to the heat exchanger.
1 | Ambient coils | 5 | Heat exchanger |
---|---|---|---|
2 | Oil separator | 6 | Four-way valve |
3 | Compressor | 7 | Receiver |
4 | Accumulator | 8 | EEV |
Note: This diagram is for reference only, it does not represent the actual PID.
Heat pump mode
Liquid refrigerant enters the ambient coil and is fully evaporated and
superheated by the energy absorbed from the ambient air.
Low-pressure, superheated refrigerant vapor passes through the four-way
reversing valve and the accumulator and enters the compressor, where pressure
and superheat are increased. Highpressure, superheated refrigerant vapor
enters the water plate heat exchanger where heat is rejected to the water. The
high- pressure liquid refrigerant, leaving the plate heat exchanger passes
through the liquid receiver and enters electronic expansion valve (EEV) where
the refrigerant pressure is reduced and subsequently
cooled before returning to the ambient coil.
Defrost mode
When ice builds up on the ambient coils, an automatic defrost cycle is
initiated with the machine in a cooling mode. Each of the refrigerant circuits
are defrosted separately. When in defrost mode, the circuit operating in heat
pump mode is in balance with the circuit operating in defrost (cooling). Heat
output is, at worst case, net zero during defrost period.
Advanced defrost logic is employed to reduce defrost cycle time and system
impact. This includes the following capabilities:
- Defrost based on the refrigerant pressure
- Subcooling circuits are designed to prevent ice build-up at the bottom of the coil
- Defrost staging logic that cycles circuits through defrost sequentially, minimizing deviation from setpoint during defrost. No more than half of the total number of circuits can defrost at the same time. In the most extreme case, the system provides net zero heating output for the defrost period
- The defrost generates water, which collects in the unit drain pan below the coils and channels out of the bottom of the unit frame through large diameter flexible tubing. The drain pan and tubing are freeze-protected by the heat generated inside the unit cabinet.Include a drain under each unit to collect condensate water and move it away from the working area surrounding the unit
1 | Ambient coils | 5 | Heat exchanger |
---|---|---|---|
2 | Oil separator | 6 | Four-way valve |
3 | Compressor | 7 | Receiver |
4 | Accumulator | 8 | EEV |
Note: This diagram is for reference only, it does not represent the actual PID.
Simultaneous heating and cooling mode, four-pipe unit
The heat pump can simultaneously provide both heating and cooling to different
zones or areas within a building. Control logic auto-balances cooling and
heating within the YMAE four-pipe chiller allowing independent and dynamic
control of both hot and chilled water temperatures. Auto-balance logic also
maximizes the utilization of cooling with heat recovery to improve energy
efficiency.
For example, the
following figure shows a system in operation, targeting 90% cooling and 60%
heating.Firstly, the unit meets the 90%
cooling demand and ecovers 90% of heat while working as simultaneous cooling
and heating.
Heating is 30% more than the demand, so it switches to the right side and
provides 50% heat, which is 10% less than the demand.
With the mode switching control, 90% cooling and 60% heat is achieved.
To avoid the unit frequently shutting off and turning on cycling and to ensure
water temperature is stable, the building system water volume needs to be
above the recommended value.
Sequence of operation
The following section describes the start-up process after unit powerup, loading and unloading, and the defrosting process:
-
After applying power supply to the system, the microprocessor performs pre-check to ensure that the daily or holiday schedule and any remote interlocks allow the unit to run, all safety cut-outs are satisfied, and no faults are unsettled. Any problems identified during the pre-check are shown on the HMI display
-
The unit can start automatically based on an internal schedule function, without user or building management system (BMS) manual input command every time. When the unit is on, the water pump will be controlled to start working instantly and the water valves will be open (if with water valve). The unit then detects the status of the flow switch to ensure sufficient liquid flow is supplied. The water pump should be controlled by leader chiller module
-
If there are no problems, the unit will be ready for loading process depending on customer load requirement. The control system adjusts the unit load depending on the liquid temperature and temperature change rate. If operating at a high load demand, the controller increases the speed of the inverter compressor or turns on more compressors. If there is a low load demand, the inverter compressor may continue to operate at low speed or may simply stop. If the latter is the case, one compressor restarts automatically when needed
-
When a compressor is running, the controller monitors the discharge/ suction pressure and various other system parameters such as liquid temperature, ambient temperature, and heat exchanger temperature. If any problems are detected, the control system takes appropriate action and displays the related fault message on the HMI display
-
The corresponding EC fan works when the compressor starts in cooling and heating mode. Fan speed is automatically adjusted based on system pressure, ambient temperature, and other key parameters
-
Each system is configured with a main EEV in the liquid line between the condenser and the evaporator. The device automatically adjusts opening steps to satisfy refrigerant flow demand, mainly based on the difference between the actual and target suction superheat
-
If demand requires, more compressors will start up either from another system in dual circuit units, or another unit in a modular control system. The sequence is as follows:
a. Load compressors to meet the frequency increase requirement
b. Load compressors in the standby modules. The priority is to run compressors with fewer running hours
c. Load any other compressors, also those with fewer running hours -
Modular array packages can be regarded as a single unit with multiple circuits. The customer can set a unique address for each single module through a dip switch on the control board located in the electrical panel.
One module is set as the Leader, and all circuits are managed by a centralized controller. When loading or unloading, each circuit is independent but given equal priority if it has similar running speed and running hours. For example, when two circuits need to be loaded, they can be two circuits in the same module or two circuits in two different modules. The centralized controller monitors and records the accumulative running duration of each circuit compressor in real time. When loading, the compressor with a shorter accumulative running time has higher priority. When unloading, the compressor with longer accumulative running hours is in higher priority to unload.
Between one and three compressors can be loaded at any one time, which is based on the total number of modules in one control network and the loading requirement -
As the load decreases below the setpoint, the compressors shut down in sequence. This normally occurs at intervals of between approximately 20 seconds and 40 seconds based on water temperature as compared to the setpoint and the rate of temperature change
-
When the compressor in a system is unloading to shut off, the system switches off its fan and then the EEV shortly afterwards
-
The compressor heaters energize at a specific ambient temperature to prevent liquid refrigerant condensing and accumulating in the compressor housing and to prevent the liquid flooding and oil lubrication risk
-
YMAE simultaneous cooling and heating loading and unloading priority
• If both cooling and heating require loading, priority is to load systems running in cooling and heating operation. After heating load meetsrequirement, continue loading systems running in cooling operatio -
If both cooling and heating require unloading, priority is to unload systems running in cooling and heating operation. If the heating load meets the requirement, continue unloading systems runningin cooling operation
-
When multiple modules are packagedtogether, the capacity of each circuit i1/2n of the total capacity, where n is the number of modules. When the unit is running, the following processecan occur:
• If only cooling or heating is requiredthe unit loads step by step and operates in cooling only or heating only mode until it meets therequired capacity
• If cooling and heating are both required simultaneously, the unit starts up with the cooling and heat recovery mode. The unit loads the circuits step by step until it meets the required capacity for cooling or heating, whichever is lower. Then, for the remaining cooling or heating capacity, the unit continues to load other circuits and operate in cooling only or heating only mode until the remaining capacity is met
• If the cooling and heating recovery mode has been loaded into the last circuit, this last circuit switches between the cooling and heat recovery mode and cooling only or heating only mode -
To mitigate adverse effects on system performance due to air-source heat exchanger frosting, the unit intermittently activates defrost mode when the following conditions are met:
• If the coil temperature is less than or equal to the target temperature for 3 min and the cumulative heating duration is greater than or equal to 40 min. The default target ambient temperature is 19.4°F (-7°C)
• If the saturated suction temperature is less than or equal to the target temperature for 3 min and the cumulative heating duration is greater than or equal to 40 min. The default target ambient temperature is 21.2°F (-6°C)
• The system cumulative heating duration is greater than or equal to 180 min when ambient temperature is below 14°F (-10°C) 15. In defrost mode, a unit runs a reversed refrigeration cycle and air-to-water heat pump heating capacity is diminished as a result -
When ice builds up on the ambient coils, operate the unit in defrosting mode to remove defrost. The number of defrosting circuits must not exceed half of the total number of circuits. When in defrost mode, the circuit operating in heat pump mode is in balance with the circuit operating in defrost. Heat energy is not removed from the hot water system because the controller minimizes the quantity of circuits that can defrost at any one time. Less than half of total circuits can enter defrost at any time, which
reduces heating capacity loss and helps minimize the temperature impact on the system
Leak detection control scheme
The leak detection sensor and ventilation fans are installed inside the
enclosure to avoid any refrigerant accumulations in case leakage occurs. The
sensor is located near the compressor mounting base where the piping is most
densely arranged.
The ventilation fans run for 60 seconds when the unit is powered on for the
first time, and periodically for 30 seconds every 24 hours. When the
refrigerant concentration reaches 25% of low flammable limit (LFL) the fans
start to extract the gas mixture from the enclosure and the unit shuts down,
with the exception of the ventilation fans if the concentration reaches 50% of
LFL.
The leakage sensor is a non-dispersive infrared (NDIR) sensor. The sensor is
calibration-free and designed for a lifespan of 15 years.
System and unit sizing
Correct system design considers the range of potential operating conditions,
system and heat pump equipment sizing, and any requirements for redundancy.
Commonly used high-temperature, hot-water conditions do not only result in
high system energy consumption but are not even attainable with commonly
available heat pump technologies. The common high-temperature heating
assumptions of the past must be abandoned and low-temperature supply heating
concepts embraced. Historic “rules-of-thumb” for system capacity sizing must
be reconsidered.
Computerized load analysis for new buildings and accurate load history for
existing buildings is essential for designing the correct system and meeting
owners’ environmental and financial goals. This section discusses many of the
important aspects of system design relative to an air-cooled heat pump modular
unit in a system.
Size guidelines – minimum module quantity
The minimum unit design principles for air-cooled heat pumps can be considered
based on the following aspects:
Load requirements: Evaluate the heating and cooling load demands of the
building or space. Consider factors such as building size, usage, occupancy
and equipment heat load to determine peak and average load requirements. In
general, sizing for either greater
heating or greater cooling demand is recommended, but building operation and
usage may determine the most appropriate system design.
The design temperature of heating water should also be carefully considered.
Higher temperatures will reduce heat pump efficiency but offer savings on
terminal unit sizing and are often necessary for retrofits. Lower water
temperatures are recommended, especially for new construction.
Single-unit capacity: Based on the load requirements and heat pump performance
data, determine the minimum capacity of a single heat pump. Ensure that a
single unit can meet the minimum load demand to provide sufficient heating and
cooling capacity even at low loads.
Defrost derating: Defrost operation results in a weighted performance derate
to the equipment heating capacity. The published rating report includes a
derated capacity considering average defrost, in accordance with EN14511:2013.
Consideration of site conditions by the design engineer is recommended, in
order to consider additional derate in case of unusually high humidity. Low
outdoor air temperatures cause the outdoor coil temperature to drop below
freezing potentially resulting in frost accumulation.
Defrost typically only occurs below 47°F (8.3°C) OAT. Air-to-water heat pump
units automatically enter defrost operation when required. The YMAE unit
control has intelligent defrost control to minimize defrost while maximizing
unit heating efficiency and capacity. The controls algorithm minimizes the
quantity of circuits allowed to defrost. Less than half of total circuits
enter defrost at any one time, which reduces heating capacity loss and helps
minimize the temperature impact on the system.
Turndown rate: Turndown rate refers to the ability of a heating or cooling
system to reduce its output capacity or energy consumption below its maximum
rating. It indicates the range over which the system can be adjusted or
modulated to meet varying load demands.
The turndown rate is an important consideration in HVAC system design and
selection for several reasons:
- Energy efficiency: A low turndown rate allows the system to operate at lower capacities when the demand is low, which improves energy efficiency. By matching the system output closely to the actual load requirements, energy wastage is minimized, resulting in energy savings and reduced operating costs
- Comfort control: Systems with a low turndown rate can provide precise temperature control and maintain optimal comfort levels. They can respond quickly to changes in load demands and adjust their output accordingly, preventing temperature fluctuations and ensuring consistent comfort conditions
- Load flexibility: In applications where the load varies significantly, such as commercial buildings with fluctuating occupancy or variable process loads, a low turndown rate allows the system to adapt to these changes effectively. It ensures that the system can handle both high and low load conditions without compromising performance or efficiency
- System longevity: Systems with a low turndown rate tend to have a longer lifespan. Operating at lower capacities for extended periods reduces wear and tear on system components, resulting in reduced maintenance requirements and extended equipment life
Table 1: YMAE turndown rateModel| YMAE0035| YMAE0070| YMAE0105| YMAE0140
---|---|---|---|---
Turndown rate| 19%| 9.50%| 6.30%| 4.70% - Control strategy: Consider the control strategy of the heat pump system. Determine whether the minimum unit design requires a leader-follower configuration, or a central control system based on operational needs, to achieve effective controand modulation
- Allowance for future expansion: Consider future expansion and changes. It is advisable to reserve space in the minimum unit design to easily accommodate additional heat pump units when needed
It is important to balance cost-effectiveness, energy efficiency and system
reliability in the minimum unit design. Consulting professional HVAC engineers
or heat pump suppliers is advisable to receive customized recommendations
based on specific project
requirements and environmental conditions.
Water temperature difference, Delta T
When sizing an HVAC system, it’s important to consider not only the target
Delta T but also the temperature of the heating or cooling medium as it enters
and leaves the system. If the temperature of the medium is too high or too
low, it can cause damage to the system.
For example, if the temperature of the cooling medium entering an air-to-air
heat pump is too high, it can cause the compressor to overheat and fail.
Conversely, if the temperature of the cooling medium entering a water-to-air
heat pump is too low, it can cause the system to freeze and stop working.
Liquid temperature that is too high or too low is adverse for system stability
and may cause reliability risks.
The YMAE liquid leaving temperature range is between 41°F and 68°F (5°C and
20°C) with water, -4°F and 68°F (-20°C and 20°C) with glycol in cooling, and
77°F and 140°F (25°C and 60°C) in heating. YMAE units monitor the cooling
liquid temperature and heating liquid temperature status and have a protection
trip in case any abnormalities are detected.
To avoid these problems, it’s important to select an HVAC system that is
correctly sized for the application and has a suitable Delta T range. With
proper planning and selection, the system can provide many years of reliable
operation.
Careful evaluation of the design Delta T and quantity of modules must be
considered to ensure stable unit and system operation.
If a large delta T is required, then a low flow rate switch in the system
yields better stability.
Design delta T guidance
At maximum design flow for the heat exchanger, the delta T is about 5°F
(2.78°C). At minimum design flow, the delta T is about 20°F (11.1°C). The
standard flow switch is a mechanical paddle type switch that is switched on or
off in response to the flow or non-flow of a fluid.
The paddle is displaced due to the force of fluid moving past it. In two-pipe
units, there is one flow switch for each module, and the flow switch and
entering strainer are factory-mounted inside the unit base enclosure. In four-
pipe units there is one flow switch for each water loop, making a total of two
for each module. The flow switch and strainer are shipped loose for field
installation with a short section of water pipe that includes a threaded
fitting and Victaulic-type water connections, including Victaulic clamp for
the unit brazed plate heat exchanger (BPHX) to piping section. On both two-
pipe and four-pipe units, the standard flow switch is suitable for flow above
51 gpm (193 Lpm).
The optional reduced flow switch is a mechanical paddle switch that operates
and installs the same as the standard switch but is suitable for flow above 37
gpm (140 Lpm)
Table 2: Minimum and maximum flow rate for correct operation
Unit Models | Water Flow Range USgpm (Lpm) | Comments |
---|---|---|
Cooling-Water Side | Heating-Water Side | |
Min. | Max. | Min. |
Four-Pipe
| YMAE0035PJS| 37 (140)| 126 (477)| 37 (140)| 164 (621)| Two water loops
YMAE0070PJS| 74 (280)| 252 (954)| 74 (280)| 327 (1,238)
YMAE0105PJS| 111 (420)| 378 (1,431)| 111 (420)| 492 (1,862)
YMAE0140PJS| 148 (560)| 503 (1,904)| 148 (560)| 656 (2,483)
Two-Pipe| YMAE0035PJP| 37 (140)| 126 (477)| –| –| One water loop
YMAE0070PJP| 74 (280)| 252 (954)| –| –
YMAE0105PJP| 111 (420)| 378 (1,431)| –| –
YMAE0140PJP| 148 (560)| 503 (1,904)| –| –
Two-pipe and four-pipe selection
Suitability for application
A two-pipe HVAC system uses the same piping for both heating and cooling.
The two-pipe system is less expensive to install and maintain. However, it may
not be convenient if the application requires frequent changes between heating
and cooling modes, or where there are multiple areas with different operating
requirements.
A four-pipe HVAC system uses separate pipework for hot- and cold-water loops.
These are suitable for applications with four-pipe terminals, or with separate
heating and cooling terminals. The system allows multiple areas to be served
independently with either cooling or heating as required. A four-pipe system
may be more expensive to install because it has more components but offers
much greater flexibility and can provide much higher overall building energy
performance, which can result in significant operating cost savings. It can
also heat the space and dehumidify the air at the same time.
Two-pipe and four-pipe combination system
It is possible to combine a YMAE four-pipe heat pump with a standard modular
YMAE two-pipe in one system. This flexible combination offers better solutions
for various cooling and heating loads. A maximum of 32 YMAE modules, either
two-pipe, four-pipe, or a combination, can be connected electronically to
operate as a single unit through the modular control capability included as
standard on every unit.
This offers significant flexibility to the system designer.
Up to four modules are available as a factory-packaged modular array, with all
units in the array either two-pipe or four-pipe units. The array includes
single-point power connection (SPC) as standard with a 65 kA SCWR circuit
breaker mounted within the unit frame. It is possible to connect up to two
arrays, or eight modules, with an optional singlepoint terminal block
enclosure, which is field-mounted adjacent to the heat pumps on a separate
base, and field wired to each array single point connection circuit breaker.
When selecting either a two-pipe or four-pipe heat pump, prioritize the peak
heating demand. Use thisto determine the capacity required, and as result,
the quantity of modules. On four-pipe units, the unit control logic auto-
balances cooling and heating loads within the unit frame, allowing independent
and dynamic control of both hot and chilled water temperatures to meet
customers’ requirements. Excess heat is rejected, or required heat is
captured, as necessary using the air-side heat exchanger coils. In an
application with much higher peak heating than cooling demand, it is possible
to use a combination of both two-pipe and four-pipe heat pumps, reducing cost
and complexity of the installed unit and piping header.
The following is an example of a combined two-pipe and four-pipe application:
Peak heating load is 6400MBH at -5°F (-20.5°C), which requires approximately
30 modules to meet the heating load.
Peak cooling load is 325T at 90°F (-32.2°C), which requires approximately 10
modules.
Peak simultaneous load is 2,500 MBH, which requires approximately eight
fourpipe modules.
For this application, lay out 10 four-pipe modules and 20 two-pipe modules,
then connect the piping header to the heating side of the four-pipe modules
and to the two-pipe modules, so that the cooling side only goes to the chilled
water loop.
In peak summer, the 10 four-pipe modules would run as chillers because there
is no heating load. In the shoulder months, the four-pipe modules would
operate in simultaneous mode, potentially having excess capacity. In winter,
there is no cooling load so the four-pipe modules operate to heat only in
conjunction with two-pipe modules.
Layout guideline
To achieve optimum performance and trouble-free service, it is essential that
the proposed installation site meets the location and space requirements for
the model being installed.
The clearances recommended are nominal for the safe and efficient operation
and maintenance of the unit and power and control panels. Local health and
safety regulations, or practical considerations for service replacement of
large components, may require larger clearances than those given in this
manual.
Outdoor installations
The user can install the units at ground level on a suitable, level foundation
easily capable of supporting the weight of the unit, or on a suitable rooftop
location. In both cases an adequate supply of air is required. Avoid locations
where the sound output and air discharge from the unit could cause
disturbances. The location must be away from boiler flues and other sources of
airborne chemicals that could attack the condenser coils and steel parts of
the unit.
For ground level locations, install the unit on a suitable flat and level
concrete base that extends to fully support the two side channels of the unit
base frame. A one-piece concrete slab, with footings extending below the frost
line is recommended. To avoid noise and vibration transmission, do not secure
the unit to the building foundation. It is advisable to use optional neoprene
isolators, at the very least.
On rooftop locations, choose a place with adequate structural strength to
safely support the entire operating weight of the unit and service personnel.
The user can mount the unit on a concrete slab, similar to ground floor
locations, or on steel channels of suitable strength.
Space the channels with the same centers as the unit side and front base
rails. This allows the user to install vibration isolators if required.
Isolators are recommended for rooftop locations.
Ensure that the place of installation and operation can support the weight of
the unit and any extra operation and maintenance weights that may occur.
Location clearances
Adequate clearances around the units are required for the unrestricted airflow
for the air-cooled condenser coils and to prevent re-circulation of warm
discharge air back onto the coils. If clearances given are not maintained,
airflow restriction or recirculation causes a loss of unit performance, an
increase in power consumption and may cause the unit to malfunction. Consider
the possibility of down drafts, caused by adjacent buildings, which may cause
re-circulation or uneven unit airflow and other potential obstructions, such
as snow in low temperatures. The installing contractor must include
ventilation and drainage in the plumbing.
Recommended minimum clearances:
- Control panel to wall: 36 in.
- If panels face each other, space between panels: 48 in.
- HMI side to wall: 25.6 in.
- Duct side to wall: 20 in.
- Between adjacent devices: 25.6 in.
- Top: no obstructions allowed
- Adjacent walls must not exceed the height of one unit
The water system
Water system configurations
System structure
- Primary pumping system: The chiller and the fan coil unit share a set of circulating water pumps
- Secondary pumping system: The chiller and the fan coil unit are equipped with separate circulating water pumps Flow variation of fan coil units
- Constant flow system: The circulating water flow on the fan coil side is maintained at a constant value. If the end of the water system has a manual water valve, an electric three-way regulating valve, or three-way solenoid valve, it is a constant flow water ystem
- Variable flow system: The circulating water quantity at the fan coil side changes with the change in cooling capacity. If the end of the water system has an electric two-way valve, an electromagnetic two-pass valve, or a dynamic balanced electric regulator valve, it is a variable flow water system
Water system layout
When a centralized controller manages multiple modules, these modules create
one system. Each HMI controller can control up to 32 modules. The layout of
the water system ensures all modules in the system have flow requirements met,
regardless of the capacity of the unit. If there is insufficient water flow,
various unit protections are triggered, which can affect normal operation of
the system
Note: To ensure the correct water flow in the system, the water pump
needs to be considered:
- Each modular array has a passive output signal, contact capacity 1 A/ 250 V, on only the first module, which controls the water pump. At startup, the water pump starts first, and the modular array will perform the startup process 20 seconds later. When the chiller shuts down, the modular array shuts down first, and the pump stops about 90 seconds later
- The water pump must be interlocked with the chiller
Primary pump, constant flow system
The primary pump, constant flow system is a widely used air conditioning
system. There are two circuit arrangements for this system: series or
parallel.
Series arrangement:
- At startup, all the water pumps start, not including the standby pump; otherwise, it leads to insufficient water flow in the unit
- All pumps can only stop when all the modules are shut down.
- Check valves are installed at each pump outlet
- Simple pipework
Parallel arrangement:
- A water pump is installed in the piping of each module, and a check valve is installed at each pump outlet
- When a unit starts, the water pump on the same circuit is opened. If the unit is turnedoff, the water pump on the same circuit is turned off. Pumps on parallel circuits do not interact or interfere with adjacent circuit operation
Primary pump, variable flow system
Series and parallel arrangements are both also applicable in the primary pump,
variable flow system. Variable flow systems offer energy savings by reducing
the pump speed and water volume at partial load
Series arrangement:
- At startup all water pumps start, not including the standby pump; otherwise, it leads to insufficient water flow in the module
- All pumps can only stop when all modules are shut down
- Check valves are installed at each pump outlet
Parallel arrangement:
- A water pump is installed in the piping of each module, and a check valve is installed at each pump outlet
- When a unit starts, the water pump on thesame circuit is opened. If the unit is turnedoff, the water pump on the same circuit is turned off. Pumps on parallel circuits do not interact or interfere with adjacent circuit operation
- This arrangement can achieve energy-saving operation due to partial load operation
Regardless of the arrangement, with variable flow systems the outlet side flow
changes with unit loading and unloading.
To ensure that the water flow across the heat pump is unchanged, the pumping
system must also perform a dynamic hydraulic balance.
Constant flow/variable flow, secondary pump system
In constant or variable flow systems with a secondary pump, the end secondary
pump side is constant or variable flow, while the primary pump side is always
circulating at constant flow.
This kind of system is not widely used. When implemented, use a parallel
arrangement for the main equipment room under partial load operation. Some
pumps can be manually shut down along with the module to achieve energy saving
operation.
The building load side of the secondary water system cannot adopt variable
frequency pump.
Benefits of a VPF system compared to a constant primary-secondary system
- Low installation cost: Both systems have similar arrangements, but secondary pumps are substituted in a VPF system for higher capacity VFD pumps, which are only used in a primary circuit to regulate flow in the entire system. Other accessories like the flow meter, bypass control valve, DP sensor, and chiller isolation valve are an additional cost in VPF system but roughly 5% of the overall cost can be saved in initial investment
- High energy saving: VPF systems save energy compared with constant flow pumping systems during part load operation because water flow is reduced and less pump energy is required. Also, less pumping power is required as the overall system head loss is reduced. Around 15% net saving in pumping power is possible with VPF systems. In addition, with reduced water flow during part load operation, less compressor energy is required. So, an overall operating cost saving of between 20% and 30% is possible
- Reduced plant room footprint: Because the VPF system does not have a secondary pumping system, this saves on installation space
- Better response to low Delta T syndrome: If a system has Low Delta T Syndrome, the system pumps more water than is required, which wastes energy. This can occur because of several different potential chilled water or airside issues. To compensate for this, additional pumps have to be turned on in a constant primary flow system while the same can be achieved by speeding up the already-running pump for a VPF system
Designing a VPF bypass
- Size for minimum flow through one module
- Bypass valve must be the normally open type
- Valve head ratings must be higher than pump dead head
- Linear characteristic: valve position % equals flow %
- Fast actuator
- Valve control range: 100:1
- The flow meter controls the bypass to maintain modular minimum flow
- In accordance with the manufacturer’s instructions
Challenges
- Avoid using VPF systems where chilled water temperature is critical, such as a clean room or process applications
- Cannot use in systems where only three-way valves are used
- Do not use VPF if it is unlikely that the operator will run the plant as designed
- The system must be able maintain a minimum flow rate through the chiller, have quick unloading cooling capacity, and have condenser head pressure control
- Requires a more robust, complex and calibrated control system
- Requires coordinated controls of chillers, isolation valves and pumps in sequencing
Pipework connection
The following piping recommendations are intended to ensure satisfactory operation of the unit. Failure to follow these recommendations could cause damage to the unit, or loss of performance, and may invalidate the warranty:
- A flow switch is included as standard on each module. It is factory-wired and installed in the extension pipe between the heat exchanger outlet and the edge of the heat pump (two-pipe) or field-wired and installed in the included, externally mounted pipe at the outlet of the heat exchanger (four-pipe)
- For modular combinations, an additional flow switch must be installed in the main outlet pipe of the modular array system. The switch must be wired to the terminals on XTB2 of the Leader unit located in the power panel. See Figure 14
- Pipework and fittings must be externally supported to prevent any loading on the heat exchangers. Flexible connections are recommended, which also minimizes transmission of vibrations to the building. Flexible connections must be used if the unit is mounted on anti-vibration mounts because some movement of the unit is expected in normal operation
- Pipework and fittings immediately next to the heat exchangers must include provision for removal to enable cleaning before operation, and to facilitate visual inspection of the exchanger nozzles
- Each heat exchanger must be protected by a strainer, preferably of 20 mesh, fitted as close as possible to the liquid inlet connection, and provided with a means of local isolation to enable regular strainer cleaning. A 20-mesh wye-strainer is provided as tandard to provide additional protection at the heat exchanger inlet
- The heat exchangers must not be exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass and valve arrangement be installed to allow flushing of the pipework system. The bypass can be used during maintenance to isolate the heat exchangers without disrupting flow to other units
- It is recommended to provide thermometer and pressure gauge connections on the inlet and outlet connections of each module piping connection
- Provide drain and air vent connections at all low and high points in the pipework to permit drainage of the system and to vent any air in the pipes
- Protect liquid systems at risk of freezing due to low ambient temperatures by using insulation and heater tape or a suitable glycol solution. The liquid pumps must also be managed to circulate liquid when the ambient temperature approaches freezing point. YMAE standard control logic includes an optimized, temperature-dependent pump control sequence. A pump controlled by external system is also acceptable
- On two-pipe units, factory-installed insulation and heater tape is provided for all pipework and heat exchangers inside the unit frame. On four-pipe units, the external, field-mounted pipe connection (with flow switch) and inlet strainer must be insulated, by others
- When multiple modules are combined, the connected water pipes must be designed to provide balanced water flow to each module. This can be achieved with a properly sized, reverse return type as detailed in the following figure
- Shut-off valves, thermometer and pressure gauges should be installed on the inlet and outlet pipes of individual modules to regulate the water flow and to shut off the water flow during maintenance
When multiple modules are combined, it is recommended that each module inlet
be provided with an isolation valve, to stop water flow through the module
when it cycles off. The YMAE standard control logic can control this valve.
Different valves have different times from closing to fully opening and can be
set by the HMI according to the selected valve opening time: 0-120 seconds.
The valve receives on-off signals. The valve must be provided by others.
- Selecting unit isolation valves: variable flow system
- A butterfly-type valve is recommended to provide the largest flow as quickly as possible when opening
- Valve pressure rating must be greater than pump dead head
- Linear characteristic: valve position % equals flow %
- The unit can be provided with an optional water pump, which is controlled by the unit automatically. If the unit is not equipped with a factory water pump, the unit provides a signal by dry contact for water pump control: dry contact capacity 1 A at 250 VAC. The water pump must be linked to the control signal on the Leader module to use this feature. It is recommended that a backup pump is installed on site to prevent the failure of the commonly used pump from affecting the operation of the unit. When the factory dual pump kit option is equipped, run hours will be equalized between the primary and standby pump. When external dual pumps are used, only a run signal is provided and run hour equalization should be controlled internally by the pump
- Water pump outlet must include a check valve. If two or more pumps are connected in parallel in a water circuit, the outlet of each pump needs to be equipped with a check valve. The purpose of installing check valves is to prevent water bypassing from unused pumps or faulty pumps
- It is recommended to install a water filter of no less than 30 mesh per inch on the inlet pipe of the external water pump to ensure reliable operation of the water pump
- Drain connections should be provided at all low points in the piping system to permit complete drainage of the cooler and system water piping during low ambient temperature periods when system operation is not required for an extended duration, or for service
Field Wiring and check before starting up
YWSV2| MODULE HOT WATER VALVE| SFM2| MODULE H-WATER SF| FU| FUSE| BLST2|
EAVING SYS. H-WATER TN)
---|---|---|---|---|---|---|---
YWSV1| MODULE COLD WATER VALVE| SFM1| MODULE (-WATER SF| FLP1| HEATING LOW
PRESS SWITCH| 81ST1| EAVING SYS (-WATER TEMP
YOSV| OIL RETURN SOL VALVE| SEI| EXTERNAL INTERLOCK SWITCH| FLP1| COOLING LOW
PRESS SWITCH| BLMT1| EAVING MODULE H-WATER TEMP
YMSV| MODE SOL VALVE| SUM| COOLING t HEATING MODE SWITCH| FHP| HIGH PRESS
SWITCH| BLMT1| EAVING MODULE (-WATER If*
YMEV| MAIN EEV| SOH| COOLING/KAM MODE SWITCH| EXT| EXTERNAL PART| BPHE| RAZED
PLATE HEAT EXCHANGER
YLISV| LIQUID INJECT SOL VALVE| SGEO| BACNET GATEWAY BO| EPH24| OUT-PIPE
HEATER OF H-WATER HYDRO KIT| BEMT2| NTER MODULE H-WATER TEMP
YEW| EVI SOL VALVE| QCB| CIRCUIT BREAKER| EPH14| OUT-PIPE HEATER OF C-WATER
HYDRO KIT| BEMT1| NTER MODULE (-WATER TEMP
YEEV| EVI EEV| MRF| REFRIGERANT FAN| EPH23| 11-PIPE HEATER OF H-WATER HYDRO
KIT| BECOT| CO OUTLET TEMP
YDSV| DEROST SOL VALVE| MP2| H-WATER PUMP| EPH13| il-PIPE HEATER OF C-WATER
HYDRO KIT| BECIT| CO INLET TEMP
Y(SV| COIL BRANCH SOL VALVE| MP1| C-WATER PUMP| EPH21/22| II/OUT-PPE HEATER OF
H-WATER PHE| DT| ISCHARGE TEMP
YAW| AC BPHE SOL VALVE| MF| EC FAN| EPH11/12| II/OUT-PPE HEATER OF [-WATER
PHE| BAMB| At43IENT TEMP
XT| TERMINAL BLOCK| MDF| DRIVER COOLING FAN| EEH2| HOT WATER PHE HEATER|
BACOT| R COL DEFROST TEMP
SRS| REMOTE START SWITCH| MC| COMPR MOTOR| EEH1| (OLD WATER PHE HEATER| BAIT|
UUMULATOR INLET TEIf
SSG?| SMART GRID READY 2| LR| REACTOR| ECH| (RANK CASE HEATER| AF| LTER/FLTER
BOARD
SSG1| SMART GRID READY 1| KRS| RUNNING STATUS RELAY| BSP| SUCTION PRESS
TRANSDUCER| APB| FLAY BOARD
–| –| KPH| PUMP KIT HEATER RELAY| BRLD| REFRIGERANT LEAK DETECTOR| ADB| RIVER
BOARD
| –| KAL| ALARM OUTPUT RELAY| BDP| DISCHARGE PRESS TRANSDUCER| AMB| N CONTROL
BOARD
ABBR| DESCRIPTION| ABBR| DESCRIPTION| ABBR| DESCRIPTION| ABBR| ESCRIPTION
-
Unit power should be on to provide the freeze protection function unless the liquid systems have been drained. When liquid systems have been drained, unit power should be left switched off to avoid damage by auto starting freeze protection when liquid is not present
-
Install an auto-feed valve for closed-type water systems, without an open expansion tank, to prevent unit damage from operation without sufficient water volume in the system. Set the outlet water pressure of the auto-supply valve 4.35 psi (0.3 bar) higher than the static pressure of the system. Ensure the value set is lower than the supplementing water pressure, that is the source of the water supplementing, or it would not conduct normal water supplement. The auto-feed valve is usually installed at the return water line of the system. Heat isolation measures must be implemented on the water supplement pipeline and water supply valve to protect against freezing in low temperatures
-
Install a buffer tank in the water system to prevent frequent start-ups of the unit. For buffer tank selection, see loop volume recommendations
-
The terminal device in the water system must be equipped by the customer with a three-way valve or a bypass valve to make the water system circulate fluently during the period when the anti-freezing water pump is operating in low temperatures
-
When the unit is a modular array, the total inlet and outlet pipes of the water system must each have a location to install a temperature sensor for the inlet and outlet water temperature sensors of the system. If the water system requires the installation of auxiliary electric heating, the water system’s total outlet water temperature sensor must be installed after the auxiliary electric heating
-
The flow range of the unit must be controlled between 70% to 130% of the rated flow.
Standard pipework connections are Victaulic connections. The inlet and outlet cooler connection sizes are 2-1/2 in. Use the left side piping for the cold- water connection and the right side (four-pipe model) for the hot-water connection -
The inlet minimal pressure of the water pump reaches 20 kPa to avoid cavitation noise and damage to the water pump
Note:
- If using a constant flow system, do not use isolation valves to isolate units that are not running. Keep flow through all units
- System LWT sensor on head supply pipe for LWT control
- Circulation pump and back up pump on the return pipe
- Strainer on the inlet of pump to avoid impurities
- Delta P bypass valve to keep water flowing when all indoor FCUs are closed
- Expansion tank to ensure there is enough water capacity in the water system
- Drain valve for draining water for maintenance or inactivity The following figure is the water connection diagram on one side. The water connections for the cold and hot water systems of the air conditioner must adhere to the following diagram:
Note:
- Additional electrical control valve for each follower module
- Do not set the electrical control valve on the leader module
- Cold side piping is shown; the hot side is identical
Variable flow with hydraulic kit option
- The VSD pump provided with the hydraulic kit auto-adjusts the pump output speed according to the pressure difference between the pump inlet and outlet
- The Delta P meter detects the building-side resistance
- A proportional valve controls the user side resistance to a preset target based on the Delta P meter detection
- The VSD pump has a constant Delta P control
- Other VSD pump control based on specific water system No electrical control valve design. Contact your local Johnson Controls sales office to consult on alternate configurations
| Strainer| | Pressure gauge| | Exhaust valve| | Flow switch| | Proportional
valve
---|---|---|---|---|---|---|---|---|---
| Water pump| | Stop valve| | Check valve| | Flexible pipe| | P meter
| Thermometer| | Relief valve| | | | | |
Variable flow without hydraulic kit option
Figure 20 shows the recommended and alternate control points for pump control
on systems without a factory hydraulic kit option.
- The Delta P meter detects the user side resistance
- A proportional valve controls the user side resistance to a preset target based on the Delta P meter detection
- The Delta P meter and proportional valve are located near the first terminal device, near the fan coil, or the outlet of the mechanical/pumping space
- The VSD pump has a constant Delta P control
- The VSD pump is controlled to constant pressure differential at Delta P2, which is recommended. Delta P2 is located between the water supply/return pipe near the exit of the mechanicalsystem, close to the first terminal device on building load side
| Strainer| | Pressure gauge| | Exhaust valve| | Flow switch| | Proportional
valve
---|---|---|---|---|---|---|---|---|---
| Water pump| | Stop valve| | Check valve| | Flexible pipe| | P meter
| Thermometer| | Relief valve| | | | | |
Alternate pump control methods
There are alternate control points possible for a variable primary system. See
Figure 19 in the previous section.
- Delta P1, between the modular array supply/return pipe. This is recommended on less stable water systems with low volume or rapid load changes and may result in short cycling of the heat pump
- Delta P3 is the most unfavorable circuit for customer terminal loop because it has the biggest pressure drop in the piping system. This is not recommended due to its slow response
- Other VSD pump control based on specific water system design
Piping
Closed-loop systems can be further classified as direct return or reverse
return.
Direct return
The direct return system allows piping to be run in the most direct path to
optimize piping costs. The length of the water circuit through the supply and
return piping to each unit is different in direct return piping. Units close
to the pump receive a greater flow rate than those further away unless
balancing is accomplished. ![YORK YMAE Air to Water Inverter Scroll Heat Pumps
-
Direct return](https://manuals.plus/wp-content/uploads/2024/04/YORK-YMAE- Air-to-Water-Inverter-Scroll-Heat-Pumps-Direct-return.jpg)
- Water enters Unit 1 from supply
- Water leaves Unit 1 and returns directly to source
- The first unit supplied is the first returned
- Unequal circuit pressure drops result
- Circuit pressure drop through
- Unit 1 < Unit 2 < Unit 3 < Unit 4 < Unit 5
- Balancing valves are a necessity
Reverse return
The reverse return system is piped so that the length of the water circuit
through the supply and return piping to each fan coil or air handler is
essentially the same. As a result, pressure drops are basically equal.
Figure 22: Reverse return
- Water leaves Unit-1 and goes all the way around in returning to source
- The first unit supplied is the last returned
- Circuit pressure drop through
- Unit 1 = Unit 2 = Unit 3 = Unit 4 = Unit 5
Balancing valves may be eliminated Reverse return has greater pipe lengths and
cost. However, the cost of adding a balancing valve for each unit using a
direct return system could offset the additional costs of the added reverse
return piping.
Note: Reverse return piping layout is strongly recommended to ensure
equal flow across all units, preventing nuisance trips and reducing risk of
freeze damage.
Loop volume recommendations
Buffer water tank
A buffer tank is not mandatory in the water system but it can help improve the
system operating stability, stabilize the water temperature and provide a
buffer for temperature variation due to unit sequencing and defrost. If the
system water capacity is too low, use a buffer tank to reach the minimum value
shown in Table 2.
In the following cases, the system must include buffer tanks to prevent
frequent start and stop cycling of the unit, which can cause damage to the
compressors and increase operating costs:
- The water system volume is below the minimum required volume
- The application requires high accuracy temperature control
- The load between the unit and the customer terminal does not match, for example if the customer terminal loading is less than the minimum turndown rate (20%) of the unit
Ensure the volume of the buffer tank is not less than the minimum water
capacity minus the pipeline water capacity minus the end water capacity. The
minimum volume is 6.06 gal/ton (6.5 L/kW) and the recommended volume is
between 7 gal/ton (7.5 L/kW) and 11.18gal/ton (12 L/kW).
Note: If the site’s requirement of water temperature fluctuation is
specific, contact your local Johnson Controls office.
To avoid this, a buffer water tank should be applied, or the diameter of main
water pipe should be enlarged to meet the recommended range in the Table 2.
See the following figure for thcorrect installation method of the buffer
tank. Expansion tank (Pot)
The system design must include an expansion tank to help manage the following
potential issues:
- To help with water volume changes in the system, for example from thermal expansion and contraction caused by the water temperature change
- To prevent the water system from freezing and cracking in low temperatures
- To prevent unstable pressure at the inlet of the pump
- To replenish water in the system and outlets
Connect the expansion tank piping to the pump inlet before the pressure gauge
on the water return pipeline. Ensure it is between 59.06 in. (1.5 m) and 118.1
(3 m) from the pressure gauge.
Note: Consider using antifreeze for insulation in low temperatures.
Freeze protection
Intelligent anti-freezing
With the temperature sensor for monitoring the temperature of entering and
leaving water, the YMAE unit shuts down to avoid the water-side heat exchanger
being frozen when the monitored water temperature is lower than the anti-
freezing setpoint. It resumes after the temperature rises above the anti-
freezing setpoint again.
Ambient Temperature | Freeze Protection Entry Conditions |
---|---|
32°F to 37.4°F | 0°C to 3°C |
26.6°F to 32°F | -3°C to 0°C |
system LWT or EWT ≤ 50°F (10°C)
14°F to 26.6°F| -10°C to -3°C| Water pump has been OFF for 15 min, or either
system LWT or EWT ≤ 53.6°F (12°C)
Less than 14°F| Less than -10°C| Water pump has been OFF for 8 min, or either
system LWT or EWT ≤ 53.6°F (12°C)
If there is fault with the sensor| Water pump has been OFF for 15 min, or
either system LWT or EWT ≤ 53.6°F (12°C)
LWT = leaving water temperature
EWT = entering water temperature
- To enter freeze protection, both LWT and EWT are monitored. If either parameter meets the control logic, the unit enters freeze protection mode
- To exit freeze protection, the priority is to check the system EWT. If EWT parameters meet the control logic, the unit exits freeze protection. If there is an EWT sensor fault, the system LWT is checked
Freeze protection actions and exit criteria
Freeze protection control includes a cooling loop and heating loop:
- Heating water loop: The unit is off, or the unit is operating in cooling only mode and the heating loop is on standby
- Cooling water loop: The unit is off, or the unit is operating in heating only mode and the cooling loop is on standby.
- Glycol mode does not have this control logic
Cooling water loop:
- If the system LWT (EWT) is ≥ 55.4°F (13°C) after water pump startup has been running for 90 s, freeze protection stops
- If the system LWT (EWT) is <55.4°F (13°C) after water pump startup has been running for 90 s, the water pump keeps running until the system LWT (EWT) is >59°F (15°C), which stops freeze protection
Note: The maximum freeze protection operation duration is 120 min.
Heating water loop:
- If the system LWT (EWT) is ≥55.4°F (13°C) after water pump startup has been running for 90 s, freeze protection stops
- If the system LWT (EWT) is< 55.4°F (13°C) after water pump startup has been running for 90 s, the water pump keeps running until the system LWT (EWT) is <62.6°F (17°C), which stops freeze protection
Note: The maximum freeze protection operation duration is 60 min
Unit freeze protection design considerations
It is necessary to drain water from the unit’s water circuit when the ambient
temperature is low or if it has not been in use for 90 days. Otherwise, parts
of the water system, including the heat exchanger and pump, have a risk of
freezing at low temperature.
After draining the water, the unit needs to be powered off to avoid damaging
the pump, the compressor, and other parts when the unit automatically starts
the anti-freezing operation.
When the ambient temperature is lower than 32°F (0°C), the unit can freeze. If
the user does not drain water from the unit or if the unit still needs to run
when the ambient temperature is lower than 32°F (0°C), do not cut the power
supply of the unit, do not close the water system valve, and ensure that the
water pump can be controlled by the heat pump to enter anti-freeze operation
if necessary. Ensure that the water system can circulate smoothly during the
anti-freeze operation, so that the unit can automatically
enter the anti-freeze operation when needed.
To ensure the reliability of anti-freeze operation throughout the year, add
glycol antifreeze to the chilled water system. When there is a year-round
chilled water demand, that is cooling below 32°F 0°C or cooling and heating at
the same time, or low temperature
chilled water demand, that is chilled water temperature below 41°F (5°C), the
chilled water system needs to add the appropriate concentration of glycol
antifreeze. The antifreeze concentration and solution freezing point needs to
be reliable during the lowest possible temperatures, which is affected by the
ambient temperature and water temperature. Confirm the specific requirements
of the antifreeze solution and the inhibitor with the pump supplier if the
pump is prepared by customers.
BMS control
The YMAE building management controls use the RS-485
standard, including BACnet MS/TP, Modbus RTU or N2 connectivity for
communication with virtually any building management system.
This advanced, embedded control capability also allows multiple heat pumps to
be connected and monitored through a single controller. Each unit features a
touchscreen display that has an easy-to-use, web-style interface and intuitive
navigation for easy access to operational data. Information can be displayed
in multiple languages and setup is very easy.
To simplify installation and setup, the SC-EQ Communication Board
automatically determines the building automated system (BAS) protocol, Baud
rate, and the model of the connected chiller or rooftop unit. The only user
setting is the MAC address for the SCEQ on the BAS network.
Cabling requirements
The BAS port on SC-EQ board in the electrical cabinet of the leader module
unit is the communication interface between the unit and the BMS. The customer
needs a RS-232/RS-485 converter between the SC-EQ BAS port and the customer
BAS.
The communication line has polarity: A is connected to converter A (or +), B
is connected to converter B (or -). To avoid malfunction, ensure it is
connected correctly.
For cabling distance within 100 m, use 2 × 0.75 mm² shielded twisted pair
cable. For cabling between 100 m to 500 m, use 2 × 1.0 mm² shielded twisted-
pair cable. BMS command
instructions
The BAS can request the unit to switch between modes a minimum of every 12
minutes. The unit must operate for a minimum of six minutes before it can be
switched back to the previous mode. When switching modes, there needs to be
time between stopping one mode and starting another so that system
temperatures can moderate enough for the unit to start in the new mode of
operation. If the BAS rapidly switches the unit from heating to cooling, or
visa-versa, the extreme temperature from the previous mode may cause the unit
operational issues in the newly commanded mode.
Modbus and BACnet
For the most recent points lists for the two-pipe and four-pipe units, refer
to the YMAE Points List Two-Pipe Equipment and YMAE Points List Four-Pipe
Equipment on the Chillers Knowledge Exchange.
About Johnson Controls:
At Johnson Controls (NYSE:JCI), we transform the environments where people
live, work, learn and play. As the global leader in smart, healthy and
sustainable buildings, our mission is to reimagine the performance of
buildings to serve people, places and the planet.
Building on a proud history of nearly 140 years of innovation, we deliver the
blueprint of the future for industries such as healthcare, schools, data
centers, airports, stadiums, manufacturing and beyond through OpenBlue, our
comprehensive digital offering.
Today, with a global team of 100,000 experts in more than 150 countries,
Johnson Controls offers the world’s largest portfolio of building technology
and software as well as service solutions from some of the most trusted names
in the industry.
Visit www.johnsoncontrols.com for more
information and follow @JohnsonControls on social platforms.
© 2023 Johnson Controls. All rights reserved.
The power behind your mission
APP2306008
Documents / Resources
| YORK
YMAE Air to Water Inverter Scroll Heat
Pumps