saxby lighting 78577 Microwave Motion Sensor User Manual

October 30, 2023
saxby lighting

saxby lighting 78577 Microwave Motion Sensor User Manual
saxby lighting 78577 Microwave Motion Sensor

MICROWAVE MOTION

MICROWAVE MOTION
MICROWAVE MOTION

FEATURE

  • Sensor parameters can be conveniently set by a remote control.
  • Mounting height up to 49.2 ft (15m)max. , suitable for warehouse use.
  • Water proof sensor with IP65 rating.
  • Automatic dimming when used in combination with 1 -10V dimmable control gears.
  • Built-in adjustable daylight sensor.
  • 1-10V interface can match up with Merrytek stand-alone daylight sensor MS01 and achieve daylight harvesting.
  • Optional mounting brackets for different application.

SPECIFICATIONS

Input voltage 220-240Vac, 50/60Hz(AUS/ EU RO)120/277Vac,50/60Hz(UAS)
Rated load(EU RO/AUS) 800W- Inductive1200W- Resistive
Rated load(USA) 120Vac 50/60H z 4A ballast277Vac 50/60H z 3 A ballast
Surge current of load SOA (50% Ipeak, twidth =500uS, 277Vac full load, cold

start);80A (50% Ipeak, twidth =200uS, 277Vac, full load, cold start)
Detection area| 100 % /75 %/50 % /25 %
Hold time| 5 S/30S/1 min/3 min/5min/10min/20min/30min
Daylight sensor| 51u x/15L u x/3OL u x/50Lu x/100Iux/150Iux/ Disable
Stand – by period| 0s/105/1 min/3 min/5 min/10min/3 Omin/+ co
Stand -by dimmin g level| 10 % / 20 % / 3 0% / 50%
Sensor principle| Microwave motion detector
Microwave frequency| 5.8GH z+75MHz, ISM wave band
Mounting height| 49.2 ft (15m) Max.
Detection angle| 150°(Wall installation), 360°(Ceiling installation)
Motion detectio n| 1.6-3.3 ft/s(0.5 -1 m/s)
Operating temperature       -35°C -55°C
I P ratin g| IP65 (INDOOR USEONLY)
Factory Setting| Detection area:75 % ,Hold time:5s, Stand-by Period: 0s, Stand -by dim level:10 % , Daylight Sensor: Disable

GENERAL GUIDELINES FOR INSTALLATION

  1. The sensor should be installed by a qualified electrician. And ensure that the electricity supply is switched off before installing or servicing the product.
  2. Installation inside a glass or plastic housing will result in a reduction of detection sensitivity. Expect a reduction of approximately 20 % for every 3mm of thickness.
  3. Detection area will be affected by speed of motion, height of installation and volume of moving object.
  4. Daylight sensor was tested on sunny environment with no lampshade. ambient lux level could be different under different weather, climate, season or environment

Application Notice

  1.  Sensors settings may need to be adjusted to match installation site, please follow below instructions or contact manufacturer.
  2. The sensor is designed for indoor use only. Outdoor use for a long time may reduce the waterproof effects. The raining or wind blowing may trigger the microwave sensor even if without human motion when outdoor use.
  3. The distance between any two sensors should be at least 3m to avoid interference with each other.
  4. When the microwave sensor is installed in a metal lighting fixture or space withlarge reflector, for example a warehouse with metal roof, the microwave will be reflected and cause the lights permanently illuminated even if without motion signal. Please reduce the detection area (sensitivity) to solve the problems, or contact the microwave sensor manufacturer to provide technical support.
  5. Make sure the sensor not close to or be blocked by high density material, such as metal, glass, concrete walls etc. The materials will reduce or block microwave and cause false trigger.
  6. Make sure there are no fans or other vibrating objects in installation area. The movements will trigger sensor as well.

Initialization

  1. ON/OFF function or 3-step dimming function: After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it completely turns off light. During the initialization, the sensor is not able to detect movement.
  2. 2-step dimming function: After power on, the sensor automatically turns on light at 100% brightness. After 10sec, it dims the light to a low light level (set by stand-by dim level). During the initialization, the sensor is not able to detect movement.

DETECTION PATTERN(FOR WALL MOUTING)

DETECTION PATTERN
DETECTION PATTERN
DETECTION PATTERN
DETECTION PATTERN
DETECTION PATTERN

INSTALLATIONS

INSTALLATIONS
INSTALLATIONS
INSTALLATIONS
INSTALLATIONS

Remote Control Setting

Remote Control Setting

Remarks

Press the “ON/OFF” butto n, the light goes to constant on/off mode, sensor is disabled. Press any button to quit from this mode and the sensor starts to work Press “Reset” butto n, all parameters are same as settin g of factory settings.

Press “Sensor motion ” button , the light quits from the constant on/ off mode, and the sensor starts to work ( The latest setting stays in validity )

Press “DIM Test” button, the 1-10 V dimming works to test whether the 1-10Vdc dimmin g ports are connected p roperly. After 2 s, it returns to the latest setting automatically.

Override DH: Long press >3s,sensor will quite daylight priority(MCO54V RC3)/ daylight harvesting(MCO54V RC4) mode, daylight threshold start to work with previous daylight value NA(MCO54V RC2) DH Mode: Long press >3s,sensor move to daylight priority mode, please be sure preset daylight threshold is not “Disable” (MCO54V RC3) Long press >3s,sensor will take current light level as target lux level, dim up/ down load accroding to change of ambient light level(MCO54V RC4),each time press DIM+,DIM-,target light leve change is 5% NA(MCO54V RC2)

Set occupancy light level in range of 50-100%,dimming level is 2% each time to press Dim+/Dim- button

S(et c
._ p:ium,| reelect :in
Area| hulcrie| Stand-by| Stand-dy| Imoy ivit
St:”Ar| Srl.rdtivily
riodul
---|---|---|---|---|---|---
QS1| 100%| 5min| 10min| 10%| 30Lux| II–,
QS2| 100%| 10min| 30min| 10%| Disable| H,
QS3| 100%| 20min| 30min| 10%| Disable| Fh

Note : Detection area / H old time /Stand-by period / Stand -by dim level /Daylight sensor can be  adjusted by pressing the corresponding button. The latest setting will stay valid.

R ress the “TEST 2S ” botton can enter the test mode an y time. At the mode, the sensor parameters as below: Detectio n Area is 100 % , Hold Time is 5s, Stand -by Dim Level is 10% , Stand – by Period is 0s, daylight sensor disable. This function onIy for testin g. Quit the mode by pressing “RESET ” or any other function buttons.

Press “HS ”button to set the detection area to be high sensitive. Press “LS ” button to set the detection area to be low sensitive. The adjustment bases on the “Detection Area” parameter you set.

Daylight Sensor
Set up daylight thresh old:
5Lu x/15Lu x/3OL ux/50 Lux/100Lu x/150Lu x/ Disable

Stand-by period
Set up stand -by time: OS/10S/1 min/3min/5min/10min/30min/+ •

Hold time
Set up hold time: 5S/30S/1 mi n/3 min/5min/1 Omi n/20min/30min

Stand-by dim level
Set up stand -by dim level: 1 0%/20%/30%/50%

Detection Area
Set up detection area: 25%/50%/75%/100%

Remote Distance
Toggle button can set the remote distance of remote control and sensor.

Mounting height Distance between sensors
49.2’/15m 16.4’/5m
39.4’/12m 13.1’/4m
29.5’/9m 13.1’/4m
19.7’/6m 11.5’/3.5m

Instrauctions

Unique design of infrared transmitting device

Note
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interf-erence to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following Measures:
Unique design

  • -Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Conned the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

WIRING

WIRING

NOTE: Lord bushing of the torque is 2.5NM,Torgue of nut is 2.5NM.

FAQ

Question Cause Remedy
The load will not illuminate. Incorrect daylight sensor settin g selected.

Adjust setting.
Load has failed.| Replace load.
Power is switched off.| Switch on.
The load is permanently illuminated. (SEE NOTE1)| Co ntinuous movement in the detection area.| Check detection area setting.
The lamp (containing sensor) is installed in an area too close to reflective surfaces, i.e. metal, glass or concrete walls.| 1, Make sure installation area suitable with atleast 39.4 inches(100cm) space between lampand surrounding reflective surfaces. 2, Reduce sensitivity (detection area).
The load wilI not illuminate despite movement.| Speed of moving object is not in the range of1.6-3.3ft/s(0.5-1 m/s) or the detection radius is too small.| Check detection area setting.
The remote control is not working.| The battery on the remote control is run out.| Change the battery.
The remote control is not aligned with sensor.| Change the remote angle.

Note

WIRING

Microwave detection includes two parts called main wave and side wave. Main wave normally detects the motion signal. Side wave does not effect motion detection but might disturb main wave if the microwave motion sensor is built- in a sealed metal luminaire as microwave can not pass through metal.

When the microwave module is built into a metal lighting luminaire or installed in a sensor near a wall, the side wave will be reflected by the metal base or the wall. It can disturb the main wave. As the result of this, the microwave motion senor might not perform optimally. Reducing the detection sensitivity or the side wave will help to solve such problems.

FCC Caution:

Any Ch anges or mod i fications n ot exp ressly approved by the party respon sibIe for co mplian ce could void the user’s autho rity to operate the equ i pment. This device complies with part 15 of the FCC RuIes. O peration is subject to the foIIowing two conditions:

  1. This device may not cau se harmful interfe rence.
  2. this device must accept any interference re ceived, including interference that may cause undesire d operation .

IC RSS warning

This d ev ice co mplies with Industry Can ada licence -exempt RSS standard (s). O peration is subject to th e follow i ng two cond ition s

  1. this device may not cau se interference
  2. this device must accept any interfe rence, including interferen ce that may ca use undesired oper ation of the dev ice.

Le présent areil est confo rme aux CN R d’ I ndustrie Can ada IicabIes aux areils radio exempts de Iicence
L’expt oitatio n est autorisée au x deux Conditions suivan tes:

  1. I ’ areil ne doit pas produire de brouil lage, et
  2. I ‘ utilisateur de I ‘ ap pareil doit accepter tout brouil Iage radioélectriq ue subi, méme si Ie brouilIage est suseepti bIe d’ en compromettre Ie fo nctionnemen t

Saxby Lighting, Cabot Lane, Creekmoor, Poole, Dorset, BH17 7BY.
T: (+44) 0333 00 333 08 F: (+44) 01202 409811 E: [email protected]
www.saxbylighting.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

saxby lighting User Manuals

Related Manuals