ACDC M3EL Series Residual Current Protection Circuit Breaker User Manual
- October 30, 2023
- ACDC
Table of Contents
- ACDC M3EL Series Residual Current Protection Circuit Breaker
- Scope of application
- Main functions and characteristics:
- Product model and its meaning
- Use environment
- Description of protection characteristics
- Overcurrent short-circuit protection characteristic curve
- Communication function
- Product installation
- Operation instructions of LCD products
- Maintenance menu
- Appearance and installation dimensions
- Match of cross-sectional area and the rated current of connecting wire
- Transportation and storage
- QR SCAN
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ACDC M3EL Series Residual Current Protection Circuit Breaker
Scope of application
The rated insulation voltage of the M3EL series of residual current action circuit breaker is 800V, which is suitable for those three-phase four-wire neutral-point direct ground (TT) distribution network of AC 50Hz, rated voltage 400V, and rated current of up to 630A. They are used to provide indirect contact protection; to prevent the damage to insulation of the equipment, which will produce the fire hazards caused by the grounding fault current; also, they can be used to distribute power, protect circuits and power equipment from overload, undervoltage, short circuit, single-phase grounding and other malfunctions.
- The products shall meet the following standards:
- GB 14048. 1-2012 “Low-voltage switchgear and controlgear – Part 1: General Provisions”;
- GB 14048. 2-2008 “Low-voltage switchgear and controlgear – Part 2: circuit breaker”;
- GB17701-2008 “Circuit Breaker for
- Equipment”;
- GB/Z22202-2008: Reliability Test Method for Residual Current Action Circuit Breaker for
Household and Similar Applications;
JB/T 10494-2005 Reliability Test Method for Residual Current Action Circuit
Breaker for
Household and Similar Applications
JB/T 8979-2006 “Residual Current Action Circuit Breaker With or Without
Overload Protection”
Main functions and characteristics:
- A high-performance 32-bit ARM microprocessor is adopted to carry out signal processing and intelligent control in real time;
- LCD display in Chinese, with friendly human-machine interface, easy for operation;
- Residual current (leakage) protection, with residual current shift being fixable online, with the function of reclosing;
- Monitor and track the circuit’s residual current in real time, and automatically adjust the shift position, to ensure delivery rate and reliability of products;
- Three-stage protection (long delay, short delay and instantaneous), with electronic tripping, independent of the power supply voltage;
- With high breaking capacity, ensure the reliability of short-circuit protection of the line;
- Over-voltage protection, under-voltage protection, phase loss protection;
- Real-time display of residual current, three-phase power supply voltage and load current of the line;
- Protection functions and parameters can be set and modified online;
- Identification and display of tripping type (residual current, blocking, overload, undervoltage, overvoltage, phase loss), which can be stored, queried and deleted.
- With communication function, remote signaling, telemetry, remote control, remote adjustment can be realized.
- With infrared communication function, it can be also equipped with the outer hanging lightning protection module.
Product model and its meaning
Use environment
- The installation site should be free of conductive dust, corrosive gases, flammable and explosive gases, rain or snow erosion
- Altitude ≯2,000m;
- Ambient temperature -5℃~ +40℃, the average daily maximum temperature ≤ +35 ℃;
- Relative humidity ≤ 50% (when ambient temperature is +40 ℃);
- The strength of external magnetic field in the installation place should not exceed 5 times of that of the geomagnetic field in any direction.
- The installation location shall be well ventilated and heat dissipated.
Main technical parameters
Specifications and models | 125 | 250 | 400 | 630 |
---|---|---|---|---|
Frame current (A) | 125 | 250 | 400 | 630 |
Number of poles | 3P+N | 3P+N | 3P+N | 3P+N |
Rated working voltage Ue (V) | AC 400 50HZ | |||
Rated insulation voltage Ui (V) | AC 800 |
Rated impact resistance voltage Uimp
(V)
| 8000
Arc distance (mm)| >50| >50| >100| >100
Limit short-circuit breaking capacity
Icu (kA)
| 50| 50| 65| 85
Running short-circuit breaking
capacity Ics (kA)
| 35| 35| 42| 65
Rated residual short-circuit switching
(breaking) capacity IΔm(kA)
| 12. 5| 12. 5| 16 5| 21 5
Residual current action characteristics| AC type
Rated residual action current IΔn (mA)| 50/100/200/300/400/500/600/
800, automatic, OFF
| 100/200/300/400/500/600/800/
1000 automatic, OFF
Residual action time characteristics| Delay type/non-delay type
Breaking time
(S)
| Delayed type| IΔn≤0.5| IΔn≤0.5| 5 IΔn≤0.15| 10 IΔn≤0.15
Non-delayed type| IΔn≤0.3| 2 IΔn≤0.15| 5 IΔn≤0.04| 10 IΔn≤ 0.04
Delay-type limit non-driving time (S)| 2 IΔn: 0.06
Automatic reclosing time (S)| 20-60
Operating performance (times)
| Powered| 1500| 1000| 1000| 1000
Unpowered| 8500| 7000| 4000| 4000
Total number of
times
| 10000| 8000| 5000| 5000
Overload and short-circuit
characteristics
| Three-stage protection, electronically adjustable. See “Protection
Characteristics Description” for details
Overvoltage protection value (V)| Set the value (250~300)+5% off by default
Undervoltage protection value (V)| Set the value (145~200)+ 5%, off by default
Joint control delay time (ms)| ≤40ms
Communication delay time (ms)| ≤200ms
Description of protection characteristics
Overload long delay protection
Action value setting range
Table 1: Overload long delay parameter setting
Parameter | Frame current | Set value | Factory setting value |
---|
Action setting value M
| 125| 50A, 63A, 80A, 100A,
125A
| 125A
250| 100A, 125A, 140A, 160A
180A, 200A, 225A, 250A
| 250A
400| 200A, 225A, 250A, 315A,
350A, 400A
| 400A
630| 315A, 350A, 400A, 500A,
630A
| 630A
Delay time setting
value tL
| | 3s, 4s, 6s, 8s, 10s, 12s, 14s,
16s, 18s, OFF
| 12 s
Action characteristics
Table 2: Protection action characteristics
Ambient
temperature
| Current name| Current name| Current name
---|---|---|---
+ 40 ℃
| Agree not to trip the
current
| 1.05 Ir1| ≥2h
Agree to trip the
current
| 1.3Ir1| <2h
Time delay characteristics
The overload protection is carried out according to the anti-timing
characteristics:
T= ( 6Irl/I ) 2tL Delay accuracy: ± 10%
Among them, T is the action time value, Irl is the long delay protection
setting value, I is the fault current, and tL is the long delay time setting
value
short-circuit short delay protection
Short-circuit short time delay protection prevents the impedance short circuit
of the power distribution system. The delay of trip is to realize the
selective protection.
Setting of short-circuit short delay protection parameters
Table 3: Setting of short-circuit short delay parameters
Parameter setting | Factory setting value |
---|
Short delay action current
setting value Ir2
| 2Irl, 2.5 Irl, 3Irl, 4Irl, 5Irl,
6Irl, 7Irl, 8Irl, 10Ir, 12Ir
| 6Irl
Short delay time setting value
ts
| 0.1s, 0.2s, 0.3s, 0.4s, 0.6s,
0.8s, 1.0s, OFF
| 0.4s
Short-circuit short delay protection action characteristics
Table 4: Short-circuit short delay action characteristics
Characteristics | Fault current multipler | Tripping time | Time delay error |
---|
Non-action
characteristic
| ≤0.8 Ir2| No action| ±40ms
Action characteristics| >1.2 Ir2| Delayed action| ±40ms
Instantaneous protection
Setting of short-circuit instantaneous protection parameters
Table 5: Instantaneous parameter settings
Parameter setting | Factory setting value |
---|
Instantaneous action current
setting value Ir3
| 4Irl, 6 Irl, 7 Irl, 8 Irl, 10Irl,
11Irl, 12 Irl, 13 Irl, 14 Irl, OFF
| 10 Irl
Short-circuit instantaneous protection action characteristics
Table 6: Instantaneous action characteristics
Characteristics | Current multipler (I/Ir3) | Time delay error |
---|---|---|
Non-action characteristic | ≤0.8 | |
Action characteristics | >1. 2 | ±40ms |
Residual current protection characteristics
Shift setting range
Model
Specification
| Parameter| Setting value (mA)| Factory setting
value
---|---|---|---
125-400|
Residual action current IΔn
| 50,100,200,300,400,500,600,800, off,
automatic
|
500
630-800| 100,200,300,400,500,600,800,1000,off,
automatic
Action characteristics
Parameter | Characteristics |
---|
Rated non-action
current
| 0.5IΔn
Rated action
current
| ≥0.75IΔn
Time delay characteristics| 2IΔn
Limit non-driving time (Δt)
| Breaking time
IΔn| 2 IΔn| 5 IΔn| 10 IΔn
Non-delayed type| —-| ≤0.3s| ≤0.15s| ≤ 0.04s
Delayed type| ≥0.06s| ≤0.5s| ≤ 0.2s| ≤ 0.15s
Automatic shift mode
In the automatic shift mode, the shift values and the floating values are:
Shift value (mA) | 200 | 300 | 400 | 500 |
---|---|---|---|---|
Floating value (mA) | 100 | 150 | 200 |
When the residual current exceeds the floating value of the shift and fails to achieve its action value, and maintains stable for 60s, it will float up by one shift, and so on, until the maximum shift; When the residual current is less than the floating value of the next shift and remains stable for 120s, it will float down by one shift, and so on, until the minimum shift. Take the “automatic” shift, with the initial residual current of the line being 100mA, as example. The circuit breaker is energized and the shift setting is automatically fixed at 300mA. After the residual current increases to 150mA and above, and keep stable for 60s, the shift changes to 400mA; When the residual current decreases to 100mA and below, and keep stable for 120s, the shift changes to 200mA.
Automatic reclosing/locking
Automatic reclosing: After the residual current exceeds the action current
value shift and gets tripped, it will be able to reconnect automatically after
20~60 seconds, but the manual closing is not time-limited.
Locking: The locking time is 5s, that is, when there is another leakage fault
within 5s after the product reclosing, the circuit breaker can trip again and
lock in the time of action, and it is necessary to manually close instead of
automatically reclosing; When the product has a leakage failure outside 5s
after the re-closing, the circuit breaker is tripped but not locked during the
action time, and it can be automatically reclosed within 20~ 60 seconds.
Over-voltage protection function
When the line phase voltage is higher than the over-voltage protection setting
value, the circuit breaker performs protective tripping. When the line voltage
is restored to normal voltage, the circuit breaker can be automatically closed
and put into operation. The setting value of over-voltage protection is 250V ~
300V, and the factory value is set to 265V. Users can set or close the
protection by themselves.
Under-voltage protection function
When the line phase voltage is lower than the under-voltage protection setting
value, the circuit breaker performs protective tripping. When the line voltage
is restored to normal voltage, the circuit breaker can be automatically closed
and put into operation. The setting value of the under-voltage protection is
150V~200V, the factory setting value is 165V. Users can set or close the
protection by themselves.
Phase loss protection function
When there is a phase loss on the line power supply terminal, the circuit
breaker performs protective tripping. When the line is restored to normal
voltage, it can be automatically closed and put into operation. The factory
default setting is closing.
Linkage protection function
Through the linkage interface, it can be linked with other fire protection
equipment for linkage protection, specifically as follows:
DI input settings| Functional
specifications
| Priority| Delay time
(ms)
---|---|---|---
Input control
| IN1 is short connected
with DCOM
| Circuit breaker closing| Low|
≤40ms
IN3 is short connected
with DCOM
| Circuit breaker opening| Height
Note: In case of short connection for a long period of time, the short- circuit is always in the opening state.
Overcurrent short-circuit protection characteristic curve
Communication function
Communication
interface
| Interface type| Communication
protocol
| Communication
address
| Communication
rate
---|---|---|---|---
RS485
| ****
External terminal
| DL/T-645
Modbus (adjustable)
| ****
1-255
| 600-38400
(adjustable)
Product installation
Product installation notes
- Please check whether the product specifications are correct and the accessories are complete before installation;
- Please read the instructions for use carefully, to ensure proper installation and daily maintenance;
- Products must be installed vertically;
- According to the product rated current and relevant criteria, select the appropriate wire and connect in strict accordance with the provisions of wiring.
The upper part is the power supply terminal, in which 1, 3 and 5 are respectively connected with phases A, B, C, and N is connected with zero line. The lower part is the load terminal, in which 2, 4 and 6 are respectively connected with phases A, B, C, and N is connected with zero line;
- The cross-sectional area of incoming and outgoing lines shall meet the construction requirements as specified in the standard, and the conductive part shall not be exposed beyond the shell;
- Install the arc plate correctly after wiring is completed;
- Install in places where non-electrician and minors are not accessible, to prevent electric shock or changes to the correct configuration and wiring of the product;
Operation of LCD products
The circuit breaker is equipped with a test power-up function upon power-on
(which can be turned off), which can effectively guarantee safety of the
follow-up equipment.
Product commissioning
After the wiring is complete and correct through check, energize the circuit
breaker. When the circuit breaker is in a disconnected state, set the
parameters according to the operation instructions. After the setting is
complete, perform the closing operation. The running states are shown in Fig.
2, Fig. 3 and Fig. 4.
In the closing condition, press [test trip] key to carry on the residual
current test trip, and perform reclosing within 20S-60S.
15:04:23 | 15:07:25Automatic | 13:01:25 Automatic | |
---|---|---|---|
Ua:220V | Ub:220V | Ua:220V Ub:220V | Rated residual 200mA |
Uc:220V | Uc:220V | Residual current 0mA | |
Opening standby | Closing operation | During closing… | |
Fig. 2 | Fig. 3 | Fig. 4 |
Closing operation of the circuit breaker
-
Automatic closing
Press [closing] key for 2 seconds, and LCD will display “during closing..”. After the closing, the state of the LCD screen appears as “closing operation”, and the circuit breaker enters the normal operation state. -
Manual closing
-
Use the attached manual wrench, insert it into the hole, and rotate clockwise by around 360°. After the success of closing, the state of the LCD screen is automatically updated as “closing operation”, and the circuit breaker enters the normal operation state.
Note: Manual switching can be performed when the circuit breaker’s main contact is disconnected. The closing operation is shown in the above Method 2. Pay attention to the safety of load equipment and personnel during manual closing.
Disconnection operation of circuit breakers
- In the running state, press the [opening] key. After the successful opening, the state of the LCD screen is shown as “opening standby”.
- If manual opening is needed, use wrench, insert it into the hole, and rotate clockwise by around 180°. After the successful opening, the state opening/closing is shown as “opening”.
Operation instructions of LCD products
Main menu
■ Setting 2 Query
3. About
4. Maintenance
| 1. Setting
■ . Query
3. About
4. Maintenance
| 1. Setting 2 Query
■ . About
4. Maintenance
---|---|---
- In the real-time display status
- Press [Setting] button to enter the main menu interface as shown above.
- Press [Up/Down] button to control the highlighted display position.
- Press [OK] button to enter the corresponding sub-menus.
Setup menu
■ Overvoltage setting | ■ Short-circuit setting | ■ Time setting |
---|---|---|
2. Undervoltage setting | 6. Characteristics setting | A. Communication |
setting
3. Default phase setting| 7. Residual current setting| B. Display setting
4. Overload setting| 8. Residual record setting| C. Password setting
■ Overvoltage setting| ■ Short-circuit setting| ■ Time setting
---|---|---
2. Undervoltage setting| 6. Characteristics setting| A. Communication
setting
3. Default phase setting| 7. Residual current setting| B. Display setting
4. Overload setting| 8. Residual record setting| C. Password setting
As shown above.
- [Up/Down] button to control the highlighted display position or page flip.
- [OK] button to enter the corresponding setting menu.
- [Return] button to return to the previous menu.
Overvoltage setting
■ Overvoltage setting | Setting value: 265V | Setting value: 265V |
---|---|---|
2. Undervoltage setting | Trip switch: ON | Trip switch: ON |
3. Default phase setting | Alarm switch: OFF | Alarm switch: OFF |
4. Overload setting | Setting: return | Save: cancel |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Overvoltage protection can be turned OFF or set as 250V to 300V.
Undervoltage setting
1. Overvoltage setting | Setting value: 145V | Setting value: 145V |
---|---|---|
■ . Undervoltage setting | Trip switch: ON | Trip switch: ON |
3. Default phase setting | Alarm switch: OFF | Alarm switch: OFF |
4. Overload setting | Setting: return | Save: cancel |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Undervoltage protection can be turned OFF or set as 150V to 200V.
Default phase setting
1. Overvoltage setting | Setting value: 50V | Setting value: 50V |
---|---|---|
2. Undervoltage setting | Trip switch: ON | Trip switch: ON |
■ . Default phase setting | Alarm switch: OFF | Alarm switch: OFF |
4. Overload setting | Setting: return | Save: cancel |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Phase default protection can be turned OFF or set as 10V to 50V.
Overload setting
1. Overvoltage setting | Setting value: 2.0Ir1 | Setting value: 2.0Ir1 |
---|---|---|
2. Undervoltage setting | Setting value: 100A | Setting value: 200A |
3. Default phase setting | Delay time: 12S | Delay time: OFF |
■ . Overload setting | Setting: return | Save: cancel |
As shown above
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Delay time is OFF / (or) overcurrent protection function is disabled when it is OFF See the curve chart for the overload delay time curve.
Short-circuit setting
1. Overvoltage setting | Setting value: 2.0Ir1 | Setting value: 2.0Ir1 |
---|---|---|
2. Undervoltage setting | Setting value: 100A | Setting value: 200A |
3. Default phase setting | Delay time: 12S | Delay time: OFF |
■ . Overload setting | Setting: return | Save: cancel |
As shown above
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Delay time is OFF / (or) overcurrent protection function is disabled when it is OFF Ir3: short-circuit instantaneous current
Ir2: short-circuit short-time delay current
Note: the Ir2 setting value cannot exceed the Ir3 setting value
Characteristics setting
5. Short-circuit setting | Common alarm: ON | Gear Return: ON |
---|---|---|
■ . Characteristics setting | Reclose: ON | Overcurrent alarm: ON |
7. Residual current setting | Overcurrent protection: ON | Sound and light |
alarm output:
ON
8. Residual record setting| Setting 1: return| Save 2: cancel
As shown above
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Delay time is OFF / (or) overcurrent protection function is disabled when it
is OFF Common alarm: short-circuit instantaneous current
Reclosing enablement: it will not automatically reclose after closing
Gear return: the residual current will not automatically float in auto
mode after shutdown Overcurrent protection: all current-related faults will
not be protected after shutdown Overcurrent alarm: all current-related faults
will not be signaled after shutdown
Sound and light alarm: all alarms will not be output after shutdown
Residual current setting
5. Short-circuit setting | Residual gear: 200mA | Residual gear: automatic |
---|---|---|
6. Characteristics setting | Non-driving time: 100ms | Non-driving time: – |
■ . Residual current setting | Action type: trip | Action type: trip |
8. Residual record setting | Setting: return | Save: cancel |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Residual record setting
5. Short-circuit setting | Change difference: 50mA | Change difference: 50mA |
---|---|---|
6. Characteristics setting | Interval time: 60 minutes | Interval time: 60 |
minutes
7. Residual current setting| Overlimit alarm value: 400mA| Overlimit alarm
value: 400mA
■ . Residual record-setting| Setting: return| Save: cancel
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Time setting
■ Time setting | Time setting | Time setting |
---|---|---|
B. Communication setting | October 12, 2014 | October 12, ■ |
C. Display setting | 12: 12: 34 | 12: 12: 34 |
D. Password setting | Setting: return | Save: cancel |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Communication setting
9. Time setting | Protocol type: Modbus | Protocol type: DL_T654 |
---|---|---|
A. Communication setting | Address: 001 | Address:001 |
B. Display setting | Baud rate: 38400 | Baud rate: 24000 |
C. Password setting | Setting: return | Save: cancel |
As shown above
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Display setting
9. Time setting | Display setting | Display setting |
---|---|---|
A. Communication setting | Scroll time: 10S | Scroll time: 10S |
B. Display setting | Return time: 10S | Return time: 10S |
C. Password setting | Setting: return | Save: cancel |
As shown above.
[Up/Down] button to control the highlighted display position or adjust
parameters.
[OK] button to enter the corresponding setting menu/switch setting
options.
[Return] button to return to the previous menu.
Password setting
9. Time setting | Level 0 password setting | Level 2 password setting |
---|---|---|
A. Communication setting | — Please enter the password!! – | –wrong password! !- |
B. Display setting | Original password: 0000 | Original password: 1234 |
C. Password setting | New password: 0000 | New password: 0000 |
As shown above
- [Up/Down] button to control the highlighted display position or page flip.
- [OK] button to enter the corresponding setting menu.
- [Return] button to return to the previous menu.
- Level 0 password default value: 0000
- Level 1 password default value: 0000
- Level 2 password default value: 0000
Other settings
D. Other setting | Other setting | Other setting |
---|---|---|
E. Trail trip setting | Switch-on trial power: OFF | Power-on trial power: OFF |
F. Restore factory setting | Power-off release: OFF | Power-off release: ON |
G. Return setting | Setting: return | Save: cancel |
As shown above
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
- Switch-on trial power: ON– if the circuit is energized and is faultless, the product will automatically close;
- Power-off release: ON– the product automatically trips when the circuit is de-energized
Trial trip setting
D. Other settings | Trial trip setting | Trial trip setting |
---|---|---|
E. Trial trip setting | Trial trip time: OFF | Trial trip time: ON |
F. Restore factory setting | 12:12 on the 12th | 12:12 on the 12th |
G. Return | Setting: return | Save: cancel |
As shown above.
[Up/Down] button to control the highlighted display position or adjust
parameters.
[OK] button to enter the corresponding setting menu/switch setting
options.
[Return] button to return to the previous menu.
Restore factory setting
D. Other settings|
---|---
E. Trial trip setting| Restore factory setting
F. Restore factory setting|
G. Return| Return OK
As shown above
[Up/Down] button to control the highlighted display position or adjust
parameters.
[OK] button to enter the corresponding setting menu/switch setting
options.
[Return] button to return to the previous menu.
Level 1 password is required for restoring factory setting. No records and password parameters are allowed to be cleared when factory setting is restored and the maintenance mode can not be exited
Query menu
1. Setting | 1. Cumulative record | 5. Trip record |
---|---|---|
2. Query | 2. Peak record | 6. Residual alarm record |
3. About | 3. Residual over-limit record | 7. Line-residual record |
4. Maintenance | 4. Self-inspection record | 8. System record |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Cumulative record
Data reset: 00000 time | Current trip: 00001 time | Trial trip: 00001 time |
---|---|---|
Fault trip: 00000 time | Voltage trip: 00001 time | Exit the residual: 00001 |
time
Blocking trip: 00001 time| Manual trip: 00001 time| Operation time: 0000
minute
Residual trip: 00001 time| Zero-default trip: 00001 time| 12:12, October 12,
2014
As shown above.
[Up/Down] button to flip for checking.
[Return] button to return to the previous menu.
October 12, 2014 is the time when the system is restarted
Peak record
XXX.XV | XXXX.XXA | XXXXmA |
---|---|---|
XXX.XV | XXXX.XXA | XXXXmA |
Type: phase B voltage | Type: phase B current | Type: residual current |
Peak date: 1st | Peak date: 21st | Peak date: 12th |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
The peak record of the three-phase voltage, the three phase current and the residual current from the 1st to the 31st (maximum and minimum occurrence time) can be queried
Residual over-limit record
1. Setting | 1. Cumulative record | Over-limit phase: unknown |
---|---|---|
2. Query | 2. Peak record | Over-limit value: XXXXmA |
3. About | 3. Residual over-limit record | Start |
4. Maintenance | 4. Self-inspection record | End 00 |
As shown above.
- [Up/Down] button to query the record before and after.
- [Return] button to return to the previous menu.
- 00: represents the current record location
Self-inspection record
1. Setting | 1. Cumulative record | Self-inspection: successful |
---|---|---|
2. Query | 2. Peak record | Self-inspection mode: button |
3. About | 3. Residual over-limit record | Date: October 12, 2014 |
4. Maintenance | 4. Self-inspection record | time: 12:11:11 |
As shown above.
- [Up/Down] button to query the record before and after.
- [Return] button to return to the previous menu.
- 01: represents the current record location
Trip record
1. Setting | 5. Trip record | Cause of fault: overvoltage |
---|---|---|
2. Query | 6. Residual alarm record | Fault phase: phase A |
3. About | 7. Line-residual record | Date: October 10, 2014 |
4. Maintenance | 8. System record | 01 time: 12:00:12 |
As shown above.
-
[Up/Down] button to query the record before and after.
-
[Return] button to return to the previous menu.
-
[OK] button to switch to the real-time status before fault.
-
01: represents the current record location
Residual alarm record
1. Setting | 5. Trip record | Start: January 10, 2014 |
---|---|---|
2. Query | 6. Residual alarm record | Time: 12:33:10 |
3. About | 7. Line-residual record | End: October 11, 2014 |
4. Maintenance | 8. System record | 01 Time: 12:35:50 |
As shown above.
- [Up/Down] button to query the record before and after.
- [Return] button to return to the previous menu.
- 01: represents the current record location
Line-residual record
1. Setting | 5. Trip record | Residual phase: unknown |
---|---|---|
2. Query | 6. Residual alarm record | Residual value: 1000mA |
3. About | 7. Line-residual record | Date: October 9, 2014 |
4. Maintenance | 8. System record | 01 time: 12:35:50 |
As shown above.
- [Up/Down] button to query the record before and after.
- [Return] button to return to the previous menu.
- 01: represents the current record location
System record
1. Setting | 5. Trip record | System record |
---|---|---|
2. Query | 6. Residual alarm record | Event 002: system start-up |
3. About | 7. Line-residual record | 00:00:00 ID:001 |
4. Maintenance | 8. System record | October 20, 2014 Return |
As shown above.
- [Up/Down] button to query the record before and after.
- [OK] button to return to the previous menu.
- [Return] button to return to the previous menu.
- ID: represents the current record location
About menu
XXXX- 250A | After-sales service: | Factory: 20XX-XX-XX |
---|---|---|
Fixed version: V01.01 | Tel: XXXXXXXX | ============= |
Hardware version: V05.08 | Company: XXXXXXXX | No.: XXXXXXA0000 |
Factory: 20XX-XX-XX | www. XX. Com | ============= |
As shown above.
- [Up/Down] button to flip up and down.
- [Return] button to return to the previous menu.
Maintenance menu
1. Setting | —-Level 2 password—- | 1. Maintenance 5. Mechanical test |
---|---|---|
2. Query | –Please enter the password!!— | 2. Capacity 6. Password reset |
3. About | 0000 | ■ Trial trip 7. Logout return |
4. Maintenance | ————————————- | 4. Self-inspection 8. Return |
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Level 2 password is required to log in maintenance menu which will be
automatically logged out when there is no keyboard operation within return
time after logging in
Maintenance menu can check and operate the event record, login password and
switch status, etc. Trial trip: if the switch is in close status, the trial
trip function will be started to check whether release can be normally carried
out
Self-inspection : the switch starts the self-inspection program to check
whether there are error parameters
Mechanical test: the switch automatically conducts the on and off
operation, with an interval of 10 to 999 seconds/time
Maintenance mode
1. Maintenance 5. Mechanical test | Maintenance mode | Maintenance mode |
---|---|---|
2. Capacity 6. Password reset | Level 0 password: **** | Level 0 password: **** |
3.Trial trip 7. Logout return | Please enter the password!! | Please enter the |
password!!
4. Self-inspection 8. Return| Enter Log out| Enter
Log out
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
The switch does not conduct any protection under the maintenance mode, the backlight of the screen flashes, and the power is still maintained in maintenance mode until you press the “return” or “logout return” to exit maintenance mode; after choosing “return” to exit, level 0 password is required for reentering the maintenance mode, while after choosing “logout return”, the password shall be entered for reentering.
Capacity
1. Maintenance 5. Mechanical test | Capacity query | Maintenance mode |
---|---|---|
2. Capacity 6. Password reset | System: 0000/1963 No | Over-limit: 0000/0010 No |
3.Trial trip 7. Logout return | Trip: 0000/0010 No | Alarm: 0000/0010 No |
4. Self-inspection 8. Return | Self-inspection: 0000/0010 No | Clear all data: |
No
- [Up/Down] button to control the highlighted display position or adjust parameters. [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Self-inspection
1. Maintenance 5. Mechanical test | Self-inspection result: successful | |
---|---|---|
2. Capacity 6. Password reset | Under self-inspection… | Self-inspection mode: |
button
3.Trial trip 7. Logout return| Please wait…| Date: December 10, 2013
4. Self-inspection 8. Return| | 01 time: 12:11:11
Mechanical test
1. Maintenance 5. Mechanical test| Successful opening: 000000 times|
Mechanical test
---|---|---
2. Capacity 6. Password reset| Unsuccessful opening: 000000 times| Closing
countdown: 101s
3.Trial trip 7. Logout return| Successful opening: 000000 times| Opening
countdown: 101s
4. Self-inspection 8. Return| Unsuccessful opening: 000000 times| Opening
standby
As shown above.
- [Up/down] button to adjust the countdown parameters.
- [Setting] button to switch setting options.
- [OK] button to check operation times.
- [Return] button to return to the previous menu.
In the mechanical test mode, press the button to exit the mechanical test mode, in which the up and down buttons are to check the number of tests, and the countdown will be automatically displayed when the buttons are not operated beyond the return time.
Password reset
1. Maintenance 5. Mechanical test| —–Level 0 password—-|
---|---|---
2. Capacity 6. Password reset| –Please enter the password!!–|
3.Trial trip 7. Logout return| 0000|
4. Self-inspection 8. Return| ———————————-|
As shown above.
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return ] button to return to the previous menu. Level 0 password is required to reset the password, and when it is correct, it will automatically return to maintenance menu
Logoff return
1. Maintenance 5. Mechanical test
2. Capacity 6. Password reset
3.Trial trip 7. Logout return
4. Self-inspection 8. Return
- [Up/Down] button to control the highlighted display position or adjust parameters.
- [OK] button to enter the corresponding setting menu/switch setting options.
- [Return] button to return to the previous menu.
Password is required for reentering after logoff return
Operation of digital tube products
The circuit breaker is provided with the switch-on trail power function (which can be turned off), which can effectively prevent the safety of the follow-up equipment. See the setting code table for specific operation.
Test run of products
After the connection is finished, the circuit breaker will be electrified
after being checked to be free of errors. The circuit breaker is in segment
status, and the parameters are set according to the operation instructions.
After the setting is completed, the closing operation is performed. During the
closing, the closing indicator light flashes, which is always on after the
closing is completed.
In the closing state, press [trial trip] key for residual current trial trip,
in which reclosing can be repeated within 20s to 60s.
Closing operation of circuit breaker
-
Automatic closing
Long press the [close] key for 2 seconds. The closing indicator light flashes, which is always on after the closing, and when the closing and opening indication is “close”, the circuit breaker enters the normal operation status. -
Manual closing
Insert the manual wrench mentioned in the annex in the hole and turn clockwise about 360°. After the closing is successful, the closing indicator light is always on, the closing indication is “closed” and the circuit breaker enters the normal operation status.
Note: when the main contact of the circuit breaker is disconnected, the manual closing can be carried out. See mode 2 above for closing operation. Pay attention to the safety of the load equipment and personnel during manual closing.
Disconnection operation of circuit breaker
- Under the operation state, press the [open] key. After the opening is successful, the closing indicator lights are off and the closing and opening indications are “open”.
- If manual opening is required, insert a wrench into the hole and turn it clockwise 180 °. After the opening is successful, the opening and closing indications are “open” and the closing indicator light is off.
Operation instructions of digital tube
Menu description of digital tube
The menu is displayed in the way of [real-time display], [parameter setting],
[fault display] and [fault query] with panel indicator light. The display
panel is as follows:
Setting menu | Unit | Setting menu | Unit | Setting menu | Unit |
---|---|---|---|---|---|
S-01 | Overvoltage | V | s-11 | Actuation time | ms |
s-02 | Overvoltage alarm | s-12 | Leakage alarm | ||
s-03 | Overvoltage trip | s-13 | Ir1 setting | A | |
s-04 | Under-voltage value | V | s-14 | Ir1 actuation time | a |
s-05 | Under-voltage alarm | s-15 | Ir2 setting | x1R1 | |
s-06 | Under-voltage trip | s-16 | Ir2 actuation time | ms | |
s-07 | Phase default value | s-17 | Ir3 setting | x1R1 | |
s-08 | Phase default alarm | s-18 | Power close | ||
s-09 | Phase default trip | s-19 | Power-off close | ||
alarm | |||||
s-10 | Leakage value | mA | s-20 | Communication type |
Fault display | Real-time display | Unit | Real-time display | Unit |
---|---|---|---|---|
F-02 | Leakage | F-07 | Phase default | F-13 |
voltage
| V| L-B| Phase B
current
| A
F-04| Zero default| F-08| Under-voltage| F-14| Simulation| U-B| Phase B
voltage
| V| L-C| Phase C
current
| A
F-05
|
Overload
|
F-09
|
Overvoltage
|
F-15
|
Blocking
|
U-C
| Phase C voltage|
V
|
L-D
| Real-time leakage current|
mA
F-06| Short
circuit
| F-12| Test| F-18| Manual| L-A| Phase A
current
| A| L-L| Rated leakage
current
| mA
- Indicator light description
- Set (indicator light): after entering the setting menu, this light is on automatically, otherwise it will be in off status.
- Query (indicator light): after entering the query menu, this light is on automatically, otherwise it will be in off status.
- Alarm (indicator light): when there is alarm information, this light is on automatically, otherwise it will be in off status.
- Fault (indicator light): when this product trips due to faults, this light is on automatically, otherwise it will be in off status.
- Automatic (indicator light): when the leakage is set as automatic mode, this light is on automatically, otherwise it will be in off status.
- Communication (indicator light): when communicating with the external equipment, this light is on automatically, otherwise it will be in off status.
- Close (indicator light): when this product is in automatic closing, this light flashes, and is always on after closing, otherwise it will be in off status.
- Block (indicator light): when the product is in closing status, this light is on automatically, otherwise it will be in off status.
Real-time display
- [Real-time display] is displayed in the way of switching display between the code and the real time value, and the display unit has been marked on the panel.
- Press [up]/[down] button for switching display contents.
- Press [set] button to enter [parameter setting] menu.
- Press [OK] button to enter [fault query] menu.
Parameter setting
- [Parameter setting] is displayed in the way of switching display between the set code and the set value, and the display unit has been marked on the panel.
- [Parameter setting] defaults to the query mode, and at this time, the set code is displayed with the set value.
- Press [up]/[down] button for switching display contents. When setting is required, press [OK] button to enter the setting mode, but at this time, only the set value is displayed, so press [up]/[down] button for
- parameter adjustment. Press [OK] button to save the set parameters, and return to query mode.
- The 4-digit operation password shall be entered for setting the parameters the first time, and the digital tube displays when the password is entered. At this time, press [OK] button to enter the password entering status, press [up]/[down] button for adjusting the password entering values and press [set] button to select the password. If the password is wrong, reenter.
Query mode
- Press [up]/[down] button for switching the setting options
- Press [OK] button to enter the setting mode, in which the operation password shall be entered for setting the first time, and press [return] button to return to [real-time display] menu.
Setting mode
- Press [up]/[down] button to adjust and set the parameters
- Press [OK] button to save the set parameters, exit the setting mode and return to query mode Press [set] button to operate the parameter shift.
- Press [return] button to return to [real-time display] menu.
- 12.6 Fault display
- [Fault display] is displayed in the way of fault code which has been marked on the panel.
Fault query
- [Fault query] is displayed in the way of fault code and fault index, in which the fault code has been marked on the panel.
- Press [up]/[down] button to query the fault record before and after
- Press [OK] to return to [real-time display] menu.
- Press [return] button to return to [real-time display] menu.
Appearance and installation dimensions
Appearance and installation dimension diagram
Match of cross-sectional area and the rated current of connecting wire
Cross-sectional area with rated current not greater than 400A but matched with the connecting wire
Rated
current (A)
| 16 and 20| 25| 32| 40 and
50
| 63| 80| 100| 125 and
140
| 160
---|---|---|---|---|---|---|---|---|---
Sectional
area of wire (mm2)
| 2.5| 4.0| 6.0| 10| 16| 25| 35| 50| 70
Rated
current (A)
| 180, 200
and 225
| 250| 315 and
350
| 400|
Sectional
area of wire (mm2)
| 95| 120| 185| 240
Cross-sectional area with rated current greater than 400A but matched with the connecting wire
Rated current A
| Cable| Copper bar
---|---|---
Cross-sectional
area m2
| Quantity| Dimension
mmxmm
| Quantity
500| 150| 2| 30 X5| 2
630| 185| 2| 40X5| 2
Transportation and storage
Transportation
Prevent the invasion and mixed loading of water, rain, snow or other harmful
liquids such as chemical solvents, corrosive liquids during the transportation
of products; prevent the strong impact and extrusion between objects; stack
according to the direction given on the packaging. See the outer box
identification for the number of layers.
Storage
- Environment conditions for storage: environment temperature -10℃ – +45℃;
- Relative humidity≤90% (when the environment temperature is + 20℃);
- The storage place shall be free of dust and conductive dust;
- There shall be free of corrosive, flammable and explosive gases and free of rain and snow invasion;
- Dry and ventilated;
- Stack according to the direction given on the package and do not stack higher than that identified on the outer box.
Precautions
- After the products are normally put into operation, they shall be tested once a month and the test record shall be done.
- The Company does not assume “three guarantees” responsibility for the non-quality problems caused by improper installation and use and the burnt wiring terminals due to improper wiring
- If there is a problem in the use of the products, please contact the local dealer or the customer service center of the Company.
Customer service hotline
Please keep this instruction properly.
CERTIFICATE OF CONFORMITY
- Name: Residual current protection circuit breaker
- Examined by: Examiner 5
The products shall conform to GB14048. 2 standard. After passing the inspection, they shall be allowed to leave the factory.
QR SCAN
NATIONAL SALES CENTRE: 010 202 3400 | TECHNICAL CENTRE: 010 202 3500
HEAD OFFICE – LONGMEADOW – 010 202 3300 – 26 Nguni Drive, Longmeadow Estate
West, Edenvale, Gauteng
Germiston 011 418 9600 | Richmond Park 021 492 2000 | Riverhorse 031 492 4800
| Pinetown 031 700 4215
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>