Danfoss OP-MPS Optyma Plus Condensing Units Instructions

October 30, 2023
Danfoss

ENGINEERING TOMROWDanfoss OP-MPS Optyma Plus Condensing Units -
icon

Optyma™ Plus
OP-MPS, OP-MPT, OP-LPV, OP-LPK and OP- MPIwww.danfoss.comDanfoss OP-MPS Optyma Plus
Condensing Units - icon

 OP-MPS Optyma Plus Condensing Units

Optyma™ Plus electrical box ingress protection level is IP54 to avoid quick A2L refrigerant migration. Sealing needs to be maintained and any damage on sealing needs to be repaired appropriately. (See section 8 – Safety)
E-Box door must always be closed during operation and after service/periodic maintenance.
Installation and servicing of the condensing units by qualified personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.
The condensing unit must only be used for its designed purpose(s) and within its scope of application and according to instruction. Refrigerant to be used as per specification with respect to model.
Under all circumstances, the EN378 and other applicable local safety regulation requirements must be fulfilled.
The condensing unit is delivered under nitrogen gas pressure (2 bar(gauge)) and hence it cannot be connected as it is; refer to the «installation» section for further details.
The condensing unit must be handled with caution in the vertical position (maximum offset from the vertical : 15°) Condensing units can be used with A2L refrigerants, necessary care to be taken during installation and servicing.
In case of A2L refrigerants, all components on the refrigeration circuit must be A2L certified. Example:
Evaporator and Expansion Valve.
For PED Cat I models:
Pressure relief valve shall be mounted in refrigerant system during field installation.
PRV should be mounted on receiver vessel.
For PED Cat II models: Pressure Pressure relief valve is factory fitted with Condensing unit on liquid receiver with 34.5 ± 1 bar pressure setting. (See section 3.1 – PRV valve) Operation of Receiver Rotolock valve should be operated by trained/skilled professional operator. Make sure all rotolock valves are open during CU operation.
Relevant Standards and Directive
EN 378-2:2016: Refrigerating Systems And Heat Pumps-Safety And Environmental Requirements.
EN 60335-1: Household And Similar Electrical Appliances – Safety –Part 1: General Requirements
EN IEC 61000-6-8:202: Electromagnetic compatibility (EMC) Part 6-8: Generic standards
EN 60335-2-40 : Household and similar electrical appliances
EN 60335-2-80 : Household and similar electrical appliances
Low Voltage Directive 2014 / 35 / UE
Machinary Directive 2006 / 42 / CE
Pressure Equipment Directive (PED) no. 2014/68/EU
RoHS Directive 2011/65/EU
WEEE Directive 2012/19/EU
(Other local applicable standards)

Introduction

These instructions pertain to Optyma™ Plus condensing units OP-MPS, OP-MPT, OP-LPV, OPLPK and OP-MPI used for refrigeration systems. They provide necessary information regarding safety and proper usage of this product.
The condensing unit includes following:

  • Microchannel heat exchanger
  • Reciprocating or scroll compressor
  • Receiver with stop valve
  • Ball valves with schrader Valve
  • Sight glass (Flare connections)
  • Suction and Discharge Pressure transducers (Schrader valve mounted)
  • High & low pressure switches
  • Filter drier (Flare connections)
  • Electronic controller
  • Main circuit breaker (Main switch with overload protection)
  • Fan and compressor capacitors
  • Compressor contactor
  • Robust weather proof housing
  • IP54 Fully pre-wired electrical panel
  • AC Fan motor for H1 & H2 Models
  • EC Fan motor for H3 & H4 models
  • PRV is fitted in PED Cat II models (Technical data sheet – Annex – A)
  • Components connected are equipped with Schrader port
  • Liquid injection controller (Module B Plus)*
  • Electronic expansion valve (ETS6) for Liquid injection*
  • Only for P02 version models

Handling and storage

  • Do not braze as long as the condensing unit is under pressure.
  • A2L refrigerants are heavier then air, hence Danfoss recommend to install above ground level. Refer Annex – A
  • It is recommended not to open the packaging before the unit is at the final place of installation.
  • Handle the unit with care. The packaging allows for the use of a forklift or pallet jack. Use appropriate and safe lifting equipment.
  • Store and transport the unit in an upright position.
  • Store the unit between -35°C and 50°C.
  • Don’t expose the packaging to rain or corrosive atmosphere.
  • After unpacking, check that the unit is complete and undamaged.

Installation precautions

| Do not braze as long as the  condensing unit is under pressure.
---|---
Place the unit in such a way that it is not blocking or hindering walking areas, doors, windows or similar.
A2L refrigerants are heavier than air. Unit has to be installed above floor level to have a good compressor compartement ventilation.
| PRV: In PED Cat II models, PRV comes with installed. For PED Cat I models, PRV shall be mounted at field during installation.

  • Ensure adequate space around the unit for air circulation and to open doors. Refer to Annex – A for minimal values of distance to walls.
  • Avoid installing the unit in locations which are daily exposed to direct sunshine for longer periods.
  • Avoid installing the unit in aggressive and dusty environments.
  • Ensure a foundation with horizontal surface (less than 3° slope), strong and stable enough to carry the entire unit weight and to eliminate vibrations (use grommets, pads or support) and interference.
  • The unit ambient temperature may not exceed 63°C during off-cycle.
  • Ensure that the power supply corresponds to the unit characteristics (see nameplate).
  • When installing units for R454C, R455A and R1234yf refrigerants, use equipment specifically reserved for A2L refrigerant which was never used for other HFO, CFC or HCFC refrigerants.
  • Use clean and dehydrated refrigeration-grade Copper / Aluminium tubes with appropriate thickness and silver alloy brazing material.
  • Use clean and dehydrated system components.
  • The suction piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations. Furthermore piping has to be done in such a way that oil return for the compressor is ensured and the risk of liquid slug over in compressor is eliminated.
  • In Optyma condensing unit has suction and liquid service valve with schrader port for field service operation
  • Optyma Plus unit codes 114X34– and 114X44– have two inline receivers with valves. Make sure both the valves are open before starting.

3.1 – PRV Valve

| For Optyma™ Plus, Condensing units which are fall in PED cat II, PRV is factory fitted with 34.5 ±1 bar presetting. (See Technical data for PED category in Annex A).
---|---
For Optyma™ Plus, Condensing units which are fall in PED cat I, PRV shall be fitted (See Technical data for PED category in Annex A).
PRV is used as damage limiting device, not as pressure limiting device.

  • PRV to be fitted on liquid receiver at 3/8″ NPT Connection. (Refer Coolselector2 for PRV spare part code). Use Locatite 554 for PRV fitment.

  • Torque: 40Nm (Don’t exceed given torque )
    Danfoss OP-MPS Optyma Plus Condensing Units - fig 1

  • Installer need to take care of where to blow the leaked refrigerant. Danfoss recommended to blow refrigerant away from condensing unit.

  • Recommended to change PRV when after discharge, Changing refrigerant

  • Don’t remove the seal and attempt to reset the valve.

  • Valves must be installed vertically or Horizontally, but ensure PRV to be fitted above system’s liquid level.

  • Ensure refrigerant is released safely to the atmosphere directly.

  • Incase of hazard, an additional spare kit has been designed in order to collect the released refrigerant. Kit should be installation with proper piping routing for discharge of refrigerant safely. (See picture below)
    Danfoss OP-MPS Optyma Plus Condensing Units - picture
1

  • PRV should not be installed on service valve.

  • Replace PRV after clean out of system or bared out.

  • No Detachable joints and valves should not accessible to public. All brazing joints should comply with EN 14276-2 and other permanent joints should comply with EN-16084.

  • Optyma Plus unit codes 114X34– and 114X44– have a PRV assembled at one of receiver. In other receiver, a blind plug is installed.

  1. HP Pressure Transmitter
  2. Pressure Relief Valve
  3. ACB Pressure Switch
  4. Gas Equalization Port
  5. Liquid Equalization Port

Installation

Installation/servicing of Optyma™ Plus condensing units must be carried out by qualified personnel with respect to applicable local/international regulation and with the correct user Personal Protective Equipment (PPE).

  • The installation in which the condensing unit is installed must comply to pressure Equipment Directive (PED) 2014/68/EU. The condensing unit
  • itself is not a ”unit” in the scope of this directive.
  • The unit must be securely installed on a stable and rigid support. Refer Annex – A.
  • It is recommended to install the unit on rubber grommets or vibration dampers (not supplied).
  • It is possible to stack units on top of each other.
Unit Maximum stacking

Housing 1
(Code no. 114X31– or 114X41–)| 3
Housing 2
(Code no. 114X32– or 114X42–)| 2
Housing 3
(Code no. 114X33– or 114×43–)| 2
Housing 4
(Code no. 114X34– or 114×44–)| 2

  • When stacking, the topmost unit must be secured to the wall, as shown in picture 2.
  • Slowly release the nitrogen holding charge through the schrader port.
  • Connect the unit to the system as soon as possible to avoid oil contamination from ambient moisture.
  • Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
  • Braze with great care using state-of-the-art technique and vent piping with nitrogen gas flow.
  • Connect the required safety and control devices. When the schrader port is used for this, remove the dummy cap.
  • It is recommended to insulate the suction pipe from evaporator up to the compressor inlet with 19 mm thick insulation.
  • Make sure there is no refrigerant or damage inside unit and crack in pipes.
  • Make sure that all components inside electrical box are protected against electrical overload and “not source of ignition” from its respective manufacturer for approved refrigerants.
  • Field wiring must be routed through IP65 cable glands and cable entry plate only. For any additional wire routing drilling or piercing electrical panel sides strictly prohibited.
  • For field wiring, only required hole to be pierced. No pierced hole should be left without cable in it.

If undesired/unwanted piercing happens entire gland plate should be replaced.
118U5258 – Spare part, cable gland

Danfoss OP-MPS Optyma Plus Condensing Units - picture
3

• Partition panel and base plate has dedicated openings for pre ventilation, do not seal / obstruct / close the openings in any manner.Danfoss OP-MPS
Optyma Plus Condensing Units - picture 4

  • In the event of uncertain leakages, to avoid refrigerant concentration in compressor compartment, Fan starts before compressor with ON time delay of 30 seconds for compressors.
  • Copper piping material should comply with EN12735-1. And all pipe joints should comply with EN14276-2
  • At filed installation, support to added according to size and weight. Recommended maximum spacing for pipe support as per EN12735-1 & EN12735-2
  • Connecting pipes shall be made before opening the valves to permit refrigerant to flow between the refrigerating system parts.

Leak detection

Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.

  • Do not use dye for leak detection.
  • Perform a leak detection test on the complete system.
  • The maximum test pressure is 25 bar.
  • When a leak is discovered, repair the leak and repeat the leak detection.

Vacuum dehydration

  • Never use the compressor to evacuate the system.
  • Connect a vacuum pump to both the LP & HP sides for quicker and efficient evacuation.
  • Vacuum pump must be certified to use in A2L refrigerant environment or ATEX certified
  • Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) absolute.
  • Do not use a megohmmeter or apply power to the compressor while it is under vacuum as this may cause internal damage.

Electrical connections

  • Verify that all electrical connections inside the condensing unit are properly fastened as they could have worked loose during transportation.
  • Switch off and isolate the main power supply.
  • Ensure that power supply can not be switched on during installation.
  • All electrical components must be selected per EN60335-1, EN60204 or local applicable standard and unit requirement.
  • Refer to wiring diagram for electrical connections details.
  • All electrical components must be qualified to use A2L refrigerants and “not source of ignition”.
  • Ensure that the power supply corresponds to the unit characteristics and that the power supply is stable (Allowable voltage tolerance ±10% and Allowable frequency tolerance ±2,5 Hz).
  • The power supply cables must be according to unit data for voltage, current and ambient condition. Refer Nameplate for voltage and current information.
  • Protect the power supply cable and ensure correct earthing.
  • Make the power supply according to local standards and legal requirements.
  • The unit is equipped with an electronic controller. Refer to Manual 118U3808 for details.
  • The unit is equipped with a main switch with overload protection and short circuit protection. The overload protection is factory preset but it is recommended to check the value before taking the unit in operation. The value for the overload protection can be found in the wiring diagram in the front door of the unit.
  • The unit is equipped with high and low pressure switches, which directly cuts the power supply to the compressor in case of activation. Parameters for high and low pressure cut outs are preset in the controller, adapted to the compressor installed in the unit.
  • P02 version models (OP-xxxxxxxxxP02E) are equipped with Electronic circuit board to operate the Liquid injection Electronic Expansion Valve (Module B Plus). Refer to section “Module B Plus User Guide” of this manual.
  • Optyma™ Plus condensing unit starting frequency need to be limited for reciprocating compressors.
    – Without starting capacitor 5 starts per hour maximum.
    – With starting capacitor 10 starts per hour maximum.

Safety

| Electrical box door should be in closed condition before connecting to power supply.
---|---
| Discharge tube temperature will go upto 120°C during unit running condition.
| Recommended to install PRV inside unit and release of refrigerant should routed to atmosphere directly.
| Optyma plus unit codes 114X34– and 114X44–, High pressure switch fitted after receiver, If the Rotolock valves are closed during the pump down cycle, the HP switch will not trip.

Unit has liquid receiver with an Adapter Plug with 3/8” NPT connection. Installer/end user can select various options as mentioned in EN378-2 : 2016 Article § 6.2.2.3

  • The unit/installation into which the condensing unit is mounted/integrated, must be in accordance with the PED.
  • Beware of extremely hot and cold components.
  • Beware of moving components. Power supply should be disconnected while servicing.
  • As per EU F-gas regulation, R1234yf, R454C & R455A are considered as A2L refrigerant.

Optyma™ Plus units are qualified with R1234yf, R454C & R455A. All precaution and safety measure to be taken care before and after installation.

  • All components should be compatible to use with specified refrigerants according to Optyma™ Plus condensing units codes. Refer Annex A In order to avoid electric arc between hermetic connector pins, compressor must not start or electrical tests such as dielectric strength must not be performed while the refrigerating system is under vacuum.
  • Optyma™ Plus condensing units have pre ventilation via condenser fan prior to compressor starting (30 seconds).
  • Danfoss always recommend to main IP54 electrical box. In case of any damage to rubber gasket (shown below), customer should replace immediately.
  • Compressor has Internal overload protector (OLP). Its will protect compressor pressure going beyond 32 bar pressure.

No valves and detachable joints shall be located in areas accessible to the general public except when they comply with EN 16084

  • Refrigerant piping shall be protected or enclosed to avoid damage.
  • Field piping should be installed such that it will be free from corrosive or salty environment to avoid corrosion in copper /Aluminum piping.
  • In case of fire incidence, pressure increases due to increasing in temperature at receiver. Hence it is very important to install the PRV.
  • For codes 114X34– and 114X44–, Door limiting switch provided for safety purpose. Don’t remove or change the connection.

Filling the system

  • Never start the compressor under vacuum. Keep the compressor switched off.

  • Use only the refrigerant for which the unit is designed for.

  • Before filling the refrigerant into the Optyma™ Plus condensing unit wear appropriate PPEs(Personal Protective Equipments).

  • If additional oil is required please refer to the compressors label for type of oil. Check the Compressor application guideline for minimum oil level limit before refilling.

  • For glide refrigerants such as R454C, R455A, R448A, R449A, R452A use liquid valve in the refrigerant cylinder to charge.

  • Fill the refrigerant in liquid phase into the condenser or liquid receiver. Ensure a slow charging of the system to 4 – 5 bar for R404A/ R507,R407A,R407F,R448A/R449A,R452A, R454C, R455A and approx. 2 bar for R134a, R513A & R1234yf.

  • The remaining charge is done until the installation has reached a level of stable nominal
    condition during operation.

  • Never leave the filling cylinder connected to the circuit.

  • Do not put liquid refrigerant through suction line.

  • It is not allowed to mix additives with the oil and/ or refrigerant.

  • When charging A2L refrigerant make sure that the charging area is well ventilated The Liquid receiver is fitted with Rotolock Valve for service purpose. As a factory setting, the valve will be in completely OPEN position. During maintenance and Pump down, the Valve must be Rotated in Clockwise direction until it is in completely CLOSED position.

  • Suction, Liquid valves and Receiver Rotolock valves as Schrader port for service operation like Gas Charging, pressure measurement.

Setting the electronic controller

| Change controller parameter o37 to 1 in case of SPPR (Supply monitoring relay) retrofit. In case you add the SPPR option to protect the compressor please change the setting o37 from 0 to 1
---|---
For P02 version models (OP xxxxxxxxxP02E), the o30 values are only 19= R404A / 40=R448A / 41=R449A / 51= R454C / 52 = R455A in controller
Fluid Group| Refrigerant| Parameter (o61 *)
---|---|---
A2L| R4S5A & R454C| LLZ013 , LLZ015,
LLZ018, LLZ024 &
LLZ034 = 19
MLZOS8 &
MLZ076 = 18
LLZ013 = 43
LLZO1S = 44
Al| R404A/R507,
R452A, R448A &| LLZ018 = 45
LLZ024 = 39
LLZ034 = 40
MLZOS8 = 37
MLZ076 = 38

  • Refer Optyma™ plus controller installation – User manual (BC08728642552802)

    • The unit is equipped with an electronic controller which is factory programmed with parameters for use with the actual unit. Refer to Manual 118U3808 for details.
    • By default, the electronic controller display shows the temperature value for the suction pressure in °C. To show the temperature value for the condensing pressure, push the lower button Annex A; Picture 3.
    • Remove controller terminal DI1 (room thermostat input) to avoid any unwanted compressor start. Put it back after settings been done.

The electronic controller is factory preset for R404A / R449A / R452A / R134a / R454C / R1234yf depending on the model of compressor mounted and application (Refer Optyma™ Controller installation manual 118U3808). If another refrigerant is used, the refrigerant setting must be changed.

  • Push the upper button for a couple of seconds. The column with parameter codes appears.
  • Parameter r12 must be set to 0 before (software main switch= off).
  • Push the upper or lower button to find parameter code o30.
  • Push the middle button until the value for this parameter is shown.
  • Push the upper or lower button to select the new value: 3 = R134a.17 = R507. 19 = R404A. 20 = R407C. 21 = R407A. 36 = R513A. 37 = R407F. 40 = R448A. 41 = R449A. 42 = R452A. 39 = R1234yf. 51 = R454C. 52 = R455A
  • Push the middle button to confirm the selected value.
  • Push the upper or lower button to find parame ter code r84 (r84 = Maximum allowable discharge temperature).
  • Push the middle button, default maximum discharge temperature is 125°C
  • If customer want to increase the valve, push the upper button to select the new value: 130°C. Push middle button to confirm the selected  value.
  • Maximum allowable discharge temperature (r84) should not exceed 130 °C

The Optyma Plus 114X33YY and 114X43YY units is equipped with EC Fan motor. Optyma Plus controller parameter F17 is modified to 2 for this, to activate the 0-10V fan speed control output. As a factory setting, the max. fan speed parameter F19 is set to 80%, to limit fan speed and noise emissions in residential areas. Installers can increase this max. speed up to 100%, if the emitted noise is not a constraint. Only for P02 version models, the Digital input, DI2 from the controller will be connected to the Module B+. This will indicate the Alarm, that stops the Compressor running in case of Module B+ failure. The Controller Parameter must o37 must be set to 1.
The speed variation of the EC fan motor will be controlled by the Optyma Plus controller, by measuring the difference between the Ambient Temperature and Saturated Condensing Temperature (Dew). Lesser the difference, higher the speed. The default factory  set will be 8K. The adjustable range will be 2-20 K. To adjust, from the home screen of the Optyma controller (showing saturated suction Temperature), press the middle button and vary the value with upper or lower key.

Verification before commissioning

| Use safety devices such as safety pressure switch and mechanical relief valve (not supplied) in compliance with both generally and
locally applicable regulations and safety standards. Ensure that they are operational and properly set.
---|---
Check that the settings of highpressure switches and relief valves don’t exceed the maximum service pressure of any system component.

  • Before starting condensing unit ensure receiver valves and ball valve are completely open.
  • Verify that all electrical connections inside the condensing unit are properly fastened as they could have worked loose during transportation.
  • When a crankcase heater is required, the unit must be energized at least 12 hours before initial start-up and start-up after prolonged shutdown for belt type crankcase heaters.
  • Crankcase heater must be firmly fixed with compressor shell. Ensure that it does not fall down and energizes in air.
  • Electrical panel door must be firmly closed using the knob in door panel.
  • All interconnecting tubes with (liquid and suction) Optyma™ Plus condensing unit must be sized properly depending upon the evaporator location.
  • Pressure drop in the suction and liquid line pipes must be evaluated as per evaporator location and distance (refer coolselector2).
  • Optyma™ Plus condensing units suction / discharge pressure must be within the operating envelope, never operate condensing unit suction pressure below absolute pressure (vacuum).
  • The unit is equipped with a main switch with overload protection and short circuit protection. Overload protection is preset from factory, but it is recommended to check the value before taking the unit in operation. The overload protection value can be found in the wiring diagram in the unit front door.
  • Check if discharge temperature sensor is firm and has proper contact with discharge pipe.
  • Ensure that you have read the installation guideline that is delivered with the condensing unit
  • Only use the correct refrigerant(s) as detailed on the data plate
  • Check compressor oil level
  • Check that all service valves are open
  • Ensure the high pressure transmitter is open to the system
  • Check all mechanical connections are tight
  • Check all electrical overload settings are correct

Start-up

  • Never start the unit when no refrigerant is charged.
  • All service valves must be in the open position.
  • Rotalock valve on the receiver should be completely open. Turn anticlockwise direction to open completely open
  • Check compliance between unit and power supply.
  • Check that the crankcase heater is working.
  • Check that the fan can rotate freely.
  • Check that the protection sheet has been removed from the backside of condenser.
  • Balance the HP/LP pressure.
  • Energize the unit. Condenser fan must start promptly and after 30 seconds of time delay the compressor starts (pre ventilation).
  • Eventual reverse rotation of a 3-phase compressor can be detected by following phenomena; the compressor doesn’t build up pressure, it has abnormally high sound level and abnormally low power consumption. In such case, shut down the unit immediately and connect the phases to their proper terminals.
  • If the rotation direction is correct the low pressure indication on the controller (or low pressure gauge) shall show a declining pressure and the high pressure indication (or high pressure gauge) shall show an increasing pressure (only during startup).

Check with running unit

  • Check the fan rotation direction. Air must flow from the condenser towards the fan.
  • Check current drawn and voltage.
  • Check suction superheat to reduce risk of slugging.
  • When a compressor sight glass is provided observe the oil level at start and during operation to confirm that the oil level remains visible.
  • Respect the operating limits.
  • Optyma™ Plus condensing units are designed to operate upto 43 degree Celsius. During normal operation or peak operation saturated dew point condensing temperature not to exceed corresponding to 63 deg Celsius for R404A/ R507, R448A, R449A, R452A, R454C, R455A. Saturated dew point condensing temperature not to exceed corresponding to 65 deg Celsius for R134a, R513A & R1234yf.
  • Check all tubes for abnormal vibration. Movements in excess of 0.15 mm require corrective measures such as tube brackets.
  • When needed, additional refrigerant in liquid phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this process.
  • Do not overcharge the system.
  • Follow the local regulations for restoring the refrigerant from unit.
  • Never release refrigerant to atmosphere.
  • Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise and leak detection.
  • Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.
  • Check suction & discharge pressure and temperature.
  • Check refrigerant charge and running currents of motors to ensure correct operation .
  • Check compressor suction superheat to reduce risk of liquid slugging.
  • Allow the system to run for 3 – 4 hours. Check compressor oil level and top up with the correct oil type as identified on the data plate of the unit and compressor.
  • Recheck the compressor oil level again after 24 hours operation.
  • Carry out final leak test and ensure all covers are fitted and all screws are fastened.
  • Complete refrigerant labelling to comply with local standard
  • Scroll Compressors are allowed to Operate at maximum of 12 Start/Stop cycles per hour.
  • Reciprocating Compressors are allowed to Operate at maximum of 10 Start/Stop cycles per hour.
  • Ensure maintenance is carried out in accordance with the installation instructions.

Emergency running without controller

In case of controller failure, the condensing unit can still be operated when the controller standard wiring is modified into a temporary wiring as described below.

| This modification may be done by authorized electricians only. Country legislations have to be followed.
---|---
Disconnect the condensing unit from power supply (turn hardware main switch off)
The controller must be exchanged as soon as possible to avoid any lifetime reduction.

  • Contact of room thermostat at 24 – 25(i.e. DI1) must be possible to switch 250VAC.
  • Remove wire 22 (safety input DI3) and wire 24 (room thermostat DI1) and put them together with an insulated 250 Vac 10mm² terminal bridge.
  • Remove wire 25 (room thermostat DI1) and wire 11 (compressor supply) and put them together with an insulated 250VAC 10mm² terminal bridge.
  • Remove wire 6 and connect it with terminal bridge for wire 11 and 25. A fan pressure switch or fan speed controller can be connected in series to wire 6.
  • Remove wire 14 (crankcase heater) and connect it to the compressor contactor terminal 22.
  • Remove wire 12 (supply crankcase heater), extend this wire by using an 250 Vac 10mm² terminal bridge and 1,0mm² brown cable and connect it to compressor contactor terminal 21.
  • Remove the large terminal block from the controller terminals 10 to 19.
  • Connect the condensing unit to power supply (turn hardware main switch on).
  • For 114X33YY and 114X43YY unit with EC Fan motor, Open the fan motor terminal box and connect the 0-10V fan speed input to the 10V supply terminal

Maintenance

| Always switch off the power supply to the condensing unit by turning off the main switch before opening the fan panel
---|---
Internal pressure and surface temperature are dangerous and may cause permanent injury.
Maintenance operators and installers require appropriate PPEs, skills, tools to carryout the maintenance activity. Tubing temperature may exceed 100°C and can cause severe burns.
Ensure that periodic service inspections are performed to the system reliability and as required by local regulations are performed.

To prevent system related problems, following periodic maintenance is recommended:

  • Verify that safety devices are operational and properly set.
  • Ensure that the system is leak tight.
  • Check the compressor current drawn.
  • Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
  • Check that all electrical connections are still adequately fastened.
  • Keep the unit clean and verify the absence of rust and oxidation on the unit components, tubes and electrical connections.
  • Micro channel heat exchanger surface adequately cleaned to avoid clogging.

The condenser must be checked at least once a year for clogging and be cleaned if deemed necessary. Access to the internal side of the condenser takes place through the fan door. Microchannel coils tend to accumulate dirt on the surface rather than inside, which makes them easier to clean than fin&-tube coils.

  • Switch off the power supply to the condensing unit by turning off the main switch before opening the fan panel.
  • All electrical equipments, PPEs, tool must be compatible and approved to use with A2L refrigerants like R454C, R455A & R1234yf.
  • Remove surface dirt, leaves, fibres, etc. with a vacuum cleaner, equipped with a brush or other soft attachment. Alternatively, blow compressed air through the coil from the inside out, and brush with a soft bristle. Do not use a wire brush. Do not impact or scrape the coil with the vacuum tube or air nozzle.
  • Check if openings in partition panel and base plate are free for pre-ventilation.
  • Before closing the fan door, turn the fan blade in a safe position, to avoid that the door hits the fan.

If the refrigerant system has been opened, the system has to be flushed with dry air or nitrogen to remove moisture and a new filter drier has to be installed. If evacuation of refrigerant has to be done, it shall be done in such a way that no refrigerant can escape to the environment.Danfoss OP-MPS
Optyma Plus Condensing Units - picture 6

  1. Valve inlet
  2. Valve outlet
  3. HP switch (Schrader port)
  4. Service port

• Valve Fully Closed (Valve spindle entirely turned clockwise)
– 1,3 and 4 Connected
– 2 has not connection to other ports
• Valve opened some turns (valve spindle somwher between open & close)
– 1,2, 3 and 4 Connected
– Valve Fully Opened (Valve spindle entirely turned anti clockwise)
– 1,2 and 3 Connected
– 4 has no connection to other ports

Spindle completely closed
Danfoss OP-MPS Optyma Plus Condensing Units - picture
7Spindle completely openedDanfoss OP-MPS
Optyma Plus Condensing Units - picture 8

Declaration of incorporation

Pressure Equipment Directive 2014/68/EU
EN 378-2:2016 – Refrigerating systems and Heat Pumps – Safety and environmental requirementsParts 2: Design, construction, testing, marking and documentation.
Low Voltage Directive 2014/35/EU EN 603351:2012 + A11:2014- Household and similar electrical appliances-Safety-Part 1: General requirements-for all below mentioned condensing units.
Eco-design DIRECTIVE 2009/125/ EC, establishing a framework for the setting of Ecodesign requirements for energy-related products.
REGULATION (EU) 2015/1095, implementing Ecodesign Directive 2009/125/EC with regard to Ecodesign requirements for professional refrigerated storage cabinets, blast cabinets, condensing units and process Chiller.
Condensing unit measurements are made according to standard “EN 13771-2:2017” – Compressor and condensing units for refrigerationperformance testing and test methods- part 2:
Condensing units. Eco design declaration; refer Danfoss Coolselector®2 with code number (114X….) to find the declaration.

Warranty

Always transmit the model number and serial number with any claim filed regarding this product. The product warranty may be invalied in following cases:

  • Absence of nameplate.
  • External modifications, in particular, drilling, welding, broken feet and shock marks.
  • Compressor opened or returned unsealed.
  • Rust, water or leak detection dye inside the compressor.
  • Use of a refrigerant or lubricant not approved by Danfoss.
  • Any deviation from recommended instructions pertaining to installation, application or maintenance.
  • Use in mobile applications.
  • Use in explosive atmospheric environment.
  • No model and serial number transmitted with the warranty claim.

Disposal

Danfoss recommends that condensing units and oil should be recycled by a suitable company at its site.

Module B Plus – User guide

Module B plus is an electronic circuit board used in P02 version models for automatic liquid injection into compressor scrolls set using an electronic expansion valve.Danfoss OP-MPS Optyma Plus Condensing Units - picture
9

Module B plus is covered by touch protection cover as Picture 6.
Do not remove touch protection cover unless required. Switch of the unit before removing this cover.Danfoss OP-MPS Optyma Plus Condensing Units -
picture 10

Application
Module B Plus controls liquid injection, and it also monitors the following parameters: Discharge gas temperature, phase sequence and phase failure.
Functional description
• Liquid injection
– Module B Plus can control discharge gas temperature. The default set point is 125 °C, this is required to run the condensing unit within safe envelope.
Do not change this set point.
– When compressor stops the liquid injection valve will be closed within 6 seconds.
• Discharge gas temperature overheat protection
– Discharge gas temperature sensor from Module B Plus can detect discharge gas temperature within the range -50 to 180°C, temperature measurement accuracy ±0.5°C. Discharge sensor is installed within 150mm from compressor discharge port.
– If the discharge gas temperature is higher than Overheat Trigger Point (set point + 10 K)within 1 second, alarm relay (J5) will open. This status is named as DGT Overheat Static referring to Table 1. If the discharge gas temperature lower than Reset Point (Set Point -15 °C) continuously for 5 minutes, the alarm relay (J5) will close. This 5 minutes delay status is named as DGT Reset Delay.
– If the discharge gas temperature overheat more than 5 times within 1 hour, alarm relay (J5) locks on open status and only can be reset by resetting Module B Plus power supply manually (switch-off the unit and switch-on again after some time). This status is named as DGT Overheat Lock, refer table 1 for error identification.
– If discharge gas temperature sensor is malfunction, i.e. Sensor Open, Sensor Short circuit or Out of Range, alarm relay (J5) locks on open status too, refer table 1 for error identification.
• Phase protection
– Phase sequence and missing phase detection will only be performed every time the compressor was powered on. If a wrong phase status Phase Loss or Phase Reverse detected, within 4.5s to 5s, alarm relay (J5) will open and lock on open status. This lock on  open status only can be reset by resetting Module B Plus power supply manually, refer table 1 for error identification.
• User interface
– Module B Plus powers on, power LED 1 will be solid red all the time. When the Module is powered off, power LED 1 will be off. If Module B Plus powers on and has no error, status LED 2 will be solid green on. Refer picture 6 for LED 1 and LED 2 location on module B plus.
– If Module B Plus powers on, and detects an error, status LED 2 will be yellow and red blinking one second alternately. Detail blink code see table 1.Danfoss OP-MPS Optyma Plus Condensing Units - picture
11

• Module B plus communication with Optyma™ Plus controller.
– When alarm relay (J5) is open, signal is communicated to Optyma controller digital input 2 (DI2), which enables safety alarm (A97) in Optyma™ plus controller and power supply to compressor will be stopped immediately.Danfoss OP-MPS Optyma Plus Condensing Units - picture
12

Category| Yellow Blink
Times| Red Blink
Times| Error| Description| Action
---|---|---|---|---|---
Discharge gas
temperature| 1| 1| DGT Overheat static/ DGT Reset Delay| Discharge gas temperature is higher than compressor stop trip point| Check if Optyma Controller shows safety alarm (A97). If yes, wait till it gets resolved automatically. If this error is observed frequently, check if unit is running in recommended envelope.
2| DGT Overheat Lock| DGT Overheat Static occurs
5 times within 1 hour| Reset Module B Plus supply manually (switch-off the unit and switch-on again after some time).
3| DGT out of range| DGT is out of normal range (-50 … 180°C)| Check if discharge gas temperature sensor is mounted properly on discharge line. Check discharge gas temperature on Optyma’ Plus controller parameter U27 (should be within -50 … 180°C).
4| DGT Sensor Open / DGT Sensor Short| Discharge gas temperature sensor open/short circuit| Check discharge temperature sensor and connection.
Triple Phase| 2| 1| Phase Loss| One phase signal loss| Check 3-Phase power supply (J2) to Module B Plus, if one of the 3 phases is missing. If yes, do correct power supply connection and reset Module B Plus manually (switch-off the unit and switch-on again after some time).
2| Phase Reverse| Incorrect phase connection| Check 3-Phase power supply (J2) to Module B Plus, if 3 phases are in correct sequence. If not, do correct power supply connection in sequence and reset Module B Plus manually (switch- off the unit and switch-on again after some time).

Table 1: Error Blink Code (LED 2 Yellow -Red Blink code)

Annex – A

Technical data
Name plateDanfoss OP-MPS Optyma Plus Condensing Units - Name
plate

  • For exact values please refer name plate in unit

A:Model
B:Code number
C: Serial Number and bar code
D: EAN number
E:Refrigerant
F:PED Category
G: Application, Ingress Protection
H: Maximum Allowable Pressure (HP side)
I: Maximum Allowable Pressure (LP side)
J: Test Pressure
K: Maximum allowable Design Temperature
L: Pressure Relief Valve set pressureDanfoss OP-MPS Optyma Plus Condensing
Units - Name plate 1

Picture 1 : Minimum mounting distances

Unit X [mm] Y [mm] W [mm]
Housing 1 (Code no. 114X31– or 114X41–) 250 550 460
Housing 2 (Code no. 114X32– or 114X42–) 250 650 530
Housing 3 (Code no. 114×33– or 114×43–) 250 760 580
Housing 4 (Code no. 114X34– or 114X44–) 250 700 700

Danfoss OP-MPS Optyma Plus Condensing Units - Name plate
2

T: Mounting brackets for stacked mounting (not supplied)
U: M8 bolts for stacked mounting (supplied)
V: Mounting bolts (not supplied)

Danfoss OP-MPS Optyma Plus Condensing Units - picture
13

Picture 3 : Electronic controller display
A: Up/Menu button
B: Select / Confirm
C: Down button

Compressor running|
---|---
Crankcase heater on|
Fan running|
Temperature value for suction pressure. Push lower button to switch to temperature value for condensing pressure|

Danfoss OP-MPS Optyma Plus Condensing Units - picture
14

Instructions
Designation system for the Optyma™ Plus range

Danfoss OP-MPS Optyma Plus Condensing Units - Designation
system

1| Application
M = MBP
L = LBP
---|---
2| Package
Condensing unit family: P = Plus
3| Refrigerant
T = R404A/R507,R455A,R454C,R448A/R449A,R452A
S = R134a, R513A, R1234yf
V = R454C, R455A, R452A, R404A/R507
I = R404A / R507, R134a, R407A, R407F, R448A, R513A, R449A, R452A, R454C, R455A
K = R448A, R449A, R404A, R452A, R455A, R454C
4| Condenser
M = Microchannel heat condenser
5| Swept volume
Displacement in cm3 : Example 034 = 34 cm3
6| Compressor platform
DP/DX/DS = Fixed speed Reciprocating compressor
ML/LL = Fixed speed Scroll Compressors
7| Version
P00: Optyma™ Plus (see Version table)
P02: Optyma™ Plus with Liquid injection (see version table)
8| Voltage code
G = 230V/1-phase compressor & fan
E = 400V/3-phase compressor & 230V/1-phase fan

Version control

OptymatM Plus (P00) (P02)
Condensing unit :IP level IPS4 IPS4
Refrigerant Group 1 / Group 2
Compressor technology Reciprocating / Scroll
Control box (pre-wired E-panel) Yes Yes
Microchannel condenser Yes Yes
Fan speed controller Yes (inbuilt in controller)
Main switch (circuit breaker) Yes Yes
Filter drier (flare connections) Yes Yes
Sight glass Yes Yes
Crankcase heater Yes Yes
HP/LP adjustable pressostat Electronic
Fail safe mini-pressostat Mechanical / Panel
Access door(s) Yes Yes
Acoustic insulation Yes* Yes
Condensing unit electronic controller Yes Yes
Network connectivity Yes Yes
Stack mounting Yes Yes
Oil separator
Discharge gas thermostat Yes Yes
Common alarm contact SPDT (HP/LP alarm) Yes Yes
Liquid injection kit Yes
Electrical Box design 11354 11354
Adjustable time delay (Compressor) Yes Yes
Pressure Relief Valve** Yes Yes
  • Not Factory pre-mounted
    ** PED category II models only (See Technical data table)

Technical data

Application| Code| Model| Compressor
Model| Electrical
Code| Refrigerant| Receiver(L)| PED category| pc
‘ “| Suction
Valve| Liquid
Valve| Housing| Uni Dimensions (mml
---|---|---|---|---|---|---|---|---|---|---|---|---
bar| Inch| Inch| H| W| L
LBP| 114X3110| OP-LPVM016DPPOOG| DPT16LA| G| V| 1.| I| 32| 3/8″| 3/8′| H1| 650| 941| 406
114X3201| OP-LPVMO26DSPOOG| DST26NA| G| V| 3.| II| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X3202| OP-LPVM034DSPOOG| DST34LA| G| V| 3.| II| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X3204| OP-LPVM048NTPOOG| NTZ048-5| G| V| 3.| II| 32| 5/8″| 3/8′| H2| 813| 1090| 480
114X3205| OP-LPVM048NTPOOE| NTZ048-4| E| V| 3.| II| 32| 5/8″| 3/8″| H2| 813| 1090| 480
114X3207| OP-LPVM068NTPOOE| NTZ068-4| E| V| 3.| II| 32| 5/8″| 3/8′| H2| 813| 1090| 480
114X3304| OP-LPKM067LLP02E| LLZ013T4B| E| K| 6.| II| 32| 3/4″| 1/2″| H3| 965| 1441| 531
114X3305| OP-LPKM084LLP02E| LLZ015T4B| E| K| 6.| II| 32| 3/4″| 1/2′| H3| 965| 1441| 531
114X3306| OP-LPKM098LLP02E| LLZ018T4B| E| K| 6.| II| 32| 3/4″| 1/2′| H3| 965| 1441| 531
114X3405| OP-LPKM12OLLP02E| LLZ024T4B| E| K| 2 X 5| II| 32| 1 1 /8′| 3/4′| H4| 966| 1835| 650
114X3406| OP-LPKM168LLP02E| LLZ034T4B| E| K| 2 X 5| II| 32| 1 1 /8′| 3/4′| H4| 966| 1835| 650
MBP| 114X4107| OP-MPTMOO8DYPOOG| DLY8ORAb| G| T| 1.| I| 32| 3/8″| 3/8′| H1| 650| 941| 406
114X4111| OP-MPTMOO9DYPOOG| DLY9ORAb| G| T| 1.| I| 32| 3/8″| 3/8′| H1| 6S0| 941| 406
114X4113| OP-MPTM012DPPOOG| DPT12RA| G| T| 1.| I| 32| 3/8″| 3/8′| H1| 6S0| 941| 406
114X4114| OP-MPTM014DPPOOG| DPT14RA| G| T| 1.| I| 32| 3/8″| 3/8′| H1| 6S0| 941| 406
114X4115| OP-MPTM018DXPOOG| DX18Tba| G| T| 1.| I| 32| 3/8″| 3/8′| H1| 6S0| 941| 406
114X4217| OP-MPTMO21DXPOOG| DX21Tba| G| T| 3.| II| 32| 1/2″| 3/8′| H2| 813| 1090| 480
114X4237| OP-MPTMO22DSPOOG| DS22TB| G| T| 3.| II| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X4238| OP-MPTMO26DSPOOG| DS26TB| G| T| 3.| II| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X4239| OP-MPTMO26DSPOOE| DS26T3| E| T| 3.| II| 32| 1/2″| 1/2″| H2| 813| 1090| 480
114X4243| OP-MPSMO26CSPOOG| CS26TB| G| S| 3.| I| 32| 1/2″| 1/2″| H2| 813| 1090| 480
114X4244| OP-MPSMO3OCSPOOG| CS3OTB| G| S| 3.| I| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X4241| OP-MPTM034DSPOOG| DS34TB| G| T| 3.| II| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X4242| OP-MPTM034DSPOOE| DS34T3| E| T| 3.| II| 32| 1/2″| 1/2′| H2| 813| 1090| 480
114X4204| OP-MPIM034MLPOOE| MLZ015T4B| E| I| 3.| II| 32| 3/4″| 1/2′| H2| 813| 1090| 480
114X4205| OP-MPIM034MLPOOG| MLZ01 STSB| G| I| 3.| II| 32| 3/4″| 1/2′| H2| 813| 1090| 480
114X4218| OP-MPTM038DSPOOG| DST38NA| G| T| 3.| II| 32| 1/2″| 3/8″| H2| 813| 1090| 480
114X4206| OP-MPIM046MLPOOE| MLZ021T4B| E| I| 3.| II| 32| 3/4″| 1/2′| H2| 813| 1090| 480
114X4207| OP-MPIM046MLPOOG| MLZ021T5B| G| I| 3.| II| 32| 3/4″| 1/2″| H2| 813| 1090| 480
114X4208| OP-MPIM057MLPOOE| MLZ026T4B| E| I| 3.| II| 32| 3/4″| 1/2′| H2| 813| 1090| 480
114X4209| OP-MPIM057MLPOOG| MLZ026T5B| G| I| 3.| II| 32| 3/4″| 1/2″| H2| 813| 1090| 480
114X4306| OP-MPIM068MLPOOE| MLZ030T4B| E| I| 6.| II| 32| 7/8| 5/8′| H3| 965| 1441| 531
114X4307| OP-MPIM068MLPOOG| MLZ030T5B| G| I| 6.| II| 32| 7/8| 5/8′| H3| 965| 1441| 531
114X4309| OP-MPIM080MLPOOE| MLZ038T4B| E| I| 6.| II| 32| 7/8| 5/8′| H3| 965| 1441| 531
114X4312| OP-MPIM080MLPOOG| MLZ038T5B| G| I| 6.| II| 32| 7/8| 5/8″| H3| 965| 1441| 531
114X4314| OP-MPIM108MLPOOE| MLZ048T4B| E| I| 6.| II| 32| 7/8| 5/8″| H3| 965| 1441| 531
114X4409| OP-MPIM125MLPOOE| MLZ058T4B| E| I| 2 X 5| II| 32| 1 1 /8″| 3/4″| H4| 966| 1835| 650
114X4410| OP-MPIM162MLPOOE| MLZ076T4B| E| I| 2 X 5| II| 32| 1 1 /8″| 3/4″| H4| 966| 1835| 650

Annex – B,
GA & PID Drawings 

OP-MPT, OP-LPV, OP-LPKDanfoss OP-MPS Optyma Plus Condensing Units - PID
Drawings 1

OP-MPT, OP-LPV, OP-LPK OP-MPS, OP-MPIDanfoss OP-MPS Optyma Plus
Condensing Units - PID Drawings 2

OP-MPT, OP-LPV, OP-LPK, OP-MPS, OP-MPI, OP-LPK
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
3 OP-LPK, OP-MPI
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
4 Legend

A Ø12 Hole for Mounting
B Sight Glass
C Controller Display| D Air in
E Air out
F Suction Port
G Liquid Port| H Nameplate
Electrical Cables
Note: all dimension are in mm
---|---|---

P00 Models: OP-MPT, OP-LPV, OP-LPK OP-MPS, OP-MPI
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
5 P02 Models: OP-LPK
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
n6P00 Models: OP-MPI(114X44–), P02 Models: OP-LPK(114X34–)
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
7 Legend

  1. Compressor
  2. EXV- Electric Expansion Valve (P02 only)
  3. Micro Channel Heat Exchanger with axial fan
  4. Refrigerant receiver with rotalock valve
  5. Filter Drier
  6. Sight Glass
  7. Liquid Ball Valve
  8. Suction Ball Valve
  9. Non return Valve
  10. Pressure Relief Valve (PED category II models only)
    B1 Condensing Pressure Transducer (P1)
    B2 Suction Pressure Transducer (P2)
    B3 High Pressure cartridge Switch (auto-reset)(PSH)
    B4 Low Pressure cartridge Switch (auto-reset) (PSL)
    R1 Discharge Temperature Sensor (T1)
    R2 Ambient Temperature sensor (T2)
    R3 Suction Temperature Sensor (T3)
    Insulation

Annex – C,
Wiring Diagram
Code G : OP-LPV, OP-LPKM016, OP-MPTM008,009,012,014,018,02Danfoss OP-MPS
Optyma Plus Condensing Units - PID Drawings 8 Code G : OP-MPTM022,026,034,038, OP-LPV, OP-LPKM026,034,OP- MPSM,026,030
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
9

Code G: OP-LVM048,068, OP-MPIM034,046,057

Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
10

Code E: OP-MPWM057, OP-MPTM026,034, OP-LPV, OP-LPKM048,068, OP-MPIM034,046
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
11 Code G (P00) : OP-MPIM068,080
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
12 Code E (P00) : OP-MPIM068,080,108
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
13Code E (P02) : OP-LPKM067,084,098
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
14
Code E: OP-LPKM120 &168
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
15 Code E: OP-MPIM125 & 162
Danfoss OP-MPS Optyma Plus Condensing Units - PID Drawings
16

Legend

A1 : Optyma™ Plus Controller
A2 : EMI Filter
A3 : Liquid Injection Controller
B1,B5 : Condensing Pressure Transducer
B2 : Suction Pressure Transducer
B3 : High Pressure Switch (OFF = 31bar(g), ON = 24bar(g))
B4 : Low Pressure Switch (OFF = -0,3bar(g),
ON = 0,5bar(g))
C1 : Start Capacitor (Compressor)
C2 : Run Capacitor (Compressor)
C3 : Run Capacitor (Fan 1)
C4 : Run Capacitor (Fan 2)
E1 : Crankcase Heater
F1 : Fuse (Control Circuit)
F2,F3 : Motor protector
K1 : Contactor
K2 : Start Relay
M1 : Compressor| M2 : Fan Motor 1
M3 : Fan Motor 2
M4 : Electronic Expansion Valve
Q1 : Main Switch
R1 : Ambient Temp. Sensor
R2,R8 : Discharge Temp. Sensor
R3 : Suction Temp. Sensor
R4,R5 : Auxiliary Temp. Sensor (optional)
R7 : NTC Resistor
S1 : Room Thermostat (optional)
S2 : Door Limit Switch
X1 : Terminal
Supply : Supply
Fan : Fan
Alarm : Alarm
Comp. : Compressor
CCH : Crankcase Heater
Aux : Auxiliary
---|---

Danfoss A/S Climate Solutions
danfoss.com
+45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

821AN37261897352601-010401 – 118A2177D
© DanfossiClimate Solutions 2023.05

Documents / Resources

| Danfoss OP-MPS Optyma Plus Condensing Units [pdf] Instructions
OP-MPS, OP-MPT, OP-LPV, OP-LPK, OP-MPI, OP-MPS Optyma Plus Condensing Units, Optyma Plus Condensing Units
---|---

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals