APPA VP-2 Voltage Tester User Manual
- June 10, 2024
- APPA
Table of Contents
APPA VP-2 Voltage Tester
Product Information
The VP-2 is a voltage tester that can detect voltage and phase sequence. It has a test probe, detection result indication area, clip, battery cover, function key, and mode indication lights. The device is protected by double or reinforced insulation and conforms to EU directives. It comes with a limited warranty.
Product Usage Instructions
Safety Information:
- Read and follow the operating instructions carefully.
- Use the meter only as specified in the manual to ensure protection.
Power On/Off:
- To turn on/off the VP-2, press and hold the function key for 1 second.
- The detectors will automatically power off after approximately 5 minutes of idle time.
Switch Detection Mode:
- To switch between voltage and phase detection mode, click the function key.
- On AC voltage detection mode, the yellow light flashes.
- On phase rotation detection mode, the red light flashes.
Voltage Detection:
- When detecting voltage >100Vac of the conductor, the yellow light stays on and the red light in the detection result indication area flashes with beeping intermittently.
- The higher the voltage, the quicker the intermittency.
Phase Sequence Indication:
- To locate line interruptions, follow these steps:
- Test on the 1st line until the red light of this mode is flashing once/sec with beeping
- Move the probe tip to the 2nd line within 2 seconds, and test on the 2nd line until the green light of this mode turns to flashing once/sec from still on with beeping.
- When the test is completed, the green light of this mode is off, and the test result is shown on the detection result indication area as mentioned in phase sequence indications.
Battery Replacement:
- To replace batteries, unscrew the battery cover and remove discharged batteries.
- Insert new batteries by respecting the correct polarity and close the battery cover carefully.
- If the instrument is likely to remain unused for a long period,
it is advised to remove the batteries.
Maintenance:
- Do not attempt to repair this detector. It contains no user-serviceable parts.
- Repair or servicing should only be performed by qualified personnel.
Read First Safety Information
Understand and follow operating instructions carefully. Use the meter only as specified in this manual; otherwise, the protection provided by the meter may be impaired.
WARNING
- Only touch the instrument handle for any detection. Do not touch the tip of the instrument while testing. When using detector, keep your fingers behind thefinger guards.
- Use the detector only as specified in this manual or the protection by the detector might be impaired
- Before use, check the instrument for damages. Do not use the tester if damages are detected.
- Use caution with voltages above 30 Vac rms, 42 Vac peak,or 60 Vdc. These voltages pose a shock hazard.
- The signal during the voltage detection does not provide any indication of the type and level of voltage present. when testing mains connected cables for interruptions the user must ensure that both lines are connected once to phase.
- Do not use detector around explosive gas or vapor.
- To reduce the risk of fire or electric shock do not expose this product to rain or moisture.
- The detector must only be used under conditions and for the purposes for which it has been designed. Particular attention should be paid to the safety instructions, the technical specifications relating to environmental conditions and the use of the detector in dry surroundings.
- The following factors might affect the correct functioning of the phase test and phase sequence test :
- excessive distance to the phase (external conductor) to be tested
- excessive insulation and shielding of the phase (external conductor)
- protective clothing and insulating conditions on site
- constructional differences of sockets / CEE couplings with recessed contacts, e.g. 63 A CEE coupling
- mains failures or lacking mains quality
- battery condition
WARNING
Identifies hazardous conditions and actions that could cause BODILY HARM or
DEATH.
CAUTION
Identifies conditions and actions that could DAMAGE the detector or equipment
under test.
Symbols as marked on the Meter and Instruction manual
Features
- AC Voltage detection on conductive and insulated parts.
- Phase sequence indication and conformity phase test.
- Test on outlets, cables and /or electrical appliances.
- Visible LED and acoustic buzzer indications.
- Practical pen clip and very small size.
- Auto Power OFF.
- Meter suitable for any electrical installer. Compact design with convenient battery door.
- CAT. IV 600V /CAT. III 1000V Safety Standard.
The Meter Description
-
Test probe.
-
Detection result Indication area.
(Red light/Green light) -
Clip.
-
Battery cover.
-
Function key.
-
Phase sequence detection mode indication.(Red light / Green light)
-
Voltage detection mode indication.
(Yellow light)
Power On/Off
Press function key for 1 seconds to turn the VP2 on/off.
Auto Power Off
The detectors will automatically power off after approximately idle 5 minutes.
Switch detection mode
- Press function key to switch Voltage/Phase detection mode.
- On AC Voltage detection mode: the Yellow light of this mode flashing.
- Phase rotation detection mode: the Red light of this mode flashing.
Voltage detection
While detecting the voltage >100Vac of the conductor, the Yellow light of this
mode is still on and the Red light in the Detection result indication area is
flashing with beeping intermittently.
The higher voltage with quicker intermittency
Voltage test at insulated conductors.
Locating line interruptions.
Phase sequence indication
- Test on 1st line, the Red light of this mode is flashing once/sec with beeping, keep the test on L1 until the Green light of this mode is still on.
- Move the probe tip to 2nd line in 2 seconds, test on 2nd line the Green light of this mode turns to flashing once/sec from still on with beeping.
- When test is completed the Green light of this mode is Off and the test result is shown on detection result indication area as mentioned in Phase sequence indications.
Phase sequence indications
The test result is to be one of light showings below with 3 intermittent beeps
in 5 seconds.
-
1st line ahead 2nd line: The Green light of Detection result indication area is still on.
(1st line >> 2nd line) -
1st line after 2nd line: The Red light in Detection result indication is still on.(2nd line >> 1st line)
-
The same phase field indication :
The Green Light in Detection result indication is flashing. -
Error indication : The Green light and Red light in Detection result indication are flashing alternately. Detection result represented the relation of Line 1 and Line2 and Line3(Left rotary / Left rotary).
-
The phase sequence test always requires a countercheck during which the phase sequence must change.
Note:
Always hold the device steady during the measurements without wobbling.
Mains failures or a lacking mains quality might affect the correct functioning
of the device.
Battery replacement
Unscrew the battery cover Remove discharged batteries and insert new by
respecting the correct polarity. Close the battery cover careful.
WARNING
If the instrument is likely to remain unused for a long period it is advised
to remove the batteries. Please think of our environment when getting rid of
used batteries. They should be disposed in a place suitable for hazardous
waste.
Maintenance
Do not attempt to repair this Detector. It contains no user-serviceable parts.
Repair or servicing should only be performed by qualified personnel.
Cleaning
Periodically wipe the case with a dry cloth and detergent.
Do not use abrasives or solvents.
Specifications
- Auto Power Off : Approx. 5 minutes
- Voltage range : 100VAC~1000 VAC Frequency : 45 ~ 65 Hz
- Overvoltage category :
- Designed to meet IEC 61010 & UL61010
- CAT III 1000 VAC, CAT IV 600 VAC
- CAT Application field
- The circuits not connected to mains.
- The circuits directly connected to Low- voltage installation.
- The building installation.
- The source of the Low-voltage installation.
- Protection category : IP 53
- Battery Life : 150 hours (standby)
- Pollution Degree: 2
- Operating temperature :
- 10 °C ~ 50 °C
- 10 °C ~ 40 °C (≤ 75% RH)
- 40 °C ~ 50 °C (≤ 45% RH)
- Storage temperature : -20 to 60 °C for current, 0 to 80% RH (batteries not fitted).
- Power supply : 2x AAA, 1.5 V LR03
- Dimensions : 20.6mm(W) x 151mm(L) x 25.2mm(D)
- Weight : approx. 40 g (incl. batteries)
- Drop Protection : 4 feet drop to hardwood on concrete floor.
Limited Warranty
The testers are subject to stringent quality controls. If in the course of
normal daily use a fault should occur, we provide 3 year guarantee (only valid
with invoice) .
Faults in manufacture and materials will be rectified by us free of charge,
provided the tester has not been tampered with, and is returned to us
unopened.
Damage due to dropping, abuse ormisuse is not covered.
Our service department will promptly repair any fault that occur outside the
guarantee period.
This instruction manual has been prepared with great care.
No liability is accepted for the correctness and completeness of the data and
illustrations it contains. We reserve the right to make technical alterations.