Safety Information
Understand and follow operating instructions carefully. Use the meter only as
specified in this manual; otherwise, the protection provided by the meter may
be impaired.
Warning
This identifies hazardous conditions and actions that could cause BODILY HARM
or DEATH.
To avoid possible danger, follow below guidelines.
- If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
- Always use proper terminals, switch position, and range for measurements.
- To reduce the risk of fire or electric shock, do not use this product around explosive gas or in damp locations.
- Do not apply more than the rated voltage, as marked on meter, between terminals or between any terminal and earth ground.
- To avoid false readings that can lead to electric shock and injury, replace battery as soon as low battery indicator blinks.
- Avoid working alone so assistance can be rendered.
- Do not use the Tester if the Tester is not operating properly or if it is wet.8
- Individual protective device must be used if hazardous live parts in the installation where the measurement is to be carried out could be accessible.
- Individual protective equipment should be used if HAZARDOUS LIVE parts in the installation where measurement is to be carried out could be ACCESSIBLE.
Symbols as marked on the Tester and Instruction card
| Risk of electric shock
---|---
| See instruction card
| DC measurement
| AC measurement
| Both direct and alternating current
|
Equipment protected by double or reinforced insulation
| Battery
| Earth
****| Conforms to EU directives
| Application around and removal from hazardous live conductors is permitted
| Do not discard this product or throw away.
Maintenance
Do not attempt to repair this Meter. It contains no user-serviceable parts. Repair or serving should only be performed by qualified personal.
Cleaning
Periodically wipe the case with a dry cloth and detergent.
Do not use abrasives or solvents.
Front Panel Illustration
-
Jaw
-
Trigger
-
Barrier for Hand Guard
-
Function swith
-
ZERO A( ****) button
-
LED indicator
• Power on indicator (Green, flash while powering-on)
• Low battery on indicator (Red) -
Coiled Cable Connector – Voltage output
Making Basic Measurements
Measuring AC/DC Ampere
Warning
The barrier on the JAW is indicating the limit of safe access of the hand-held
part, do not hold over the barrier when in normal use.
DCA ZERO
Auto Power off (APO)
Wake up the meter by switching the slide switch.
Battery Replacement
Replace the battery as soon as the low battery indicator appears, to avoid false reading. Refer to the following figure to replace the batteries
Unscrew the screw by a cross screw driver, then open the battery cover.
- Remove discharged batteries
- Replace by new batteries
- Close the battery cover and re-screw the screw
Specifications
1-1 General Specifications
Dimensions : 66 mm (W) x 185 mm (L) x 40 mm (H).
Weight : 270 grams (including battery).
Power requirement : 9V battery x1
Auto power Off : The meter automatically turns the power off after powering up
and no operation for 35 ± 10minutes.
Battery life (based on Alkaline Battery) : 66 hours
Maximum Conductor Size : 22mm
LVD : EN61010-1, EN61010-031, EN61010-2-032
EMC : EN61326-1
Installation Category : CAT.III. 600V for Jaw
II | The circuits directly connected to Low-voltage installation. |
---|---|
III | The building installation. |
IV | The source of the Low-voltage installation. |
1-2 Environmental Conditions
Indoor Use.
Maximum operating altitude : 2000m (6562ft)
Operating temperature : 0°C ~ 50°C, ≦75%RH
Storage temperature : -20 to +60°C, 0 to 80% RH (no batteries).
Temperature coefficient : 0.2 x (Specified accuracy) / °C, < 18°C, > 28°C
Pollution Degree : 2
Shock vibration : MIL-PRF-28800F for A class 2 Instrument
Drop Protection : 4 Feet Drop to hardwood on concrete Floor
Type of sensing : Hall effect sensing for AC and DC
1-3 Electrical Specifications
Accuracy is given as ± (% of reading + counts of least significant digit) at
23°C ± 5°C, with relative humidity less than 80% R.H. Accuracy is specified
for a period of one year after calibration.
Position Error of Clamp: Add ±1% of LCD reading.
Ampere
Range | Output Ratio | Accuracy |
---|---|---|
(0 – 40)A | 10mV/A | ±(1.0% +0.2A) |
(40 – 200)A | 1mV/A | ±(1.0% +1A) |
(200 – 300)A | 1mV/A | ±(1.9% +2A) |
Frequency Response : DC,AC 40Hz to 400Hz
Output Impedance : < 10kΩ
Overload Protection : AC/DC 300A
Limited Warranty
This meter is warranted to the original purchaser against defects in material
and workmanship for 3 years from the date of purchase.
During this warranty period, Manufacturer will, at its option, replace or
repair the defective unit, subject to verification of the defect or
malfunction.This warranty does not cover fuses, disposable batteries, or
damage from abuse, neglect, accident, unauthorized repair, alteration,
contamination, or abnormal conditions of operation or handling. Any implied
warranties arising out of the sale of this product, including but not limited
to implied warranties of merchantability and fitness for a particular purpose,
are limited to the above.
The manufacturer shall not be liable for loss of use of the instrument or
other incidental or consequential damages, expenses, or economic loss, or for
any claim or claims for such damage, expense or economic loss. Some states or
countries laws vary, so the above limitations or exclusions may not apply to
you.
www.appatech.com
APAC
MGL APPA Corporation
cs.apac@mgl-intl.com 700019912
700019912 JULY 2021 V1
©2021 MGL International Group Limited.
All rights reserved.
Specifications are subject to change
without notification
Documents / Resources
| APPA
30T AC DC Current
Transducer
[pdf] User Manual
30T AC DC Current Transducer, 30T, AC DC Current Transducer, DC Current
Transducer, Current Transducer, Transducer
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>