Read First

Safety Information

  • If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
  • Verify this detector operation by measuring a known voltage before using it. If in doubt, have the detector serviced.
  • Do not apply more than the rated voltage, as marked on Detector, at the tip.
  • Avoid working alone so that assistance can be rendered.
  • Do not use the Detector if the detector is not operating properly or if it is wet.
  • Individual protective device must be used if hazardous live parts in the installation where the measurement is to be carried out could mbe accessible.
  • The detector must be used only in earthed mains supply circuits and in the conditions specified in this manual.

Symbols as marked on the Tester and Instruction manual

| Risk of electric shock
---|---
| See instruction manual


| Do not discard this product or throw away


| AC measurement
| Battery
| Earth


| Conforms to EU directives


| Equipment protected by double or reinforced insulation

Maintenance

Do not attempt to repair this Clamp Meter.

It contains no user-serviceable parts.

Repair or serving should only be performed by qualified personnel.

Cleaning

Use a damp cloth with household cleaner and wipe the surface by applying light pressure.

Do not use the tester till it is completely dry

Voltage detecting

Voltage detecting

Warning
The LED indicates the electric field.
If the VoltSense LED is not on, voltage could still be present.

Localize wire break of live line

Localize wire break of live line

Pass the tip of detector along the isolated live line from the voltage source to the other end of the line. Detector flashes and beeps until the tip pass over the position of wire break.

Battery replacement

Battery replacement

Warning
Verify this detector’s operation by measuring a known voltage. If no response, replace the batteries first. Please Make sure that the battery cover is tightened.

Specifications

General Specifications

Operating Temperature : 0°C to 50 °C (≤ 80% R.H.)
Storage Temperature : -20°C to 60 °C (≤ 80% R.H., no batteries)
Operating Altitude : 2000m (6562 ft)
Drop Protection : 4 feet drop to hardwood on concrete floor
Vibration : Random Vibration per MIL-PRF-28800F Class 2
Dimensions : 152 x 22 x 18mm
Weight : approx. 40g (included batteries)
Voltage Sensing Range: 100V AC to 1000V AC (phase to earth)
Frequency : 45Hz to 65Hz
Battery Type : AAA 1.5V x 2
Overvoltage category : IEC/EN 61010-1, IEC/EN61010-2-030, CAT.IV 600V,CAT. III 1000V

CAT Application field
The circuits are not connected to mains.
The circuits are directly connected to Low-voltage installation.
The building installation.
The source of the Low-voltage installation.

Pollution degree : 2
EMC : EN 61326-1

Limited warranty

The testers are subject to stringent quality controls. If in the course of normal daily use, a fault should occur, we provide 3 years guarantee (only valid with invoice). Faults in manufacture and materials will be rectified by us free of charge, provided the tester has not been tampered with, and is returned to us unopened.

Damage due to dropping, abuse or misuse is not covered.Our service department will promptly repair any faults that occur outside the guaranteeb period.

This instruction manual has been prepared with great care.

No liability is accepted for the correctness and completeness of the data and illustrations it contains. We reserve the right to make technical alterations.

Customer Support

www.appatech.com

APAC
MGL APPA Corporation
[email protected]
Flat 4-1, 4/F, No. 35,
Section 3 Minquan East Road,
Taipei, Taiwan
Tel : +886 2-2508-0877

APPA Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

APPA User Manuals

Related Manuals