BLUE JAY BJ-PR200 Series Electronic Motor Protection Relay User Manual
Read me
When you use BJ-PR200 series electronic motor protection relay, be sure to read this user manual carefully, and be able to fully understand the implications, the correct guidance of operations in accordance with user manual, which will help you make better use of BJPR200 series motor protector, and help to solve the various problems at the scene.
- Before the meter turning on the power supply, be sure that the power supply within the provisions of the instrument;
- When installation, the current input terminal must non-open, voltage input terminals must Nonshort circuit;
- Communication terminal (RS232/RS485 or Ethernet) is strictly prohibited to impose on high pressure;
- Be sure the instrument wiring consistent with the internal system settings;
- When communicating with the PC, instrument communication parameters must be consistent with the PC.
Please read this user manual carefully Please save this document
1. – SUMMARIZE
PR200 motor protection relay is an all-in-one solution designed to continuously monitor 3-phase power lines for abnormal conditions. It can use with motors less than 690V/820A. Packed inside a small and economic package you’ll find a solution designed to save you time and money.
The series of products through the real-time monitoring of the scene signal, provide various protection trip to avoid motor failure. When the PR200 sense the motor operating parameters to achieve the preset alarm value, will trig the DO port to warning the abnormal status; abnormal parameters continue to accumulate to a dangerous value, will automatically trigger the release switch to shut down the circuit.
Option RS485 communication port can upload the monitor data and alarm status to remote control system.
Protection function (Details please refer to chapter 7)
Start Overtime,
Over Load,
Phase Failure,
Stall,
Current imbalance,
Under load,
Jam,
Ground fault
2. – FEATURES
-. High accuracy sample calculation, class 0.5 for 2% -120% measurement range; class 1 for 120% -1000% measurement range.
-. Built-in 2-channel relay, free to user set protected trip mode, alarm mode and trig mode. In protection mode, channel 1 relay can use for alarm, channel 2 for trig operation.
-. User free to set each protection function act off, alarm or trip.
-. Build in Sequence of Event function, can logger last 10 trip records.
-. With programmable analog output function, user option RS-485 communication interface.
-. Can provide basic electrical parameter for user SCADA system.
-. Wide range of power supply AC85-265V or AC80-450V.
3. – SPECIFICATIONS
Working environment:
Motor rated voltage: AC380V / AC660V
Motor rated current: 0.5-820A
Working temperature: -20C ~ +60C
Storage temperature: -40C ~ +80C
Relative humidity: < 93% RH
Elevation: not more than 3000 m
Atmospheric conditions: installation site does not allow the explosive medium,
containing gas to corrode metal and damage the insulation and conductive
medium.
Measuring accuracy:
Current: ± 0.5% (2% to 120% of Ie)
± 1% (120% to 10% of Ie)
Voltage: ± 0.5%
Leakage current: ± 1% (10% to 100% of Ir)
Analog Output: ± 1% (4 ~ 20mA)
Electrical parameters:
Auxiliary Power: AC80-450V (DC110V-500V)
Power consumption: <4 VA
Insulation resistance: > 100MΩ
Relay: Trip relay @ 10A / AC250V, 10A / 30VDC (NC node) Alarm relay @ 5A /
250VAC, 5A / 30VDC (NO node)
Electrical test:
IEC 61000-4-2 level III
IEC 61000-4-4 level III
IEC 61000-4-5 level III
IEC 61010-1 AC2kV/1min Between power / input / output
Product standards
Protection CT selection guide
Residual current CT
If PR200 choose ground fault protection, need external LCT05/30 series CT for
detect leakage current.
LCT05 rated current of 500mA, the current range (50 ~ 500mA) LCT30 rated
current of 30A, the current range of (3 ~ 30A)
Each PR200 need 1pcs, please contact sales team for purchase issue.
4.- INSTALLATION AND START-UP
⚠ The manual you hold in your hand contains information and warnings that the
user should respect in order to guarantee a proper operation of all the
instrument functions and keep it in safety conditions. The instrument must not
be powered on and used until its definitive assembly is on the cabinet’s door.
If the instrument is not used as manufacturer’s specifications, the protection
of the instrument will be damaged.
When any protection failure is suspected to exist (for example, it presents
external visible damages), the instrument must be immediately powered off. In
this case contact a qualified service representative.
4.1.- Installation
Mounting
PR200 series motor protector have two version installation mode, one for CT
separate installation, another is CT integrated installation. Each instrument
is to be mounted on panel (cut-out a mounting hole). Keep all connections into
the cabinet.
Note that with the instrument powered on, the terminals could be dangerous to
touch and cover opening actions or elements removal may allow accessing
dangerous parts. Therefore, the instrument must not be used until this is
completely installed.
Note: This connection drawing is for reference only; the actual connecting
terminal please refer to the label on the rear part.
4.2.- Typical Wiring
4.2.1.- Connection with residual protection CT
4.2.2.- Connection with analog output
5. OPERATION MODE
5.1- Panel key operation
5.1.1- Key operation
← → In Monitor screen for move to next / previous page
In configuration menu for value increase/decrease
Menu Configuration menu enters or exit & roll back to up layer menu
Enter next layer menu or confirm the change
5.1.2- Enter configuration menu
In normal monitor status, press key MENU, the main screen will show “CodE” press key into password screen, use key and to enter password (default user password is 0001), then press key to confirm enter, in password correct can into the menu screen, or still ask password.
5.1.3- Exit configuration menu
After parameter set, press key MENU, protector screen show “SAVE”, then press key for save the change and exit, press key MENU for exit without save.
5.2- Motor protector start
When the PR200 is powered up, the screen show “Stop”, mean the motor without
work, user can press key and to check basic electrical parameter.
In the motor start period will show “- – – -“, after the start successful, the
protector in normal working status, will automatic show three phase electrical
parameter in turn. Then press key can choose page rolling manually or page
rolling automatically, use key or for manually switch to next or previous
display page.
5.3- Real-time fault detection
When a motor failure is detected, PR200 will act different logic:
Act for alarm -. Indicator lights in the front panel will ON; -. Alarm relay
be trigged
After the failure be removed: -. Indicator will automatically turn off; -.
Alarm relay automatic reset to NO status
Act for trip -. Indicator lights in the front panel will flicker -. Alarm
relay be trigged -. Trip replay be trigged
After the failure be removed: -. Must press key to reset protector to normal
status;
Notes: If overload protection trip, must waiting enough time for cool down
then can success release.
5.4- Sequence of Event (SOE)
5.5- Configuration menu structure introduction
Note: Not all PR200 series have above complete configuration menus, please confirm your purchased PR200 sub-code, if do not have the corresponding extension module. In configuration menu corresponding part is invalid.
5.6- Example of programming menu operation
5.6.1- Set sampling input value
Step1: Press Menu enter configuration menu; device ask password;
Step2: Press for entry password, use key ← & → to input password 0012, will
move to Level-1 configuration menu;
Step3: Press to enter level-2 of “Signal Input” menu, to set Input current
range “InPt”;
Step4: Press enter level-3 value range selecting, you can see default current
range “5A”;
Step5: Press← or → to select input current range, in example use “10A”;
Step6: Press to confirm the modify and return to the previous level menu;
Step7: Press Menu for roll back to the level-1 menu;
Step8: Press Menu for exit configuration to the monitor screen;
Step9: Main screen show “SAVE”, press for save the change and exit
configuration; press Menu for exit without save.
5.6.2- Overload protection setting
Step1: Press Menu enter configuration menu; device ask password;
Step2: Press for entry password, use key ← & → to input password 0001, will
move to Level-1 configuration menu;
Step3: Press ← or → to choose Protection function setting menu “Pro.t”;
Setp4: Press to enter level-2 of “Pro.t”, you can see Start timeout set menu
“S.LnG”;
Step5: Press ← or → to choose Overload protection submenu “L.our”;
Step6: Press to entry level-3, device ask set Protection mode menu “ModE”,
Then press again entry selection, Press ← or → to choose “ALRM”, ”TRIP”,
”OFF”;
After select, press to confirm the modify return to the previous level menu
Step7: In protection mode level-2, press → can set the overload K-factor;
Step8: In protection mode level-2, press → can set the overload cool down
time;
Step9: In protection mode level-2, press → can set the overload reset mode;
Step10: Press Menu for exit configuration to the monitor screen;
Main screen show “SAVE”, press for save the change and exit configuration;
press Menu for exit without save.
6. – RS485 COMMUNICATION PORTOCOL
6.1.- MODBUS © protocol
The composition of the RS-485 cabling must be carried out with a meshed screen
cable (minimum 3 wire), diameter of not less than 0.5mm2, with a maximum
distance of 1,200 m between the motor protector and the master unit. This Bus
may connect a maximum of 32unit.
Notes:
- For communication with the master unit, customers can choose the RS-232 to RS-485 converter to use.
- Not all the PR200 with RS485 port, please check your ordered product to confirm if the meter has remote communication function.
Due to product modifications or custom requirements, the interface pin place may be change. For details, please refer to product label on the rear board
6.1.1- Modbus RTU Frame Format:
6.1.2.- Modbus function code
6.2.- Register Map-I (Only Read, use code 04)
6.3.- Register map (II.- Read and write parts)
Cautions!
- This chapter register map in default products the write function is disable in standard PR200, that to avoid unexpected damage due to frequent write operations, only opened for customer requirement!!
- Registers support maximum 100,000 times writes, wrong write registers may cause device irreparable damage! Please ensure that host software engineer proficient in RS485 MODBUS protocol.
- When the customer request valid the register write function, Blue Jay Technology Co., Ltd. will not responsible for any damage caused by the register write operation!!
7.- PORTECTION FUNCTION INTRODUCTION
7.1- Start Overtime protection
After the starting timer, if the three-phase average current 1.1 times the motor rated current (Ie) or 10% of the motor rated current (Ie) or three-phase average current, start timeout protection action.
Protection mode Alarm / Trip
Start timer 1.0 ~ 300.0s
Trip delay 0
7.2- Overload protection
Protector can track thermal capacity of the motor to avoid motor from overheating or damage. Controllers to simulate the thermal capacity of the motor in a variety of operating conditions, can real-time monitoring of motor heating conditions. Ensure effective protection of the repeated starting of the motor overheating condition continuous run.
Device provide 12 inverse time protection curves; user can select suitable curve for different motor working condition.
Typical trip time in different K factor and protection class
Overload inverse time curve quick select chart ( t unit: sec)
Cool down timer:
After motor stop, the cool down timer countdown to simulated the motor cools
to a safe state process; the definition of the cooling time is to reach steady
state of ambient temperature (the maximum allowable temperature) when motor
overload trip. Typically, cool timer can set to 30 minutes as heat capacity
values decreased from 100% to 15%.
7.3- Phase failure protection
When motor meet phase failure (Any of two phase over 25% of the rated current, another phase less than 12.5% of the rated current), will trip the phase failure protection.
Protection mode OFF / Alarm / Trip
Trip delay 0.1 ~ 50.0 s
7.4- Stall protection
Stall protection to prevent motor-driven equipment in serious operation block
or motor overload operation and heat damage to the motor,
Note: Stall protection only be act after the motor starter is complete.
Protection mode OFF / Alarm / Trip
Threshold 100 ~ 1000%Ie
Trip delay 0.5 ~ 50.0 s
7.5- Current imbalance protection
Current imbalance protection based on the maximum phase current imbalance to determine whether to start phase unbalance protection function. Current unbalance is calculated as follows:
7.6- Under load protection
If motor load occurs abnormal mutations, such as belt break or pump idling, define this situation is under load. Typically set under load protection in alarm mode, to let site worker pay attention.
Protection mode OFF / Alarm / Trip
Threshold 20 ~ 100 %Ie
Trip delay 0.5 ~ 50.0 s
7.7- Rotor Jam protection
Compare the motor maximum measured current value and motor rated current in
the starting process, to determine whether to act the protection.
Note: Jam protection only be act in the starting process, after motor normal
working will be automatic locked.
Protection mode OFF/Alarm/Trip
Threshold 100 ~ 1000% Ie
Trip delay 0.5 ~ 50.0 s
7.8- Ground Fault Protection(Optional)
If any part of winding comes in contact with the ground, then we can say the motor is earthed. Device use external CT to detect residual current, ideal state to set the low residual current failure action values to protect as much stator coil and prevent the motor casing with electricity and dangerous.
In direct grounding system should be set short delay time to avoid damage; In resistance grounding system, the value of the residual current is limited within the safe range, user can choose a longer delay time.
Protection mode OFF / Alarm / Trip residual current threshold 10 ~ 100%IΔn
Trip delay 0.1 ~ 5.0 s
7.9.- tE Protection
The tE protection function used for increased safety(IEC-60079-7) type motor, it provides 8 extra inverse time protection curves, to avoid unexpected overheat status.
Note:
-. The setting value of tE trip delay will transfer to actually trip time refer above chart
-. To ensure that the regular overload protection act before tE trap time, we suggest choose lower inverse time curve in overload protection, typically less 15%.
Protection mode OFF / Alarm / Trip
Trip delay 0.1 ~ 5.0 s
8- I/O Output (Optional)
8.1.- Analog output port
PR200 can provide 1 channel analog output port, can provide 4 ~ 20mA signal to
PLC or other device, user can free to select the transmit electrical
parameters: Ia, Ib, Ic, Iavg
Note: Analog output port cannot be choosing with the ground fault protection
function.
8.2.- Digital output port
PR200 can choose extra 2 channels digital output, the physical DO relay standard is 5A 250VAC / 5A 30VDC.
*Remote mode operation
In “Remote” mode, user can use function code 05 to trig single relay, device
RS-485 port follow MODBUS-RTU protocol, command as following:
Detail operation please refer to chart 5.5- Programming menu structure introduction
9. – SAFETY CONSIDERATIONS
All installation specification described at the previous chapters named:
INSTALLATION AND STARTUP, INSTALLATION MODES and SPECIFICATIONS.
Note that with the instrument powered on, the terminals could be dangerous to
touching and cover opening actions or elements removal may allow accessing
dangerous parts. This instrument is factory-shipped at proper operation
condition.
10. – MAINTENANCE
The PR200 series not require any special maintenance. No adjustment,
maintenance or repairing action should be done when the instrument is open and
powered on, should those actions are essential, high-qualified operators must
perform them.
Before any adjustment, replacement, maintenance or repairing operation is
carried out; the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be
immediately put out of service. The instrument’s design allows a quick
replacement in case of any failure.
For any inquiry about the instrument performance or whether any failure
happens, contact to Blue Jay’s technical service.