MEAN WELL HDR-15 Series 15W Ultra Slim Step Shape DIN Rail User Guide

June 11, 2024
MEAN WELL

MEAN WELL HDR-15 Series 15W Ultra Slim Step Shape DIN Rail

Product Information

The 15W Ultra Slim Step Shape DIN Rail HDR-15 series is a product designed for use in a variety of applications. It is UL508 and UL62368-1 certified and has been tested and approved by Bauar t gepruft Sicherheit and egel ma ge od o s be wac g. The product has been manufactured in compliance with BS EN/EN61558 and R33100 RoHS standards. It is also TPTC004 AS/NZS60950-1 and IEC62368-1 certified. The product has an ultra-slim design with a width of 17.5mm (1SU). It has a universal input of 85~264VAC (277VAC operational) and has no load power consumption.

Product Usage Instructions

Before using the product, ensure that it is installed correctly in compliance with the DIN rail mounting instructions provided in the user manual. Once the product is installed, follow the instructions below:

  1. Ensure that the input voltage is within the range of 85~264VAC (277VAC operational).
  2. Connect the input wires to the appropriate terminals on the product.
  3. Connect the output wires to the appropriate terminals on the product.
  4. Ensure that all connections are secure.
  5. Turn on the power supply.
  6. The product is now ready for use.

Note : The product has no load power consumption, which means that it will not consume any power when there is no load connected to it. However, it is recommended to disconnect the power supply when not in use to save energy.

Features

  • Ultra slim design with 17.5mm(1 SIJ) width
  • Universal input 85-264VAC(277VAC operational)
  • NO load power consumption<O.3W
  • Isolation class [I
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections : Short circuit / Overload / Over voltage
  • Cooling by free air convection (working
  • DIN rail TS-35/7.5 or 15 mountable
  • LED indicator for power on
  • 3 years warranty

Description

HDR-15 is one economical ultra slim 15W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 17.5mm(1 SIJ) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-15 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 87%, the entire series can operate at the ambient temperature between -300C and 700C under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1 , UL508, UL62368-1 , BS EN/EN61558-2-16) make HDR-15 a very competitive power supply solution for household and industrial applications.

Model Encoding

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTlN.asox

SPECIFICATION

MODEL| HDR-15-5| HDR-15-12| HDR-15-15| HDR-15-24| HDR-15-48
---|---|---|---|---|---








OUTPUT

| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 2.4A| 1.25A| 1A| 0.63A| 0.32A
CURRENT RANGE| 0 ~ 2.4A| 0 ~ 1.25A| 0 ~ 1A| 0 ~ 0.63A| 0 ~ 0.32A
RATED POWER| 12W| 15W| 15W| 15.2W| 15.4W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 4.5 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 2000ms, 80ms/230VAC 2000ms, 80ms/115VAC at full load
HOLD UP TIME (Typ.)**| 30ms/230VAC      12ms/115VAC at full load




INPUT

| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )     120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 80%| 85%| 85.5%| 86%| 87%
AC CURRENT (Typ.)| 0.5A/115VAC      0.25A/230VAC
INRUSH CURRENT (Typ.)| COLD START 25A/115VAC     45A/230VAC




PROTECTION

| ****

OVERLOAD

| 110 ~ 145% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed

Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed


OVER VOLTAGE

| 5.75 ~ 6.75V| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut off o/p voltage, clamping by zener diode





ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters











SAFETY & EMC

(Note 4)

| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;

Design refer to TUV BS EN/EN62368-1

WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-







EMC IMMUNITY

| BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,

>95% interruptions 250 periods


OTHERS

| MTBF| 3724.3K hrs min.      Telcordia SR-332 (Bellcore) ; 1166.1K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 17.59054.5mm (WHD)
PACKING| 78g;160pcs/13.5Kg/1.14CUFT
NOTE| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on http://www.meanwell.com)

5.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram