DAUDIN GFGW-RM01N Remote I-O Module System User Manual

June 11, 2024
DAUDIN

DAUDIN GFGW-RM01N Remote I-O Module System User Manual

1. Remote I/O Module System Configuration List

Part No. Specification Description
GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII, 4 Ports Gateway
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply
0170-0101 8 pin RJ45 female connector/RS-485 Interface Interface Module

Product Description

  1. The interface module can convert the gateway’s RS485 port into a RJ45
  2. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
  • The power module and interface module are standard for remote I/O’s and users can choose the model or brand they prefer.

Siemens S7-200 Smart Connection Setup

This section details how to connect a gateway to Siemens S7-200 Smart. For detailed information regarding , please refer to the _ -Series Product Manual_

__ i-Designer Program Setup

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cable

  2. Click to launch the software

  3. Select “M Series Module Configuration”

  4. Click on the “Setting Module” icon

  5. Enter the “Setting Module” page for M-series

  6. Select the mode type based on the connected module

  7. Click on “Connect”

  8. Gateway Module IP Settings

    **** Note: The IP address must be in the same domain as the controller equipment

  9. Gateway Module Operational Modes

Note:

Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)

Siemens S7-200 Smart Hardware Connections

This chapter explains how to use the Step7-MicroWINSMART program to connect S7-200 Smart to  . The software must be V2.4 or above for Modbus TCP support. For detailed information, please refer to the S7-200 SmartSeries Manual

  1. Modbus TCP connects with the gateway via the Ethernet cable going through the Ethernet port on the S7-200 Smart\

Siemens S7-200 Smart Connection Setup

  1. Launch Step7-MicroWINSMART and click on “Commands” on the right side of the program
    ****| A.       Click on the “Commands” menu

B.        Click on the “Bases” menu

C.        Click on the “Modbus TCP Client” menu

D.       Click to add a new “MBUS_CLIENT”

---|---

Communication protocol settings

ames & Definitions

| Names| Function
---|---|---
A| EN| Enable bits
B| Req| When it is “1”, it means to send Modbus requests to the server

C

|

Connec t

| When it is “1”, it will attempt to connect to the assigned IP address;

When it is “0”, it will disconnect and ignore any requests from the “Req” command

D

| IP Add 1~4|

Gateway IP address

E| IP Port| The gateway’s port number, which is 502
F| RW| Operating modes. “0” is “Read” and “1” is “Write”
G| Addr| Read/Write Modbus’ starting address
H| Count| Length   of   the   data   to be read/written
I| DataPtr| Address where the data is stored
J| Done| Completed bits
K| Error| Error Code

Command Memory Configurations

| A.       Click on the “Memory” menu

B.        Set up a command’s starting address and once finished, click on “Confirm”

---|---

Notes:

’s first GFDI-RM01N has the register address at 1000(HEX) converted to 4096(DEC)+1 and the starting address at 44097
 ’s first GFDO-RM01N has the register address at 2000(HEX) converted to 8192(DEC)+1 and the starting address at 48193

Sample Program

Control with one GFDI-RM01N and one GFDO-RM01N
When the first point of DI has received a signal and is triggered, the first point of DO will output a signal as it is connected