AAON CF Series Condensers and Condensing Units Instructions
- June 16, 2024
- AAON
Table of Contents
- AAON CF Series Condensers and Condensing Units
- Product Information
- Product Usage Instructions
- Startup and Service
- FAQ (Frequently Asked Questions)
- FIRE OR EXPLOSION HAZARD
- Safety
- COMPRESSOR CYCLING
- MODEL OPTIONS
- UNIT FEATURE OPTIONS
- General Information
- of Per Circuit
- of Per Circuit
- SEALING ELECTRICAL ENTRIES
- 3-PHASE ROTATION
- 1 Simple Green Simple Green is available from AAON Parts and Supply (Part
- 2 Water Flush This procedure can be used when the only material to cause the
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AAON CF Series Condensers and Condensing Units
Specifications
- Product Name: CF Series Condenser and Condensing Units
- Model Number: V04410
- UL Certification: UL-60335
- Installation, Operation, & Maintenance Manual: Included
Product Information
The CF Series Condenser and Condensing Units are designed to provide efficient cooling and refrigeration for various applications. These units are UL-60335 certified, ensuring safety and reliability. The product features and options include:
Condenser Fans
The CF Series units are equipped with high-performance condenser fans that
provide optimal airflow for efficient heat transfer. These fans are designed
for quiet operation and long-lasting performance.
Outside Air
The units are capable of incorporating outside air into the cooling
process, allowing for improved ventilation and fresh air exchange. This
feature is particularly useful in applications where air quality is a concern.
Air (MUA), Variable Air Volume (VAV), and Single Zone Variable Air
Volume (SZ VAV)
The CF Series units can accommodate different air handling systems,
including Makeup Air (MUA), Variable Air Volume (VAV), and Single Zone
Variable Air Volume (SZ VAV). This flexibility allows for compatibility with
various building configurations and HVAC setups.
Product Usage Instructions
Safety Precautions
Before using the CF Series Condenser and Condensing Units, it is important
to follow these safety precautions:
- Read and understand the installation, operation, and service instructions provided in the manual.
- Ensure proper installation, adjustment, alteration, service, and maintenance to prevent injury, death, or property damage.
- Keep a copy of the Installation, Operation, & Maintenance (IOM) manual with the unit at all times.
- Avoid storing gasoline or other flammable vapors and liquids near the appliance.
Startup and Service
Startup and service procedures should only be performed by a Factory Trained Service Technician. Follow these steps:
- Ensure that the unit is disconnected from the power source before servicing.
- Label all wires before disconnecting when servicing controls, and reconnect them correctly.
- After servicing, verify proper operation and secure all doors with a key-lock or nut and bolt.
Electrical Safety
To avoid electric shock hazards, follow these precautions:
- Before servicing, shut off all electrical power to the unit, including remote disconnects.
- Follow proper Lockout-Tagout procedures to prevent injuries from rotating parts.
Fire, Explosion, or Carbon Monoxide Poisoning Hazard
To prevent fire, explosion, or carbon monoxide poisoning, adhere to the
following guidelines:
- Replace controls with proper ones to avoid hazardous situations.
- Avoid storing or using gasoline or other flammable vapors and liquids near the appliance.
FAQ (Frequently Asked Questions)
Q: Who should perform startup and service procedures for the CF Series
units?
A: Startup and service must be performed by a Factory Trained Service
Technician to ensure proper installation and maintenance.
Q: How should I handle electrical safety when servicing the unit?
A: Before servicing, make sure to shut off all electrical power to the
unit, including remote disconnects. Follow proper Lockout-Tagout procedures to
prevent electric shock hazards and injuries.
Q: Can I store flammable liquids near the CF Series units?
A: No, it is important to avoid storing gasoline or other flammable vapors
and liquids near the appliance to prevent fire hazards.
CF Series
Condenser and Condensing Units
UL-60335
Installation, Operation, & Maintenance
WARNING
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury,
death or property damage.
Be sure to read and understand the installation, operation and service
instructions in this manual.
Improper installation, adjustment, alteration, service or maintenance can
cause serious injury, death or property damage.
Keep a copy of this IOM with the unit.
o Do not store gasoline or other flammable vapors and liquids in the vicinity
of this or any other appliance
o WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance. Do not touch
any electrical switch; do not use any phone in your building. Leave the
building immediately. Immediately call your gas supplier from a phone remote
from the building. Follow the gas supplier’s instructions. If you cannot reach
your gas supplier, call the fire department.
o Startup and service must be performed by a Factory Trained Service
Technician.
AAON CF Series Features and Options Introduction
Energy Efficiency · Two-Stage, 10-100% Variable Capacity,
or Tandem R-410A Scroll Compressors · Air-Source Heat Pump · VFD Controlled
and ECM Driven
Condenser Fans
Humidity Control · Modulating Hot Gas Reheat · Makeup Air Applications up to
100%
Outside Air
Safety · Phase and Brownout Protection · Single Point Non-Fused Disconnect
Power Switch · Automatic Low Pressure and Manual
Reset High Pressure Safety Cut-outs · Adjustable Compressor Lockout
Installation and Maintenance · Isolated Controls and Compressor
Compartment · Access Doors with Full Length Stainless
Steel Piano Hinges · Molded Lockable Handles · Color-Coded Wiring Diagrams ·
Run Test Report and Installation Manual
Included in Controls Compartment · Factory Installed Convenience Outlet ·
Service Access Lights · Remote Start/Stop Terminals · Liquid Line Sight Glass
· Compressor Isolation Valves
System Integration · Complete Split System with AAON DX
Air Handling Units · Remote Air-Cooled Condenser Option · Labeled Split System
Piping Stub Outs
with Shut-Off Valves · Flooded Condenser 0°F Low Ambient
Controls · Terminal Block for Thermostat with
Isolation Relays · Constant Air Volume (CAV), Makeup
Air (MUA), Variable Air Volume (VAV), and Single Zone Variable Air Volume (SZ
VAV)
Environmentally Friendly · R-410A Refrigerant
Extended Life · Optional 5 Year Compressor Warranty · G90 Galvanized Steel
Construction · 2,500 Hour Salt Spray Tested Exterior
Corrosion Protection · 10,000 Hour Salt Spray Tested Polymer
E-Coated Condenser Coils · Condenser Coil Guards · Custom Color Paint Options
4
Safety
Attention must be paid to the following statements: NOTE – Notes are intended
to clarify the unit installation, operation and maintenance.
CAUTION – Caution statements are given to prevent actions that may result in
equipment damage, property damage, or personal injury.
WARNING – Warning statements are given to prevent actions that could result in
equipment damage, property damage, personal injury or death.
DANGER – Danger statements are given to prevent actions that will result in
equipment damage, property damage, severe personal injury or death.
WARNING
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation,
serious injury, death or property damage.
Improper servicing could result in dangerous operation, serious injury, death
or property damage.
Before servicing, disconnect all electrical power to the furnace. More than
one disconnect may be provided.
When servicing controls, label all wires prior to disconnecting. Reconnect
wires correctly.
Verify proper operation after servicing. Secure all doors with key-lock or nut
and bolt.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Startup and service
must be performed by a Factory Trained Service Technician. A copy of this IOM
must be kept with the unit.
WARNING
ELECTRIC SHOCK
Electric shock hazard. Before servicing, shut off all electrical power to the
unit, including remote disconnects, to avoid shock hazard or injury from
rotating parts. Follow proper Lockout-Tagout procedures.
5
WARNING
FIRE, EXPLOSION OR CARBON MONOXIDE POISONING HAZARD
Failure to replace proper controls could result in fire, explosion or carbon
monoxide poisoning. Failure to follow safety warnings exactly could result in
serious injury, death or property damage. Do not store or use gasoline or
other flammable vapors and liquids in the vicinity of this appliance.
WARNING
LIVE ELECTRICAL
During installation, testing, servicing, and troubleshooting of the equipment
it may be necessary to work with live electrical components. Only a qualified
licensed electrician or individual properly trained in handling live
electrical components shall perform these tasks.
Standard NFPA-70E, an OSHA regulation requiring an Arc Flash Boundary to be
field established and marked for identification of where appropriate Personal
Protective Equipment (PPE) be worn, must be followed.
WARNING
GROUNDING REQUIRED
All field installed wiring must be completed by qualified personnel. Field
installed wiring must comply with NEC/CEC, local and state electrical code
requirements. Failure to follow code requirements could result in serious
injury or death. Provide proper unit ground in accordance with these code
requirements.
WARNING
ROTATING COMPONENTS
Unit contains fans with moving parts that can cause serious injury. Do not
remove grill containing fans until the power to the unit has been disconnected
and fan has stopped rotating.
WARNING
VARIABLE FREQUENCY DRIVES
Do not leave VFDs unattended in hand mode or manual bypass. Damage to
personnel or equipment can occur if left unattended. When in hand mode or
manual bypass mode VFDs will not respond to controls or alarms.
6
CAUTION
VARIABLE FREQUENCY DRIVES
Electric motor over-current protection and overload protection may be a
function of the Variable Frequency Drive to which the motors are wired. Never
defeat the VFD motor overload feature. The overload ampere setting must not
exceed 115% of the electric motors FLA rating as shown on the motor nameplate.
CAUTION
3-PHASE ROTATION
Rotation must be checked on all
MOTORS AND COMPRESSORS of 3
phase units at startup by a qualified
service
technician.
Scroll
compressors are directional and can
be damaged if rotated in the wrong
direction. Compressor rotation must
be checked using suction and
discharge gauges. Fan motor rotation
must be checked for proper operation.
Alterations must only be made at the
unit power connection
WARNING
UNIT HANDLING
To prevent injury or death lifting equipment capacity shall exceed unit weight
by an adequate safety factor. Always test-lift unit not more than 24 inches
high to verify proper center of gravity lift point to avoid unit damage,
injury or death.
CAUTION
DOOR LATCHES Door compartments containing hazardous voltage or rotating parts
are equipped with door latches that allow locks. Door latches are shipped with
a nut and bolt requiring tooled access. If the shipping hardware is not
replaced with a pad lock, always reinstall the nut and bolt after closing the
door to maintain tooled access.
WARNING
LEAK TESTING Do not use oxygen, acetylene or air in place of refrigerant and
dry nitrogen for leak testing. A violent explosion may result causing injury
or death.
CAUTION
PVC PIPING PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride)
are vulnerable to attack by certain chemicals. Polyolester (POE) oils used
with R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC
piping system will result in stress cracking of the piping and fittings and
complete piping system failure.
7
CAUTION
COMPRESSOR LUBRICANT Polyolester (POE) and Polyvinylether (PVE) oils are two
types of lubricants used in hydrofluorocarbon (HFC) refrigeration systems.
Refer to the compressor label for the proper compressor lubricant type.
CAUTION
COIL CLEANERS To prevent damage to the unit, do not use acidic chemical coil
cleaners. Do not use alkaline chemical coil cleaners with a pH value greater
than 8.5, after mixing, without first using an aluminum corrosion inhibitor in
the cleaning solution.
WARNING
COIL CLEANERS Some chemical coil cleaning compounds are caustic or toxic. Use
these substances only in accordance with the manufacturer’s usage
instructions. Failure to follow instructions may result in equipment damage,
injury or death.
8
CAUTION
COIL CLEANING Do not clean DX refrigerant coils with hot water or steam. The
use of hot water or steam on refrigerant coils will cause high pressure inside
the coil tubing and damage to the coil.
WARNING
ENCLOSED AREA Do not work in an enclosed area where refrigerant or nitrogen
gases may be leaking. A sufficient quantity of vapors may be present and cause
injury or death.
WARNING
CONVENIENCE OUTLETS
Factory installed convenience outlets are not intended for use while the unit
is operating.
CAUTION
Unit power supply wire must be only copper or aluminum.
CAUTION
In order to avoid a hazard due to inadvertent resetting of the THERMAL CUT-
OUT, this appliance must not be supplied through an external switching device,
such as a timer, or connected to a circuit that is regularly switched on and
off by the utility.
WARNING
This appliance is not intended for use by persons with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instruction concerning use of the
appliance by a person responsible for their safety. Children must be
supervised to ensure they do not play with this appliance.
WARNING
Units
with
VFD
driven
motors/compressors have adjustable
overload settings. These are set by
the AAON factory for the protection of
these motors/compressors and must
not be adjusted over this factory
setpoint or bypassed.
WARNING
COMPRESSOR CYCLING
MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle
off for a minimum of 3 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must
cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 7 starts per hour.
1. Startup and service must be performed by a Factory Trained Service
Technician.
2. The unit is for outdoor use only. See General Information section for more
information.
3. Every unit has a unique equipment nameplate with electrical, operational,
and unit clearance specifications. Always refer to the unit nameplate for
specific ratings unique to the model purchased.
4. READ THE ENTIRE INSTALLATION, OPERATION AND MAINTENANCE MANUAL. OTHER
IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL.
5. Keep this manual and all literature safeguarded near or on the unit.
9
CF Series Feature String Nomenclature
Model Options
:
Unit Feature Options
1 5
1 4
1 3
1 2
1 1
1 0
8 A 8 B 8 C 8 D
6 A 6 B 6 C
3 A 3 B
2 A 2 B
A 1 A 2 A 3 A 4 A 5
VL T
MNRE V
SERIES
SIZ E
GE N MJREV
9
7
4 5
1
2 2
CF A – 015 – A – 0 – 3 – D A 0 0 K : 0 – A 0 – E 0 – C 0 – A J 0 – D – B A 0 0
– 0 0 A 0 E 0 0
0 0 0 0 0DB
2 1
2 0
1 9
1 8
1 7
1 6
CF Series Feature String No menclature
MODEL OPTIONS
Series and Generation CF
Major Revision A
Unit Size 002 = 2 ton Capacity 003 = 3 ton Capacity 004 = 4 ton Capacity 005 =
5 ton Capacity 006 = 6 ton Capacity (Obsolete) 007 = 7 ton Capacity 009 = 9
ton Capacity 011 = 11 ton Capacity 013 = 13 ton Capacity 015 = 15 ton Capacity
016 = 16 ton Capacity 018 = 18 ton Capacity 020 = 20 ton Capacity 025 = 25 ton
Capacity 026 = 26 ton Capacity 030 = 30 ton Capacity 031 = 31 ton Capacity 040
= 40 ton Capacity 050 = 50 ton Capacity 060 = 60 ton Capacity 070 = 70 ton
Capacity
Series A = 2-7 ton units B = 9-15 ton units C = 16-25 & 30 ton units D = 26 &
31-70 ton units
Minor Revision A
Voltage 1 = 230V/1/60Hz 2 = 230V/3/60Hz 3 = 460V/3/60Hz 4 = 575V/3/60Hz 8 =
208V/3/60Hz 9 = 208V/1/60Hz
A1: Compressor Style 0 = Air-Cooled Condenser – No Compressors
(1 Circuit) A = R-410A Scroll Compressors B = R-410A Two-Stage Capacity Scroll
Compressors D = R-410A Variable Capacity Scroll Compressors E = R-410A Tandem
Scroll Compressors G = R-410A Tandem Variable Capacity Scroll
Compressors P = Air-Cooled Condenser – No Compressors
(2 Circuits) Q = Air-Cooled Condenser – No Compressors
(4 Circuits)
A2: Condenser Style A = Air-Cooled Microchannel Condenser C = Air-Cooled
Condenser (Fin and Tube) (Obsolete) J = Air-Source Heat Pump (Fin and Tube)
A3: Configuration 0 = Standard
A4: Coating 0 = Standard E = Polymer E-Coated Condenser Coil F = Stainless
Steel Casing (Obsolete) G = Copper Fin + Stainless Steel Casing (Obsolete) H =
Option E + F (Obsolete)
A5: Staging 0 = No Cooling G = 1 On/Off Refrigeration System H = 1 Variable
Capacity Refrigeration System J = 2 On/Off Refrigeration Systems K = 1
Variable Capacity Refrigeration System + 1
On/Off Refrigeration System L = 2 Variable Capacity Refrigeration System M = 2
Two-Stage Refrigeration System N = 1 Variable Capacity Refrigeration System +
1
Two-Stage Refrigeration System R = 4 On/Off Refrigeration Systems T = 2
Variable Capacity Refrigeration Systems + 2
On/Off Refrigeration Systems U = 4 Variable Capacity Refrigeration Systems
10
CF Series Feature String Nomenclature
Model Options
:
Unit Feature Options
1 5
1 4
1 3
1 2
1 1
1 0
8 A 8 B 8 C 8 D
6 A 6 B 6 C
3 A 3 B
2 A 2 B
A 1 A 2 A 3 A 4 A 5
VL T
MNREV
SERIES
SIZ E
GE N MJREV
9
7
4 5
1
2 2
CF A – 015 – B – 0 – 3 – D A 0 0 K : 0 – A 0 – E 0 – C 0 – A N 0 – B – DE0 0 – 0 0A0 E 0 0 0 0 0 0 0 DB
2 1
2 0
1 9
1 8
1 7
1 6
UNIT FEATURE OPTIONS
1: Unit Orientation 0 = Vertical Condenser Discharge – Standard Access A =
Horizontal Condenser Discharge – Standard
Access
2A: Refrigeration Control 0 = Standard A = 5 Minute Compressor Off Timer + 20
Second
Compressor Stage Delay B = Fan Cycling (Obsolete) C = Adjustable Fan Cycling D
= Adjustable Compressor Lockout E = Freeze Stats (each circuit) (Obsolete) F =
Option A + B (Obsolete) G = Option A + C H = Option A + D J = Option A + E
(Obsolete) K = Option B + D (Obsolete) L = Option B + E (Obsolete) M = Option
C + D N = Option C + E (Obsolete) P = Option D + E (Obsolete) Q = Option A + B
- D (Obsolete) R = Option A + B + E (Obsolete) S = Option B + D + E (Obsolete)
T = Option C + D + E (Obsolete) U = Option A + B + D + E (Obsolete) V = Option
A + C + D + E (Obsolete) W = Option A + C + D
2B: Blank 0 = Standard
3A: Refrigeration Options 0 = Standard A = Hot Gas Bypass Lead Stage [HGB] B = HGB Lead + HGB Lag C = On/Off Hot Gas Reheat [HGR] (Obsolete) D = Hot Gas Bypass Non-Variable Capacity
Refrigeration Systems [HGBNV] E = Modulating Hot Gas Reheat [MHGR] F = HGB Lead + HGR (Obsolete) G = HGB Lead + HGB Lag + HGR (Obsolete) H = HGB + MHGR J = HGB Lead + HGB Lag + MHGR
3A: Refrigeration Options Continued K = HGBNV + HGR (Obsolete) L = HGBNV +
MHGR M = HGB Lag (Obsolete) N = HGB Lag + MHGR (Obsolete)
3B: Blank 0 = Standard
4: Refrigeration Accessories 0 = Standard A = Sight Glass B = Compressor
Isolation Valves C = Options A + B D = Flooded Condenser 0°F Low Ambient
Controls
One Circuit E = Options A + D F = Options B + D G = Options A + B + D H =
Flooded Condenser 0°F Low Ambient Controls-
Two Circuits J = Options A + H K = Options B + H L = Options A + B + H R =
Flooded Condenser 0°F Low Ambient Controls
Four Circuits S = Options A + R T = Options B + R U = Options A + B + R
5: Blank 0 = Standard
6A: Unit Disconnect Type 0 = Single Point Power Block A = Single Point Power
Non-Fused Disconnect
6B: Disconnect 1 Size 0 = Standard N = 100 amps R = 150 amps V = 250 amps Z =
400 amps
6C: Blank 0 = Standard
11
CF Series Feature String Nomenclature
Model Options
:
Unit Feature Options
1 5
1 4
1 3
1 2
1 1
1 0
8 A 8 B 8 C 8 D
6 A 6 B 6 C
3 A 3 B
2 A 2 B
A 1 A 2 A 3 A 4 A 5
VL T
MNREV
SERIES
SIZ E
GE N MJREV
9
7
4 5
1
2 2
CF A – 015 – B – A – 3 – D A 0 0 K : 0 – A 0 – E 0 – C0 – AN0 – B – D E 0 0 –
0 0 A 0 E 0 0
0 0 0 0 0DB
2 1
2 0
1 9
1 8
1 7
1 6
7: Accessories 0 = Standard A = Suction Pressure Transducer on Lead
Refrigeration Circuit (Obsolete) B = Phase & Brown Out Protection D = Suction
Pressure Transducer on Each
Refrigeration Circuit E = Compressor Sound Blanket F = Options A + B
(Obsolete) J = Options A + E (Obsolete) L = Options B + D M = Options B + E Q
= Options D + E T = Options A + B + E (Obsolete) 1 = Options B + D + E
8A: Control Sequence A = Terminal Block for Thermostat w/ Isolation
Relays D = VAV Unit Controller – VAV Cool + CAV Heat E = CAV Unit Controller F
= Makeup Air Unit Controller – CAV Cool + CAV
Heat H = Constant Volume HP Unit Controller – CAV
Cool + CAV Heat J = Makeup Air HP Unit Controller – CAV Cool +
CAV Heat N = Field Installed DDC Controls by Others with
Isolation Relays
8B: Control Suppliers 0 = Standard Terminal Block C = Orion VCM-X (Main
Controller in Air Handling
Unit) (Obsolete) E = Orion VCC-X (Main Controller in Air Handling
Unit) H = AAON Touchscreen Controller (Main Controller
in Air Handling Unit) (Obsolete) J = AAON Refrigeration System Supervisory
Controls
8C: Control Supplier Options 0 = Standard
8D: BMS Connection & Diagnostics 0 = Standard
9: Blank 0 = Standard
10: Blank 0 = Standard
11: Maintenance Accessories 0 = Standard A = Factory Wired 115VAC Convenience
Outlet B = Field Wired 115VAC Convenience Outlet C = Service Lights E = Remote
Unit Start/Stop Terminals F = Options A + C H = Options A + E J = Options B +
C L = Options B + E N = Options C + E R = Options A + C + E U = Options B + C
- E
12: Code Options 0 = Standard ETL USA Listing B = ETL USA + Canada Listing
13: Air-Cooled Condenser Accessories 0 = Standard A = Condenser Coil Guard C = ECM Condenser Fan Head Pressure Control E = VFD Condenser Fan Head Pressure Control G = Options A + C J = Options A + E K = Low Sound Condenser Fan (Obsolete) L = Options A + K (Obsolete) N = Options C + K (Obsolete) S = Options A + C + K (Obsolete)
14: Blank 0 = Standard
15: Blank 0 = Standard
16: Electrical Options 0 = Standard 5 kAIC C = 10 kAIC
12
1 5
2 2
CF Series Feature String Nomenclature
Model Options
:
Unit Feature Options
1 4
1 3
1 2
1 1
1 0
8 A 8 B 8 C 8 D
6 A 6 B 6 C
3 A 3 B
2 A 2 B
A 1 A 2 A 3 A 4 A 5
VL T
MNREV
SERIES
SIZ E
GE N MJREV
9
7
4 5
1
2 1
2 0
1 9
1 8
1 7
1 6
CF A – 015 – B – A – 3 – D C 0 0 K : 0 – A 0 – E 0 – C 0 – A N 0 – B – DE0 0 –
0 0 A0 E0 0 0 0 0 0 0 DB
17: Shipping Options 0 = Standard A = Crating B = Export Crating
18: Blank 0 = Standard
19: Blank 0 = Standard
20: Cabinet Material 0 = Galvanized Steel Cabinet
21: Warranty 0 = Standard D = Compressor Warranty – Years 2-5
22: Type B = Premium AAON Gray Paint Exterior E = Premium AAON Gray Paint Ext
- Shrink Wrap X = SPA + Premium AAON Gray Paint Exterior 1 = SPA + Premium
AAON Gray Paint Exterior +
Shrink Wrap
13
General Information
AAON CF Series air-cooled condensers and condensing units have been designed
for outdoor use only. They are factory assembled, wired, charged, and run-
tested.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Installation and
service must be performed by a Factory Trained Service Technician.
WARNING
SHARP EDGES
Coils and sheet metal surfaces present sharp edges and care must be taken when
working with equipment.
WARNING
Failure to observe the following instructions will result in premature failure
of your system and possible voiding of the warranty.
Codes and Ordinances CF Series units have been tested and certified, by ETL,
in accordance with UL Safety Standard 60335-2-40 4th Edition, ANSI Safety
Standard Z21.47-2016.
System must be sized in accordance with the American Society of Heating,
Refrigeration and Air Conditioning Engineers Handbook.
Installation of CF Series units must conform to the ICC standards of the
International Mechanical Code, the International Building Code, and local
building, plumbing and electrical codes. All appliances must be electrically
grounded in accordance with local codes, or in the absence of local codes, the
current National Electric Code, ANSI/NFPA 70 or the current Canadian
Electrical Code CSA C22.1.
Receiving Unit When received, check the unit for damage that might have
occurred in transit. If damage is found it must be noted on the carrier’s
freight bill. A request for inspection by carrier’s agent must be made in
writing at once. Check the nameplate to ensure the correct model sizes and
voltages have been received to match the job requirements.
If repairs must be made to damaged goods, then the factory must be notified
before any repair action is taken in order to protect the warranty. Certain
equipment alteration, repair, and manipulation of equipment without the
manufacturer’s consent may void the product warranty. Contact AAON Technical
Support for assistance with handling damaged goods, repairs, and freight
claims: 918-382-6450.
14
Storage If installation will not occur immediately following delivery, store
equipment in a dry protected area away from construction traffic and in the
proper orientation as marked on the packaging with all internal packaging in
place. Secure all loose-shipped items.
CAUTION
CLEAN AIR ACT
The Clean Air Act of 1990 bans the intentional venting of refrigerant as of
July 1, 1992. Approved methods of recovery, recycling, or reclaiming must be
followed.
Failure to observe the following instructions will result in premature failure
of your system, and possible voiding of the warranty.
CAUTION
CRANKCASE HEATER OPERATION
Units are equipped with compressor crankcase heaters, which must be energized
at least 24 hours prior to cooling operation, to clear any liquid refrigerant
from the compressors.
Never turn off the main power supply to the unit, except for complete
shutdown. When power is cut off from the unit, any compressors using crankcase
heaters cannot prevent refrigerant migration. This means the compressor will
cool down, and liquid refrigerant may accumulate in the compressor. The
compressor is designed to pump refrigerant gas and damage may occur if liquid
enters the compressor when power is restored.
CAUTION
3-PHASE ROTATION
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units.
All motors, to include and not be limited to pump motors and condenser fan
motors, must all be checked by a qualified service technician at startup and
any wiring alteration must only be made at the unit power connection.
Before unit operation, the main power switch must be turned on for at least
twenty-four hours for units with compressor crankcase heaters. This will give
the crankcase heater time to clear any liquid accumulation out of the
compressor before it is required to run.
Always control the system from the control panel, never at the main power
supply (except for emergency or for complete shutdown of the system).
15
CAUTION
COMPRESSOR ROTATION
Scroll compressors are directional and will be damaged by operation in the
wrong direction. Low pressure switches on compressors have been disconnected
after factory testing. Rotation must be checked by a qualified service
technician at startup using suction and discharge pressure gauges and any
wiring alteration must only be made at the unit power connection.
The standard compressors must be on a minimum of 5 minutes and off for a
minimum of 3 minutes. The cycle rate must be no more than 7 starts per hour.
WARNING
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle
off for a minimum of 3 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must
cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 7 starts per hour.
The compressor life will be seriously shortened by reduced lubrication, and
the pumping of excessive amounts of liquid oil and liquid refrigerant.
Wiring Diagrams Unit specific wiring diagrams are laminated and affixed inside
the controls compartment door.
General Maintenance When the initial startup is made, and on a periodic
schedule during operation, it is necessary to perform routine service checks
on the performance of the condensing unit. This includes reading and recording
suction pressures and checking for normal subcooling and superheat.
16
Installation
Forklifting the Unit CF Series condensing unit sizes 2-25 & 30 tons can be
lifted using a forklift. 2-7 ton units must have forks at least 1.2 m (48″) in
length. 9-25 & 30 ton units must have forks 1.8 m (72″) in length, or the
forks must have 1.8 m (72″) fork extensions. Standard units can be lifted from
all sides except the condenser coil side. CF Series condensing unit sizes 26 &
31-70 tons cannot be lifted using a forklift. They can be lifted as shown in
Figure 3.
Forks must be perpendicular to the unit and they must be in far enough that
the back of the forks are no more than 15.25 cm (6″) away from the edge of the
unit.
CAUTION
FORKLIFTING 2-7 TON UNITS
Forks or Fork Extensions must be at least 1.2 m (48″) in length.
CAUTION
FORKLIFTING 9-25 & 30 TON UNITS
Forks or Fork Extensions must be at least 1.8 m (72″) in length.
Figure 1 – Forklifting a CF Series A Cabinet
Figure 2 – Forklifting a CF Series B and C Cabinet
17
Lifting the Unit If cables or chains are used to hoist the unit they must be
the same length. Minimum cable length is 251.5 cm (99″) for CF Series 9-70 ton
units. CF Series 2-7 ton units do not include factory installed lifting lugs
and must be lifted by forklift only. Care must be taken to prevent damage to
the cabinet, coils, and condenser fans. Before lifting unit, be sure that all
shipping material has been removed from unit. Secure hooks and cables at all
lifting points / lugs provided on the unit.
Figure 3 – Lifting Details and Orientation of a CF Series 9-70 ton Condensing
Unit
Locating the Unit The CF Series condenser and condensing unit is designed for
outdoor applications and mounting at ground level or on a rooftop. It must be
placed on a level and solid foundation that has been prepared to support its
weight. When installed at ground level, a one-piece concrete slab must be used
with footings that extend below the frost line. Also
18
with ground level installation, care must be taken to protect the coil fins from damage due to vandalism or other causes.
The first clearance table below gives the clearance values for proper unit operation. The second clearance table gives the clearance necessary for removing the coil without disassembling a large part of the condensing unit. For ease of removing the condenser coil, use the second table clearances for the right hand side of the unit.
Table 1 – Clearances for Proper Operation
Unit Size
Location 2-7 tons
9-70 tons
cm (in.)
cm (in.)
Front –
(Controls Unobstructed 91.4 (36)
Side)
Left Side 15.25 (6)
76.2 (30)
Right Side 15.25 (6)
91.4 (36)
Top
7.6 (3) Unobstructed
Back
45.7 (18)
15.25 (6)
Table 2 – Clearances for Coil Pull
Unit Size
Right Hand Side
cm (in.)
2-7 tons
106.7 (42)
9-15 tons
106.7 (42)
16-25 & 30 tons
137.2 (54)
26 & 31-70 tons
167.6 (66)
Figure 4 – Orientation of Series 2-7 ton Condensing Unit
The placement relative to the building air intakes and other structures must
be carefully selected. Airflow to and from the condenser or condensing unit
must not be restricted to prevent a decrease in performance and efficiency.
The installation position for 9-70 ton units must provide at least 76.2 cm
(30″) of left and right side clearance for proper airflow to the condenser
coils. When units are mounted adjacent to each other, the minimum right and
left side clearance required between the units is 152.4 cm (60″) or 1.5 meters
(5 feet). Similarly, when 2-7 ton units are mounted adjacent to each other,
the minimum clearance required between the back side of the units is 91.4 cm
(36″) or 0.9 meters (3 feet).
Units must not be installed in an enclosure or pit that is deeper than the
height of the unit. When recessed installation is necessary, the clearance to
maintain proper airflow is at least 1.5 meters (5 feet) (0.9 meters [3 feet]
for 2-7tons).
CF Series condensers and condensing units that have a vertical air discharge
must have no obstruction above the equipment. Do not place the unit under an
overhang. CF Series condensers and condensing units that have a horizontal
discharge must have no obstruction in front of the unit.
For proper unit operation, the immediate area around condenser must remain
free of debris that may be drawn in and obstruct airflow in the condensing
section.
Consideration must be given to obstruction caused by snow accumulation when
placing the unit.
Mounting Isolation For roof mounted applications or anytime vibration
transmission is a factor, vibration isolators may be used. When vibration
isolators are used, the CF Series unit must be directly mounted either on a
flat platform or on support rails running front to back and at least 2.5 cm
(1″) wider than the unit base rail. If the CF is mounted on the support rails,
the additional width of the support rail must be on the inside of the unit
such that the support rail fully covers the corner connections of the unit
base rail. Any isolation must be applied to the platform or support rails. DO
NOT put spring isolation on the base of the CF Series Condensing Unit.
Access Doors Access doors are provided to the compressor and electrical
compartment.
CAUTION
PVC PIPING
PVC (Polyvinyl Chloride) and CPVC (Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain chemicals. Polyolester (POE) oils used with
R-410A and other refrigerants, even in trace amounts, in a PVC or CPVC piping
system will result in stress cracking of the piping and fittings and complete
piping system failure.
Standard Evacuation Instructions: Proper system evacuation is critical to
remove moisture and non-condensables from the system before charging the
system with refrigerant. A newly installed AAON condensing unit has already
been evacuated and charged with some refrigerant at the factory. When
evacuating a new system,
19
keep the condensing unit service valves closed and evacuate the suction and
liquid lines and the air handling unit. If the entire system must be
evacuated, use the following procedure to ensure the entire system is pulled
into a good vacuum.
1. System evacuation must be performed anytime a system is open to
atmospheric pressure. The POE oils used with R-410A are extremely hydroscopic
in nature and immediately begin pulling in moisture once the system is opened
to the atmosphere.
2. Before starting to evacuate the system, you MUST ensure that there are no
leaks by pressurizing the system with 2758 kpa (400 psig) of dry nitrogen and
verifying no pressure loss after one hour.
3. Four valve manifold gauge sets are more effective than standard manifold
gauge sets due to the extra hose port in combination with a 9.5 mm (3/8”)
evacuation port. The larger diameter evacuation port will expedite system
evacuation.
4. Connect the manifold set to the condensing unit with one hose on the
suction line service valve, one hose on the liquid line service valve and if
an extra Schrader valve is field installed on the suction line, connect a
third hose (not shown). The vacuum pump must be connected to the manifold set
using a 9.5 mm (3/8″) vacuum rated hose. Figure 5 shows two circuits. Both
circuits must be evacuated separately.
Figure 5 – CU evacuation connections
5. An accurate micron gauge must be used and checked by pulling a vacuum on
the gauge by itself and verify a rapid drop to less than 100 microns within a
few minutes.
6. Do not attach the micron gauge to the system until the gauge manifold is
reading 71 cm (28″) of vacuum to ensure the micron gauge does not see pressure
and is thus damaged. MICRON GAUGES WILL BE DAMAGED BY PRESSURE!!!
7. It is a good practice to replace the vacuum pump oil after one hour of the
evacuation process. The oil can be broken down in the pump in the initial
first hour causing system evacuation to take longer than it should.
8. The minimum micron level required by AAON is 350 microns for systems using
POE oils.
9. The system must then be isolated and the pump turned off to check for
vacuum rise due to leaks or moisture in the system. The micron gauge must not
rise above 500 microns after 30 minutes of wait time.
20
Low Ambient & Modulating Reheat System Evacuation Instructions: Proper system
evacuation is critical to remove moisture and non-condensables from the system
before charging the system with refrigerant. Systems with low ambient flooded
condenser option require the following procedure to ensure the entire system
is pulled into a good vacuum.
1. System evacuation must be performed anytime a system is open to
atmospheric pressure. The POE oils used with R-410A are extremely hydroscopic
in nature and immediately begin pulling in moisture once the system is opened
to the atmosphere.
2. Open the reheat valve to 50% when evacuating.
3. Before starting to evacuate the system, you MUST ensure that there are no
leaks by pressurizing the system with 2758 kPa (400 psig) of dry nitrogen and
verifying no pressure loss after one hour.
4. Four valve manifold gauge sets are more effective than standard manifold
gauge sets due to the extra hose port in combination with a 9.5 mm (3/8″)
evacuation port. The larger diameter evacuation port will expedite system
evacuation.
5. Connect the manifold set to the condensing unit with one hose on the
suction line service valve, one hose on the liquid line service valve and a
third hose on the reheat line service valve. The vacuum pump must be connected
to the manifold set using a 9.5 mm (3/8″) vacuum rated hose. Figure 6 shows
two circuits. The first circuit has a reheat line, the second circuit is just
the suction
and liquid line. Both circuits must be evacuated separately. 6. FAILURE to
connect to the liquid line service valve will result in the receiver tank not
being fully evacuated and most likely lead to noncondensables in the system.
7. An accurate micron gauge must be used and checked by pulling a vacuum on
the gauge by itself and verify a rapid drop to less than 100 microns within a
few minutes.
Figure 6 – CU evacuation connections
8. Do not attach the micron gauge to the system until the gauge manifold is
reading 71 cm (28″) of vacuum to ensure the micron gauge does not see pressure
and is thus damaged. MICRON GAUGES WILL BE DAMAGED BY PRESSURE!!! 9. It is a
good practice to replace the vacuum pump oil after one hour of the evacuation
process. The oil can be
21
broken down in the pump in the initial first hour causing system evacuation to
take longer than it should.
10. The minimum micron level required by AAON is 350 microns for systems
using POE oils.
11. The system must then be isolated and the pump turned off to check for
vacuum rise due to leaks or moisture in the system. The micron gauge must not
rise above 500 microns after 30 minutes of wait time.
Adjusting Refrigerant Charge All AAON CF Series condensers and condensing
units are shipped with a factory holding charge. The factory charge is
different depending on the unit size and system (heat pump, modulating hot gas
reheat, LAC). The factory charge per circuit is shown on the unit nameplate.
Adjusting the charge of the system will be required during installation.
Adjusting the charge of a system in the field must be based on determination
of liquid subcooling and evaporator superheat. On a system with a thermostatic
expansion valve liquid sub-cooling is more representative of the charge than
evaporator superheat but both measurements must be taken.
CAUTION
COMPRESSOR LUBRICANT
Polyolester (POE) and Polyvinylether (PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC) refrigeration systems. Refer to the compressor
label for the proper compressor lubricant type.
CAUTION
CLEAN AIR ACT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFC’s
and HCFC’s) as of July 1, 1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration may be levied for non-
compliance.
Before Charging Refer to the Unit Nameplate to determine which refrigerant
must be used to charge the system.
Unit being charged must be at or near full load conditions before adjusting
the charge.
Units equipped with hot gas bypass must have the hot gas bypass valve closed
to get the proper charge.
Units equipped with hot gas reheat must be charged with the hot gas reheat
valve closed while the unit is in cooling mode. After charging, operate the
unit in reheat (dehumidification) mode to check for correct operation.
Units equipped with heat pump options must be charged in cooling mode to get
the proper charge. After charging, operate the unit in heating mode to check
for correct charge. Charge may need to be adjusted for heating mode. If
adjustments are made in the heating mode, cooling mode must be rerun to verify
proper operation.
After adding or removing charge, the system must be allowed to stabilize,
typically 10-15 minutes, before making any other adjustments.
22
Table 3 – Acceptable Fin & Tube Refrigeration Circuit Values
Cooling Only Unit4
Cooling Only Unit with Hot Gas Reheat1,4
Heat PumpUnit2,4
Heat Pump Unit with Hot Gas Reheat3,4
Cooling Only Unit with LAC4
Cooling Only Unit with Hot Gas Reheat
& LAC4
Cooling Mode Liquid Sub-Cooling Values (°C)
4.4 – 8.3 2.8 – 8.3 1.1 – 2.2 1.1 – 3.3
4.4 – 8.3
4.4 – 8.3
Cooling Mode Liquid Sub-Cooling Values (°F)
8-15 5-15 2-4 2-6
8-15
8-15
The type of unit and options determine the ranges for liquid sub-cooling and evaporator superheat. Refer to Table 3 when determining the proper sub- cooling.
For units equipped with low ambient (-17.2°C [0°F]) option see the special charging instructions at the end of this section.
Checking Liquid Sub-cooling Measure the temperature of the liquid line as it leaves the condenser coil.
Read the gauge pressure at the liquid line close to the point where the temperature was taken. You must use liquid line pressure as it will vary from discharge pressure due to condenser coil pressure drop.
Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart.
Subtract the measured liquid line temperature from the saturated temperature to determine the liquid sub-cooling.
Compare calculated sub-cooling to Table 3 for the appropriate unit type and
options.
Notes: 1. Must be charged with the hot gas valve
closed. After charging, operate the unit in reheat (dehumidification) mode to
check for correct operation. 2. The sub-cooling value in this table is for the
unit running in cooling mode of operation. After charging, operate the unit in
heating mode to check for correct operation. 3. The sub-cooling value in this
table is for the unit running in cooling mode of operation and the hot gas
valve closed. After charging, operate the unit in reheat (dehumidification)
mode to check for correct operation and then in heating mode to check for
correct operation. 4. Sub-cooling must be increased by -17.2°C (1°F) per 3
meters (10 feet) of vertical liquid line rise for R-410A (AHU above CU). For
example, a cooling only unit with hot gas reheat and a vertical liquid drop
can charge to a sub-cooling value of 2.8 – 8.3°C (5-15°F), but a cooling only
unit with hot gas reheat and a vertical liquid rise of 9.1 m (30 ft) must
charge to a sub-cooling value of at least 4.4 8.3°C (8-15°F). DO NOT
OVERCHARGE. Refrigerant overcharging leads to excess refrigerant in the
condenser coils resulting in elevated compressor discharge pressure.
23
Table 4 – Acceptable Microchannel Air-Cooled Condenser Coil Liquid Sub-Cooling Values (Metric)
Ambient (°C)
19.4 22.2 27.8 35.0 40.6 46.1
4.4 5.0 – 7.8 5.6 – 8.3 5.6 – 8.3 5.6 – 8.3 6.1 – 8.9 5.6 – 8.3
Cooling Mode Liquid Sub-Cooling Values(°C)
Evaporator Coil Saturation Temperature (°C)
7.2
8.9
10.0
4.4 – 7.2
4.4 – 7.2
3.9 – 6.7
5.0 – 7.8
5.0 – 7.8
4.4 – 7.2
5.6 – 8.3
5.6 – 8.3
5.0 – 7.8
5.6 – 8.3
5.6 – 8.3
5.0 – 7.8
6.1 – 8.9
5.6 – 8.3
5.6 – 8.3
6.1 – 8.9
6.1 – 8.9
6.1 – 8.9
12.8 2.8 – 5.6 3.9 – 6.7 3.9 – 6.7 4.4 – 7.2 4.4 – 7.2 5.0 – 7.8
Table 5 – Acceptable Microchannel Air-Cooled Condenser Coil Liquid Sub-Cooling Values (Imperial)
Cooling Mode Liquid Sub-Cooling Values(°F)
Ambient (°F)
Evaporator Coil Saturation Temperature (°F)
40
45
48
50
55
67
9 – 14
8 – 13
8 – 13
7 – 12
5 – 10
72
10 – 15
9 – 14
9 – 14
8 – 13
7 – 12
82
10 – 15
10 – 15
10 – 15
9 – 14
7 – 12
95
10 – 15
10 – 15
10 – 15
9 – 14
8 – 13
105
11 – 16
11 – 16
10 – 15
10 – 15
8 – 13
115
10 – 15
11 – 16
11 – 16
11 – 16
9 – 14
Notes: 1. Microchannel condenser coils are more sensitive to charge. The system must
be running in cooling mode with compressor, supply airflow & condenser fan
speed at full load. The sub-cooling value changes depending on the ambient
temperature reading and the evaporator coil saturation temperature. To find
the correct sub-cooling value, find the ambient temperature on the first
column and follow that across to the SST (4.4-12.8°C [40-55°F]).
2. Superheat for Microchannel condenser coils must be between 4.4 and 8.3°C
(8 – 15°F)
Checking Evaporator Superheat Measure the temperature of the suction line close to the evaporator.
Convert the pressure obtained to a saturated temperature using the appropriate refrigerant temperature-pressure chart.
Read gauge pressure at the suction line close to the evaporator.
Subtract the saturated temperature from the measured suction line temperature to determine the evaporator superheat.
24
For refrigeration systems with tandem compressors, it is critical that the
suction superheat setpoint on the TXV is set with one compressor running. The
suction superheat must be 5.6-7.2°C (10-13-) with one compressor running. The
suction superheat will increase with both compressors in a tandem running.
Inadequate suction superheat can allow liquid refrigerant to return to the
compressors, which will wash the oil out of the compressor. Lack of oil
lubrication will destroy a compressor. Liquid sub-cooling must be measured
with both compressors in a refrigeration system running.
Compare calculated superheat to the acceptable cooling mode superheat values
of 4.4-8.3°C (8-15°F) for all system types. Superheat will increase with long
suction line runs.
CAUTION
EXPANSION VALVE ADJUSTMENT
Thermal expansion valves must be adjusted to approximately 4.4-8.3°C (8-15°F)
of suction superheat. Failure to have sufficient superheat will damage the
compressor and void the
Adjusting Sub-cooling and Superheat Temperatures The system is overcharged if
the sub-cooling temperature is too high compared to Table 3 and the evaporator
is fully loaded (low loads on the evaporator result in increased subcooling)
and the evaporator superheat is within the temperature range of 4.4-8.3°C
(8-15°F) (high superheat results in increased sub-cooling)
Correct an overcharged system by reducing the amount of refrigerant in the
system to lower the sub-cooling.
CAUTION
DO NOT OVERCHARGE!
Refrigerant overcharging leads to excess refrigerant in the condenser coils
resulting in elevated compressor discharge pressure.
The system is undercharged if the superheat is too high and the sub-cooling is
too low.
Correct an undercharged system by adding refrigerant to the system to reduce
superheat and raise sub-cooling.
If the sub-cooling is correct and the superheat is too high, the TXV may need
adjustment to correct the superheat.
25
Table 6 – R-410A Refrigerant Temperature-Pressure Chart (Metric)
°C KPA °C KPA °C KPA °C KPA °C KPA -6.7 539.9 8.3 928.8 23.3 1473.5 38.3
2213.3 53.3 3193.8 -6.1 551.6 8.9 946.0 23.9 1496.9 38.9 2245.0 53.9 3235.8
-5.6 564.0 9.4 963.2 24.4 1521.0 39.4 2276.7 54.4 3277.9 -5.0 576.4 10.0 980.5
25.0 1545.2 40.0 2309.1 55.0 3320.6 -4.4 588.8 10.6 998.4 25.6 1570.0 40.6
2341.5 55.6 3363.4 -3.9 601.2 11.1 1016.3 26.1 1594.8 41.1 2374.6 56.1 3406.8
-3.3 614.3 11.7 1034.9 26.7 1619.6 41.7 2408.4 56.7 3450.9 -2.8 627.4 12.2
1053.6 27.2 1645.1 42.2 2442.2 57.2 3495.1 -2.2 640.5 12.8 1072.2 27.8 1670.7
42.8 2476.0 57.8 3539.9 -1.7 654.3 13.3 1090.8 28.3 1696.2 43.3 2510.5 58.3
3585.4 -1.1 667.4 13.9 1110.1 28.9 1722.4 43.9 2544.9 58.9 3630.9 -0.6 681.2
14.4 1129.4 29.4 1749.3 44.4 2580.1 59.4 3677.1 0.0 695.7 15.0 1149.4 30.0
1775.5 45.0 2616.0 60.0 3724.0 0.6 709.5 15.6 1169.4 30.6 1802.4 45.6 2651.8
60.6 3771.6 1.1 724.0 16.1 1189.4 31.1 1829.9 46.1 2688.4 61.1 3819.1 1.7
738.5 16.7 1209.4 31.7 1857.5 46.7 2724.9 61.7 3867.4 2.2 752.9 17.2 1230.1
32.2 1885.8 47.2 2761.4 62.2 3915.7 2.8 768.1 17.8 1251.4 32.8 1914.1 47.8
2798.7 62.8 3965.3 3.3 783.3 18.3 1272.1 33.3 1942.3 48.3 2836.6 63.3 4015.0
3.9 798.4 18.9 1293.5 33.9 1971.3 48.9 2874.5 63.9 4065.3 4.4 814.3 19.4
1314.9 34.4 2000.2 49.4 2913.1 64.4 4115.6 5.0 829.5 20.0 1336.9 35.0 2029.9
50.0 2952.4 65.0 4167.3 5.6 846.0 20.6 1359.0 35.6 2059.5 50.6 2991.7 65.6
4219.1 6.1 861.9 21.1 1381.8 36.1 2089.2 51.1 3031.0 6.7 878.4 21.7 1403.8
36.7 2120.2 51.7 3071.0 7.2 895.0 22.2 1427.3 37.2 2150.6 52.2 3111.7 7.8
911.5 22.8 1450.0 37.8 2181.6 52.8 3153.1
26
Table 7 – R-410A Refrigerant Temperature-Pressure Chart (Imperial)
°F PSIG °F PSIG °F PSIG °F PSIG °F PSIG 20 78.3 47 134.7 74 213.7 101 321.0
128 463.2 21 80.0 48 137.2 75 217.1 102 325.6 129 469.3 22 81.8 49 139.7 76
220.6 103 330.2 130 475.4 23 83.6 50 142.2 77 224.1 104 334.9 131 481.6 24
85.4 51 144.8 78 227.7 105 339.6 132 487.8 25 87.2 52 147.4 79 231.3 106 344.4
133 494.1 26 89.1 53 150.1 80 234.9 107 349.3 134 500.5 27 91.0 54 152.8 81
238.6 108 354.2 135 506.9 28 92.9 55 155.5 82 242.3 109 359.1 136 513.4 29
94.9 56 158.2 83 246.0 110 364.1 137 520.0 30 96.8 57 161.0 84 249.8 111 369.1
138 526.6 31 98.8 58 163.8 85 253.7 112 374.2 139 533.3 32 100.9 59 166.7 86
257.5 113 379.4 140 540.1 33 102.9 60 169.6 87 261.4 114 384.6 141 547.0 34
105.0 61 172.5 88 265.4 115 389.9 142 553.9 35 107.1 62 175.4 89 269.4 116
395.2 143 560.9 36 109.2 63 178.4 90 273.5 117 400.5 144 567.9 37 111.4 64
181.5 91 277.6 118 405.9 145 575.1 38 113.6 65 184.5 92 281.7 119 411.4 146
582.3 39 115.8 66 187.6 93 285.9 120 416.9 147 589.6 40 118.1 67 190.7 94
290.1 121 422.5 148 596.9 41 120.3 68 193.9 95 294.4 122 428.2 149 604.4 42
122.7 69 197.1 96 298.7 123 433.9 150 611.9 43 125.0 70 200.4 97 303.0 124
439.6 44 127.4 71 203.6 98 307.5 125 445.4 45 129.8 72 207.0 99 311.9 126
451.3 46 132.2 73 210.3 100 316.4 127 457.3
27
Table 8 – R-454B Refrigerant Temperature-Pressure Chart (Metric)
°C KPA °C KPA °C KPA °C KPA °C KPA -6.7 484.5 8.3 843.3 23.3 1348.0 38.3
2034.6 53.3 2946.9 -6.1 495.6 8.9 859.3 23.9 1370.0 38.9 2064.1 53.9 2985.7
-5.6 506.9 9.4 875.3 24.4 1392.2 39.4 2093.9 54.4 3024.9 -5.0 518.2 10.0 891.6
25.0 1414.6 40.0 2123.9 55.0 3064.5 -4.4 529.7 10.6 908.1 25.6 1437.3 40.6
2154.3 55.6 3104.5 -3.9 541.5 11.1 924.8 26.1 1460.3 41.1 2185.0 56.1 3144.9
-3.3 553.3 11.7 941.7 26.7 1483.5 41.7 2216.1 56.7 3185.8 -2.8 565.4 12.2
958.8 27.2 1507.0 42.2 2247.4 57.2 3227.0 -2.2 577.6 12.8 976.2 27.8 1530.8
42.8 2279.1 57.8 3268.6 -1.7 589.9 13.3 993.7 28.3 1554.8 43.3 2311.1 58.3
3310.7 -1.1 602.5 13.9 1011.5 28.9 1579.0 43.9 2343.5 58.9 3353.2 -0.6 615.2
14.4 1029.4 29.4 1603.6 44.4 2376.2 59.4 3396.1 0.0 628.1 15.0 1047.6 30.0
1628.4 45.0 2409.2 60.0 3439.5 0.6 641.2 15.6 1066.0 30.6 1653.5 45.6 2442.6
60.6 3483.3 1.1 654.4 16.1 1084.7 31.1 1678.8 46.1 2476.2 61.1 3527.6 1.7
667.8 16.7 1103.5 31.7 1704.4 46.7 2510.3 61.7 3572.3 2.2 681.4 17.2 1122.6
32.2 1730.4 47.2 2544.7 62.2 3617.4 2.8 695.2 17.8 1141.9 32.8 1756.6 47.8
2579.4 62.8 3663.0 3.3 709.2 18.3 1161.5 33.3 1783.0 48.3 2614.5 63.3 3709.2
3.9 723.3 18.9 1181.3 33.9 1809.9 48.9 2650.0 63.9 3755.7 4.4 737.6 19.4
1201.3 34.4 1836.9 49.4 2685.7 64.4 3802.7 5.0 752.2 20.0 1221.5 35.0 1864.3
50.0 2721.9 65.0 3850.3 5.6 766.9 20.6 1242.0 35.6 1891.9 50.6 2758.5 65.6
3898.4 6.1 781.8 21.1 1262.8 36.1 1919.8 51.1 2795.4 6.7 796.9 21.7 1283.7
36.7 1948.1 51.7 2832.7 7.2 812.2 22.2 1304.9 37.2 1976.7 52.2 2870.4 7.8
827.7 22.8 1326.3 37.8 2005.5 52.8 2908.4
28
Table 9 – R-454B Refrigerant Temperature-Pressure Chart (Imperial)
°F PSIG °F PSIG °F PSIG °F PSIG °F PSIG 20 70.3 47 122.3 74 195.5 101 295.1
128 427.4 21 71.9 48 124.6 75 198.7 102 299.4 129 433.0 22 73.5 49 127.0 76
201.9 103 303.7 130 438.7 23 75.2 50 129.3 77 205.2 104 308.0 131 444.5 24
76.8 51 131.7 78 208.5 105 312.5 132 450.3 25 78.5 52 134.1 79 211.8 106 316.9
133 456.1 26 80.3 53 136.6 80 215.2 107 321.4 134 462.0 27 82.0 54 139.1 81
218.6 108 326.0 135 468.0 28 83.8 55 141.6 82 222.0 109 330.6 136 474.1 29
85.6 56 144.1 83 225.5 110 335.2 137 480.2 30 87.4 57 146.7 84 229.0 111 339.9
138 486.3 31 89.2 58 149.3 85 232.6 112 344.6 139 492.6 32 91.1 59 151.9 86
236.2 113 349.4 140 498.8 33 93.0 60 154.6 87 239.8 114 354.3 141 505.2 34
94.9 61 157.3 88 243.5 115 359.1 142 511.6 35 96.9 62 160.1 89 247.2 116 364.1
143 518.1 36 98.8 63 162.8 90 251.0 117 369.1 144 524.6 37 100.8 64 165.6 91
254.8 118 374.1 145 531.3 38 102.9 65 168.5 92 258.6 119 379.2 146 538.0 39
104.9 66 171.3 93 262.5 120 384.3 147 544.7 40 107.0 67 174.2 94 266.4 121
389.5 148 551.5 41 109.1 68 177.2 95 270.4 122 394.8 149 558.4 42 111.2 69
180.1 96 274.4 123 400.1 150 565.4 43 113.4 70 183.1 97 278.4 124 405.4 44
115.6 71 186.2 98 282.5 125 410.8 45 117.8 72 189.3 99 286.7 126 416.3 46
120.0 73 192.4 100 290.9 127 421.8
29
The following table is available to help with estimating the initial charge to add based on refrigerant line lengths, however, final refrigerant charge must be based on the sub-cooling and superheat values as discussed in the prior section.
Liquid Line (mm) od
Table 10 – Estimated R410A Refrigerant Charge per 1.5 meters
Additional
Additional
Additional
R410A
R410A
R410A
Hot Gas
charge per Suction charge per Reheat charge per Bypass
1.5m of Line
1.5m of Line
1.5m of Line
line (oz) (mm) od line (oz) (mm) od line (oz)* (mm) od
Additional R410A charge per 1.5m of line (oz)*
9.5
2.58
9.5
0.1
9.5
0.24
9.5
0.17
12.7
5.08
12.7
0.19
12.7
0.48
12.7
0.34
15.9
8.23
15.9
0.31
15.9
0.77
15.9
0.55
19.1
11.85
19.1
0.44
19.1
1.12
19.1
0.8
22.2
16.46
22.2
0.62
22.2
1.55
22.2
1.11
28.6
28.06
28.6
1.05
28.6
2.64
28.6
1.88
34.9
34.9
1.56
34.9
3.9
34.9
2.78
*at SCT = 35°C & Subcooling = 5.6°C,SST = 13.7°C & Superheat=5.6°C
Table 11 – Estimated R410A Refrigerant Charge per 5 ft
Liquid Line
Additional R410A
charge per 5 ft of line
(oz)*
Suction Line
Additional R410A
charge per 5 ft of line
(oz)*
Reheat Line
Additional R410A
charge per 5 ft of line
(oz)*
Hot Gas Bypass
Line
3/8od
2.58
3/8od
0.10
3/8od
0.24
3/8od
1/2od
5.08
1/2od
0.19
1/2od
0.48
1/2od
5/8od
8.23
5/8od
0.31
5/8od
0.77
5/8od
3/4od
11.85
3/4od
0.44
3/4od
1.12
3/4od
7/8od
16.46
7/8od
0.62
7/8od
1.55
7/8od
1-1/8od 28.06 1-1/8od
1.05
1-1/8od
2.64
1-1/8od
1-3/8od
1-3/8od
1.56
1-3/8od
3.90
1-3/8od
- at SCT = 115oF & Subcooling = 10oF, SST = 45oF & Superheat=10oF
Additional R410A
charge per 5 ft of line
(oz)* 0.17 0.34 0.55 0.80 1.11 1.88 2.78
Special Low Ambient Option Charging Instructions For units equipped with low ambient refrigerant flood back option being charged in the summer when the ambient temperature is warm:
If the ambient is above 21°C (70°F), charge to approximately 0.6-1.1°C (1-2°F) of subcooling measured at the inlet to the expansion valve. Once enough charge has been added to get the evaporator superheat and subcooling values to the correct setting, more charge must be added. For units with Fin & Tube Condenser coils, use Table to find the
30
additional charge amount required for the system when running in cold ambient conditions. For units with Microchannel Condenser coils, use Table 12 to find the additional charge amount required for the system when running in cold ambient conditions.
Table 12 – Charge to Flood Fin and Tube
Condenser Coil for Ambient
Above 21.3°C (70°F)
CF Size
of Per Circuit
circuits Charge (lbs)
CF 2, 3
1
4.9
CF 4, 5, 6, 7 1
6.2
CF 9, 11
2
9.1
CF 13, 15
2
12.1
CF 16, 18
2
13.1
CF 20, 25, 30 2
17.5
CF 26, 31, 40
2 4
18.0 9.1
CF 50, 60, 70
2 4
43.8 22.1
Table 13 – Charge to Flood Microchannel
Condenser Coil for Ambient Above 21.3°C
(70°F)
CF Size
of Per Circuit
circuits Charge (lbs)
CF 2, 3, 4
1
5.6
CF 5, 6, 7
1
10.2
CF 9, 11
2
5.6
CF 13, 15
2
10.2
CF 16, 18
2
13.3
CF 20, 25, 30 2
13.3
CF 26, 31, 40
2 4
19.5 9.7
CF 50, 60, 70
2 4
29.8 14.9
For units equipped with low ambient refrigerant flood back option being charged in the winter when the ambient temperature is cold:
1. If the ambient is below 21°C (70°F),
charge to approximately 0.6-1.1°C (1-
2°F) of sub-cooling measured at the inlet
to the expansion valve. Once enough
charge has been added to get the
evaporator superheat and sub-cooling
values to the correct setting more charge
may need to be added. If the ambient
temperature is -17.8°C (0°F) no more
charge is required.
Ambient
temperatures above -17.8°C (0°F) will
require a percentage of the per circuit
charge values from Table 6 (for fin and
tube condenser coils) or Table 7 (for
microchannel condenser coils). Using
your ambient temperature, find the
percentage value from Table 8, and
multiply the Per Circuit Charge value
from Table 6 (for fin and tube condenser
coils) or Table 7 (for microchannel
condenser coils) and the % value to
determine the additional charge amount.
Table 14 – % Charge to Flood Condenser
Coil for Ambient Below 21.3°C (70°F)
Condenser
Percentage
Ambient
Per Circuit
Temperature Charge from
°C (°F)
Table 6 or
15.6 (60)
60%
10.0 (50)
37%
4.4 (40)
24%
-1.1 (30)
15%
-6.7 (20)
8%
-17.8 (0)
0%
2. Check the unit for proper operation once the ambient temperature is above 26.7°C (80°F).
Example: A CF size 31 with tandem compressors and Fin and Tube Condenser Coils where the ambient temperature is 4.4°C (40°F).
31
From Table 12 – 18 lbs refrigerant charge per circuit (tandem compressors
would have 2 circuits in this size of CF).
From Table 14 – 24% of Table 12 charge Additional charge needed for a unit
with low ambient flooded condenser controls = 18 lbs * 0.24 = 4.32 lbs
additional refrigerant charge per circuit
Low Ambient Operation During low ambient temperatures, the vapor refrigerant
will migrate to the cold part of the system and condense into liquid. All CF
Series compressors are provided with factory installed crankcase heaters to
help prevent liquid refrigerant from slugging the compressors during startup
in low ambient conditions. The condenser or condensing unit must have
continuous power 24 hours prior to startup. This ensures the compressor will
receive sufficient refrigerant vapor at startup. Standard units can operate
down to 12.8°C (55°F) ambient temperature.
AAON condenser fan head pressure control units can operate down to 1.7°C
(35°F) ambient temperature. Three different condenser fan head pressure
control options available are adjustable fan cycling, ECM condenser fan, or
VFD controlled condenser fans. See detailed information following.
The AAON low ambient (condenser floodback) system is used to operate a
refrigerant system down to -17.8°C (0°F) outside air temperature. See detailed
information following.
Fan Cycling Low Ambient Adjustable fan cycling is a low ambient head pressure
control option that cycles the condenser fans to maintain refrigerant circuit
head pressures at acceptable levels during cooling operation. The head
pressure set point (689.5 3240.5 kPa [100-470 psi]) and
pressure differential (241.3 1379 kPa [35-200 psi]) can be field adjusted
using a flathead screwdriver. For example, if the head pressure is set to
2068.4 kPa (300psi), and the differential is set to 689.5 kPa (100psi), then
fans will cut in at 2068.4 kPa (300psi) and cut out at 1379 kPa (200psi). Fan
cycling and variable speed condenser fan head pressure control options allow
mechanical cooling with ambient temperatures down to 1.7°C (35°F).
Figure 7 – Adjustable Fan Cycling Switch
Variable Speed Low Ambient Variable speed condenser fan head pressure control
is a low ambient head pressure control option that sends a variable signal in
relation to the refrigerant circuit head pressure of the system to an
electronically commutated motor (ECM) or VFD. The motor either speeds up or
slows down air flow accordingly in order to maintain constant head pressure.
Fan cycling and variable speed condenser fan head pressure control options
allow mechanical cooling with ambient temperatures down to 10.6°C (35°F).
Flooded Condenser Low Ambient Flooded condenser low ambient control maintains
normal head pressure during periods of low ambient. When the ambient
temperature drops, the condensing temperature and therefore pressure drops.
32
Without ambient control, the system would shut down on low discharge pressure.
The flooded condenser method of low ambient control fills the condenser coil
with liquid refrigerant, decreasing the heat transfer capacity of the coil,
which allows the coil to operate at an acceptable discharge pressure.
The condenser coil will not be flooded during summer ambient temperatures, so
a receiver is included to store the additional liquid refrigerant required to
flood the condenser coil in low ambient. The receiver is factorysized to
contain all of the flooded volume. Without a receiver there would be high head
pressures during higher ambient conditions.
The low ambient system maintains normal head pressure during periods of low
ambient by restricting liquid flow from the condenser to the receiver, and at
the same time bypassing hot gas around the condenser to the inlet of the
receiver. This reduces liquid refrigerant flow from the condenser, reducing
its effective surface area, which in turn increases the condensing pressure.
At the same time the bypassed hot gas raises liquid pressure in the receiver,
allowing the system to operate properly. CF Series condensers and condensing
units use an LAC valve for low ambient operation.
Refrigerant Piping (See back of the manual for refrigerant piping diagrams.)
CAUTION
REFRIGERANT PIPING
This section is for information only and is not intended to provide all
details required by the designer or installer of the refrigerant piping
between the condenser or condensing unit and the air handling unit. AAON, Inc.
is not responsible for interconnecting refrigerant piping. Consult ASHRAE
Handbook Refrigeration and ASME Standards.
LAC Valve The Low Ambient Control (LAC) valve is a non-adjustable three way
valve that modulates to maintain receiver pressure. As the receiver pressure
drops below the valve setting (2034 kPa [295 psig] for R-410A), the valve
modulates to bypass discharge gas around the condenser. The discharge gas
warms the liquid in the receiver and raises the pressure to the valve setting.
The following schematic shows an example system using the LAC valve.
Figure 8 – LAC Piping Example
CAUTION
REFRIGERANT PIPING Line sizes must be selected to meet actual installation
conditions, not simply based on the connection sizes at the condensing unit or
air handling unit.
General Piping from the condensing unit to the air handler is the
responsibility of the installing contractor.
33
Use only clean type “ACR” rigid copper tubing that has been joined with high
temperature brazing alloy.
The pipe or line sizes must be selected to meet the actual installation
conditions and NOT simply based on the connection sizes at the condensing unit
or air handler.
All CF Series condensing units are provided with in-line shutoff valves on
both the liquid and suction lines. These must remain closed until the system
is ready for start-up after installation.
Piping must conform to generally accepted practices and codes.
Care must be taken not to cross the circuits on multiple circuit systems.
Upon completion of piping connection, the interconnecting piping and air
handler MUST BE evacuated to 500 microns or less; leak checked and charged
with refrigerant. Determining Refrigerant Line Size The piping between the
condenser and low side must ensure:
1. Minimum pressure drop, and
2. Continuous oil return, and
3. Prevention of liquid refrigerant slugging, or carryover
Minimizing the refrigerant line size is favorable from an economic
perspective, reducing installation costs, and reducing the potential for
leakage. However, as pipe diameters decrease, pressure drop increases.
Excessive suction line pressure drop causes loss of compressor capacity and
increased power usage resulting in reduced system efficiency. Excessive
pressure drops in the liquid line can cause the liquid refrigerant to
flash, resulting in faulty TXV operation and improper system performance. In
order to operate efficiently and cost effectively, while avoiding malfunction,
refrigeration systems must be designed to minimize both cost and pressure
loss.
Equivalent Line Length All line lengths discussed in this manual, unless
specifically stated otherwise, are Equivalent Line Lengths. The frictional
pressure drop through valves, fittings, and accessories is determined by
establishing the equivalent length of straight pipe of the same diameter.
Always use equivalent line lengths when calculating pressure drop. Special
piping provisions must be taken when lines are up vertical risers or in
excessively long line runs. Do not run underground refrigerant lines.
Liquid Line When sizing the liquid line, it is important to minimize the
refrigerant charge to reduce installation costs and improve system
reliability. This can be achieved by minimizing the liquid line diameter.
However, reducing the pipe diameter will increase the velocity of the liquid
refrigerant which increases the frictional pressure drop in the liquid line,
and causes other undesirable effects such as noise.
Maintaining the pressure in the liquid line is critical to ensuring sufficient
saturation temperature, avoiding flashing upstream of the TXV, and maintaining
system efficiency. Pressure losses through the liquid line due to frictional
contact, installed accessories, and vertical risers are inevitable.
Maintaining adequate sub-cooling at the condenser to overcome these losses is
the only method to ensure that liquid refrigerant reaches the TXV.
34
Liquid refrigerant traveling upwards in a riser loses head pressure. If the
evaporator is below the condenser, with the liquid line flowing down, the
gravitational force will increase the pressure of the liquid refrigerant. This
will allow the refrigerant to withstand greater frictional losses without the
occurrence of flashing prior to the TXV.
A moisture-indicating sight glass may be field installed in the liquid line to
indicate the occurrence of premature flashing or moisture in the line. The
sight glass must not be used to determine if the system is properly charged.
Use temperature and pressure measurements to determine liquid subcooling, not
the sight glass.
Liquid Line Routing Care must be taken with vertical risers. When the system
is shut down, gravity will pull liquid down the vertical column, and back to
the condenser when it is below the evaporator. This could potentially result
in compressor flooding. A check valve can be installed in the liquid line
where the liquid column rises above the condenser to prevent this. The liquid
line is typically pitched along with the suction line, or hot gas line, to
minimize the complexity of the configuration.
Liquid Line Insulation In cooling only systems, when the liquid line is routed
through regions where temperature losses are expected, no insulation is
required, as this may provide additional sub-cooling to the refrigerant. When
routing the liquid line through high temperature areas, insulation of the line
is appropriate to avoid loss of subcooling through heat gain.
In heat pump systems, when the liquid line is routed through regions where
temperature losses are expected (all lines exposed to outside air conditions),
insulate with a
minimum 1 inch thick Armaflex insulation, as this will prevent capacity loss
during heating mode of operation.
Liquid Line Guidelines In order to ensure liquid at the TXV, the sum of
frictional losses and pressure loss due to vertical rise must not exceed
available subcooling. A commonly used guideline to consider is a system design
with pressure losses due to friction through the line not to exceed a
corresponding -17.2 to -16.7°C (1-2°F) change in saturation temperature. The
sum of frictional losses (including valve losses, filter drier losses, other
accessories, and line losses) and pressure loss due to vertical rise must not
exceed -13.3°C (8°F) if the available sub-cooling is -12.2°C (10°F).
If the velocity of refrigerant in the liquid line is too great, it could cause
excessive noise or piping erosion. The maximum velocities for liquid lines are
100 fpm from the condenser to a receiver to discourage fluid backup, and 500
fpm from receiver tank to the evaporator (300 fpm if the line includes an
electric valve to minimize valve induced liquid hammer).
Liquid Line Accessories Liquid line shut off valves and filter driers are
factory provided. The total length equivalent of pressure losses through
valves, elbows and fittings must be considered when adding additional
components in the field. It is a good practice to utilize the fewest elbows
that will allow the mating units to be successfully joined.
A liquid line receiver is factory installed on units with modulating hot gas
reheat, units with low ambient control flooded condenser, and units with heat
pump.
Suction Line The suction line is more critical than the liquid line from a
design and construction
35
standpoint. More care must be taken to ensure that adequate velocity is
achieved to return oil to the compressor at minimum loading conditions.
However, reducing the piping diameter to increase the velocity at minimal load
can result in excessive pressure losses, capacity reduction, and noise at full
load.
Suction Line Routing For cooling only systems, pitch the suction line in the
direction of flow (about 1 inch per 20 feet of length) to maintain oil flow
towards the compressor, and keep it from flooding back into the evaporator.
For heat pump systems, do not pitch lines since they will be flowing in one
direction in cooling mode and the opposite direction in heating mode.
Crankcase heaters are provided to keep any condensed refrigerant that collects
in the compressor from causing damage or wear. Make sure to provide support to
maintain suction line positioning, and insulate completely between the
evaporator and condensing unit.
It is important to consider part load operation when sizing suction lines. At
minimum capacity, refrigerant velocity may not be adequate to return oil up
the vertical riser. Decreasing the diameter of the vertical riser will
increase the velocity, but also the frictional loss.
For difficult line routing applications, a double suction riser can be applied
to the situation of part load operation with a suction riser. A double suction
riser is designed to return oil at minimum load while not incurring excessive
frictional losses at full load. A double suction riser consists of a small
diameter riser in parallel with a larger diameter riser, and a trap at the
base of the
large riser. At minimum capacity, refrigerant velocity is not sufficient to
carry oil up both risers, and it collects in the trap, effectively closing off
the larger diameter riser, and diverting refrigerant up the small riser where
velocity of the refrigerant is sufficient to maintain oil flow. At full load,
the mass flow clears the trap of oil, and refrigerant is carried through both
risers. The smaller diameter pipe must be sized to return oil at minimum load,
while the larger diameter pipe must be sized so that flow through both pipes
provides acceptable pressure drop at full load.
Figure 9 – Double Suction Riser Construction
A double riser can also be used for heat pump operation. The specific volume
(ft3/lb) of refrigerant at the discharge temperature and pressure (heating
mode line conditions) is significantly lower than the specific volume at the
suction temperature and pressure (cooling mode line conditions). To compound
the issue, the capacity in heating mode is lower than the capacity in cooling
mode. The discharge velocity in the riser during heating mode is much lower
than the suction velocity during cooling mode. Often, a double riser is
necessary to get acceptable velocities for the discharge mode and acceptable
velocities for the suction mode. In the example diagrams (See Figure 10 &
Figure 11), the cooling mode will use both lines, and the heating mode will
use only one.
36
Suction Line Traps Include traps every 6.1 meters (20 feet) in vertical
suction riser sections for cooling only systems and every 3.7 meters (12 feet)
for heat pump systems. Include a trap at the bottom of the vertical run.
Suction Line Insulation The entire suction line must be insulated with a
minimum 1 inch thick Armaflex insulation. This prevents condensation from
forming on the line, and reduces any potential loss in capacity associated
with heat gain placing additional load on the system. This line must still be
insulated in heat pump systems even though it acts as both a discharge and
suction line.
Suction Line Guidelines For proper performance, keep suction line velocities
less than a 4,000 fpm. The minimum velocity required to return oil is
dependent on the pipe diameter, however, a general guideline of 1,000 fpm
minimum may be applied.
When suction flow is up, variable capacity compressors require a minimum
velocity of 1,500 fpm at full load.
Tandem compressors must be considered for full load operation (both
compressors operating) and at partial load (only one compressor operating).
When suction flow is up, and the tandem has a variable capacity compressor,
the velocity for only one compressor in operation must be greater than 1,500
fpm. For on/off compressors, the velocity must be greater than the minimum
velocity required to return oil.
Heat pump vapor lines must be checked for suction flow (cooling mode
operation) and discharge flow (heating mode operation). The same line must be
used for both modes of operation.
In a fashion similar to the liquid line, a common guideline to consider is a
system design with pressure losses due to friction through the line not to
exceed a corresponding -17.2 to -16.7°C (1-2°F) change in saturation
temperature.
For split system piping with long horizontal runs and short vertical risers, a
smaller pipe size can be used to provide sufficient velocity to return oil in
vertical risers at part loads, and a larger size pipe can be used on the
horizontal runs and vertical drop sections. This helps with oil return, yet
keeps the pressure drop to a minimum.
CAUTION
SUCTION RISER TRAPS
Circuits require suction riser traps every 20 feet. (every 12 feet for heat
pumps)
Suction Line Accessories If the job requirements specify suction accumulators,
they must be separately purchased and field installed. Heat pump units will
include a factory installed suction accumulator.
Discharge Line The discharge line is similar to the suction line from a design
and construction standpoint. Care must be taken to ensure that adequate
velocity is achieved to return oil to the compressor at minimum loading
conditions. However, reducing the piping diameter to increase the velocity at
minimal load can result in excessive pressure losses, capacity reduction, and
noise at full load. Pressure loss in the discharge line has less of an impact
on capacity than pressure loss in
37
the suction line. Pressure loss in the discharge line causes the compressors
to work harder and thus use more power.
Discharge Line Routing For cooling only remote condenser systems, pitch the
discharge line in the direction of flow (about 1 inch per 20 feet of length)
to maintain oil flow towards the compressor.
In a heat pump system, the field installed suction line is also used as a
discharge line in the heating mode of operation so the line must be sized to
meet both the suction line conditions in cooling mode and the discharge line
conditions in heating mode.
Because it is used in both directions for a heat pump unit, the line must be
installed level, not pitched, to facilitate oil return in both modes of
operation.
It is important to consider part load operation when sizing discharge lines.
At minimum capacity, refrigerant velocity may not be adequate to return oil up
the vertical riser. Decreasing the diameter of the vertical riser will
increase the velocity, but also the frictional loss.
For difficult line routing applications, a double discharge riser can be
applied to the situation of part load operation with a discharge riser. A
double discharge riser is designed to return oil at minimum load while not
incurring excessive frictional losses at full load. A double discharge riser
consists of a small diameter riser in parallel with a larger diameter riser,
and a trap at the base of the large riser. At minimum capacity, refrigerant
velocity is not sufficient to carry oil up both
risers, and it collects in the trap, effectively closing off the larger
diameter riser, and diverting refrigerant up the small riser where velocity of
the refrigerant is sufficient to maintain oil flow. At full load, the mass
flow clears the trap of oil, and refrigerant is carried through both risers.
The smaller diameter pipe must be sized to return oil at minimum load, while
the larger diameter pipe must be sized so that flow through both pipes
provides acceptable pressure drop at full load. (See the Double Suction Riser
Construction Figure 9)
A double riser can also be used for heat pump operation. The specific volume
(ft3/lb) of refrigerant at the discharge temperature and pressure (heating
mode line conditions) is significantly lower than the specific volume at the
suction temperature and pressure (cooling mode line conditions). To compound
the issue, the capacity in heating mode is lower than the capacity in cooling
mode. The discharge velocity in the riser during heating mode is much lower
than the suction velocity during cooling mode. Often, a double riser is
necessary to get acceptable velocities for the discharge mode and acceptable
velocities for the suction mode. In the example diagrams, the cooling mode
will use both lines, and the heating mode will use only one. See the following
schematics that illustrate how the double discharge riser can work for heat
pump applications.
38
Figure 10 – Heat Pump Piping Schematic of Cooling Mode in Double Riser
Figure 11 – Heat Pump Piping Schematic of Heating Mode in Double Riser 39
Discharge Line Traps Include traps every 3.7 meters (12 feet) in vertical
discharge riser sections. Include a trap at the bottom of the vertical run.
Discharge Line Insulation Although a typical discharge line does not need to
be insulated, the suction line does. Since the same line is used for both, the
line must be insulated as described in the Suction Line Insulation section.
Discharge Line Guidelines For proper performance, keep discharge line
velocities less than a 17.8 m/s (3,500 fpm). The minimum velocity required to
return oil is dependent on the pipe diameter, however, a general guideline of
4.6 m/s (900 fpm) minimum may be applied.
When discharge flow is up, variable capacity compressors require a minimum
velocity of 4.6 m/s (900 fpm) at full load.
Tandem compressors must be considered for full load operation (both
compressors operating) and at partial load (only one compressor operating).
When discharge flow is up, and the tandem has a variable capacity compressor,
the velocity for only one compressor in operation must be greater than 4.6 m/s
(900 fpm). For on/off compressors, the velocity must be greater than the
minimum velocity required to return oil.
Heat pump vapor lines must be checked for suction flow (cooling mode
operation) and discharge flow (heating mode operation). The same line must be
used for both modes of operation.
In a fashion similar to the suction line, a common guideline to consider is a
system design with pressure losses due to friction through the line not to
exceed a
corresponding -17.2 to -16.7°C (1-2°F) change in saturation temperature.
For split system piping with long horizontal runs and short vertical risers, a
smaller pipe size can be used to provide sufficient velocity to return oil in
vertical risers at part loads, and a larger size pipe can be used on the
horizontal runs and vertical drop sections. This helps with oil return, yet
keeps the pressure drop to a minimum.
CAUTION
DISCHARGE RISER TRAPS
Circuits require discharge riser traps every 12 feet.
Hot Gas Bypass Line Hot Gas Bypass is available for use with DX systems that
may experience low suction pressure during the operating cycle. This may be
due to varying load conditions associated with VAV applications or units
supplying a large percentage of outside air. The system is designed to divert
refrigerant from the compressor discharge to the low pressure side of the
system in order to keep the evaporator from freezing and to maintain adequate
refrigerant velocity for oil return at minimum load.
Hot discharge gas is redirected to the evaporator inlet via an auxiliary side
connector (ASC) to false load the evaporator when reduced suction pressure is
sensed. Field piping between the condensing unit and the evaporator is
required.
Hot Gas Bypass Piping Considerations Pitch the hot gas bypass (HGB) line
downward in the direction of refrigerant flow, toward the evaporator.
40
When installing vertical hot gas bypass lines, an oil drip line must be
provided at the lowest point in the system. The oil drip line must be
vertical, its diameter must be the same as the diameter of the riser, and a
maximum of 25.4 cm (10″) long. Install a sight glass in the oil drip line for
observation. Run an oil return line, using 3.2 mm (1/8 inch) capillary tube, 3
meters (10 feet) in length, from the hot gas bypass line oil drip line to the
suction line. Connect the oil return line below the sight glass and 1 inch
above the bottom of the oil drip line.
Figure 12 – Oil Return Line
HGB valves are adjustable. Factory HGB valve settings will be sufficient for
most applications, but may require slight adjustments for some applications,
including some make up air applications.
Insulate the entire length of the HGB line with a minimum 2.5 cm (1 inch)
thick Armaflex insulation.
Hot Gas Bypass Line Guidelines Choose a small size line to ensure oil return,
and minimize refrigerant charge.
Maintain velocities below a maximum of 17.8 m/s (3,500 fpm). A general minimum
velocity guideline to use is approximately 10.2 m/s (2,000 fpm).
Hot Gas Reheat The AAON modulating hot gas reheat system diverts hot discharge
gas from the condenser to the air handling unit through the hot gas line.
Field piping between the condensing unit and the air handler is required.
The line delivers the hot discharge gas to the reheat coil and/or the hot gas
bypass valve, so it is sized as a discharge line.
Discharge lines must be sized to ensure adequate velocity of refrigerant to
ensure oil return, avoid excessive noise associated with velocities that are
too high, and to minimize efficiency losses associated with friction.
Pitch the hot gas line in the direction of flow for oil return.
When installing vertical hot gas reheat lines, an oil drip line must be
provided at the lowest point in the system. The oil drip line must be
vertical, its diameter must be the same as the diameter of the riser, and a
maximum of 25.4 cm (10″) long. Install a sight glass in the oil drip line for
observation. Run an oil return line, using 3.2 mm (1/8 inch) capillary tube, 3
meters (10 feet) in length, from the hot gas reheat line oil drip line to the
suction line. Connect the oil return line below the sight glass and 1 inch
above the bottom of the oil drip line. (See Oil Return Line Figure 12)
Insulate the entire length of the hot gas line with a minimum 1 inch thick
Armaflex insulation.
Hot Gas Reheat Guidelines Maintain velocities below a maximum of 17.8 m/s
(3,500 fpm). A general minimum velocity guideline to use is approximately 10.2
m/s (2,000 fpm).
41
Electrical The single point electrical power connections are made in the electrical control compartment.
Verify the unit nameplate agrees with the power supply. Connect power and control field wiring as shown on the unit wiring diagram provided with the unit.
Table 15 – Nameplate Voltage Markings & Tolerances
Hz
Nameplate Voltage
Nominal System Voltage
Operating Voltage Range 1
Min
Max
Acceptable Performance Range2
Min
Max
115
120
104
127
108
126
208/230
208/240
187
254
187
252
208
208
187
228
187
228
60
230
240
208
254
216
252
265
277
240
293
249
291
460
480
416
508
432
504
575
600
520
635
540
630
230
50
400
230
198
254
208
254
400
344
440
360
440
Notes: 1. Operating voltage is the min and max voltage for which the unit can function. Never operate outside of this min and max voltage. 2. The Acceptable Performance Range is the min and max voltage for which the unit performance is designed and rated to give acceptable performance.
WARNING
ELECTRIC SHOCK
Electric shock hazard. Before attempting to perform any installation, service,
or maintenance, shut off all electrical power to the unit at the disconnect
switches. Unit may have multiple power supplies. Failure to disconnect power
could result in dangerous operation, serious injury, death or property damage.
Route power and control wiring, separately, through the utility entry. Do not
run power and signal wires in the same conduit.
Size supply conductors based on the unit MCA rating. Supply conductors must be
rated a minimum of 75°C (167°F).
Protect the branch circuit in accordance with code requirements. The unit must
be electrically grounded in accordance with local codes, or in the absence of
local codes, the current National Electric Code, ANSI/NFPA 70 or the current
Canadian Electrical Code CSA C22.1.
NOTE: Units are factory wired for 208V, 230V, 460V, or 575V. In some units,
the 208V and 230V options may also be provided in single or three phase
configurations. The transformer configuration must be checked by a qualified
technician prior to startup.
42
CAUTION
3-PHASE ROTATION
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units.
Condenser fan motors must be checked by a qualified service technician at
startup and any wiring alteration must only be made at the unit power
connection. Variable frequency drives are programmed to automatically rotate
the fan in the correct rotation. Do not rely on fans with variable frequency
drives for compressor rotation.
Power wiring is to the unit terminal block or main disconnect. All wiring
beyond this point has been done by the manufacturer and cannot be modified
without affecting the unit’s agency/safety certification.
All units require field supplied electrical overcurrent and short circuit
protection. Device must not be sized larger than the Maximum Overcurrent
Protection (MOP) shown on the unit nameplate.
Supply voltage must be within the min/max range shown on the unit nameplate.
Available short circuit current must not exceed the short circuit current
rating (SCCR) shown on the unit nameplate.
CAUTION
Three phase voltage imbalance will cause motor overheating and premature
failure.
Three phase voltage imbalance will cause motor overheating and premature
failure. The maximum allowable imbalance is 2%.
Voltage imbalance is defined as 100 times the maximum deviation from the
average voltage divided by the average voltage.
Example: (221V+230V+227V)/3 = 226V, then 100*(226V-221V)/226V = 2.2%, which
exceeds the allowable imbalance.
Check voltage imbalance at the unit disconnect switch and at the compressor
terminal. Contact your local power company for line voltage corrections.
CAUTION
SEALING ELECTRICAL ENTRIES
Installing Contractor is responsible for proper sealing of the electrical
entries into the unit. Failure to seal the entries may result in damage to the
unit and property.
NOTE: A qualified technician must check for proper motor rotation and check
fan motor amperage listed on the motor nameplate is not exceeded. Motor
overload protection may be a function of the variable frequency drive and must
not be bypassed.
Wire control signals to the unit’s low voltage terminal block located in the
controls compartment.
If any factory installed wiring must be replaced, use a minimum 105°C (221°F)
type AWM insulated conductors.
43
Fuses and Circuit Breakers The interrupting rating of fuses and circuit breakers is to be determined based on the KAIC rating of the unit. Refer to the wiring diagram for fuse sizing.
Table 16 35 KAIC Fuse Sizing
35 KAIC Construction
Component Description
Fuse Fuse Disconnect
Class CC, 600V, 0.5A – 30A Class J, 600V, 35A – 600A 3P, 600V, 15A 600A
Interrupting Rating (kA)
200
200
35
Table 17 65 KAIC Fuse Sizing
65 KAIC Construction
Component Description
Interrupting Rating (kA)
Fuse
Class CC, 600V, 0.5A – 30A
200
Fuse
Class J, 600V, 35A – 600A
200
Disconnect
3P, 600V, 15A – 600A
65
Startup
(See back of the manual for startup form.)
WARNING
ELECTRIC SHOCK
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
WARNING
QUALIFIED INSTALLER
Improper installation, adjustment, alteration, service or maintenance can
cause property damage, personal injury or loss of life. Startup and service
must be performed by a Factory Trained Service Technician.
Before startup of the condenser or condensing unit, make sure that the
following items have been checked.
1. Verify that electrical power is available to the unit.
2. Verify that any remote stop/start device connected to the unit controller
is requesting the unit to start.
Cycle through all the compressors to confirm that all are operating within
tolerance.
While performing the check, use the startup form to record observations of
amps and refrigerant pressures.
CAUTION
3-PHASE ROTATION
Rotation must be checked on all MOTORS AND COMPRESSORS of three phase units. Condenser fan motors must all be checked by a qualified service technician at startup and any wiring alteration must only be made at the unit power connection. Variable frequency drives are programmed to automatically rotate the fan in the correct rotation. Do not rely on fans with variable frequency drives for compressor rotation.
44
When all is running properly, place the controller in the Run mode and observe
the system until it reaches a steady state of operation.
CAUTION
Before completing installation, a complete operating cycle must be observed to
verify that all components are functioning properly.
Compressor Operation The compressors must be off for a minimum of 3 minutes
and on for a minimum of 5 minutes. Short cycling of the compressors can cause
undue stress and wear.
WARNING
COMPRESSOR CYCLING
3 MINUTE MINIMUM OFF TIME To prevent motor overheating compressors must cycle
off for a minimum of 3 minutes.
5 MINUTE MINIMUM ON TIME To maintain the proper oil level compressors must
cycle on for a minimum of 5 minutes.
The cycle rate must not exceed 7 starts per hour.
Microchannel Unit Restart Sequence Units with microchannel condenser coils
include a sequence of controls to allow additional compressor restarts without
locking out the high pressure switch on the compressors. This helps with the
startup process when the microchannel coil is cold. The sequence allows four
high pressure trips with auto reset within the first 15 minutes after
a compressor call, but will lock out the compressors on the fifth high
pressure trip. After the first 15 minutes of operation, one more restart is
allowed, but the compressors will lockout if another fault occurs within 2
hours.
Variable Capacity Compressor Controller Units with variable capacity scroll
compressors may include a variable capacity compressor controller. The
following is an explanation of the terminals and troubleshooting of the alert
flash codes on the controller. For more information on the compressor
controller, see Emerson Climate Bulletin AE8-1328.
Figure 13 – Variable Capacity Compressor Controller
Note: When using field controls any variable capacity compressors must run at 100% for 1 minute when starting.
Low Voltage Terminals
24COM
Module Common
24VAC
Module Power
C1
Demand Input –
C2
Demand Input +
P1
Pressure Common
P2
Pressure Input
P3
Pressure Power 5VDC
P4
Pressure Shield
P5
Pressure Output –
45
P6 T1 & T2
Pressure Output + Discharge Temperature Sensor
High Voltage Terminals
A1 & A2 Alarm Relay Out
M1 & M2 Contactor
L1
Control Voltage N
L2
Control Voltage L
U1 & U2
Variable Capacity Unloader Solenoid
V1 & V2 Vapor Injection Solenoid
WARNING
COMPRESSOR CONTROLLER
To avoid damaging the compressor controller, DO NOT connect wires to terminals
C3, C4, T3, T4, T5, or T6.
The compressor controller modulates the compressor unloader solenoid in an on/off pattern according the capacity demand signal of the system. The following table shows the linear relationship between the demand signal and compressor capacity modulation. The compressor controller also protects the compressor against high discharge temperature. Refer to Table 19 for the relationship between thermistor temperature readings and resistance values.
Table 18 – Demand Signal vs. Compressor Capacity Modulation
Demand Signal (VDC)
1.00 1.44 3.00 4.20 5.00
Loaded %
Off 10% 50% 80% 100%
Unloaded %
Off 90% 50% 20% 0%
Time Loaded
Off 1.5 sec 7.5 sec 12 sec 15 sec
Time Unloaded
Off 13.5 sec 7.5 sec
3 sec 0 sec
% Compressor Capacity 0% 10% 50% 80% 100%
46
Figure 14 – Compressor Controller Flash Code Details
Table 19 – Thermistor Temperature vs. Resistance Values
°C
°F
k
°C
°F
k
-40
-40
2889.60
75
167
12.73
-35
-31
2087.22
80
176
10.79
-30
-22
1522.20
85
185
9.20
-25
-13
1121.44
90
194
7.87
-20
-4
834.72
95
203
6.77
-15
5
627.28
100
212
5.85
-10
14
475.74
105
221
5.09
-5
23
363.99
110
230
4.45
0
32
280.82
115
239
3.87
5
41
218.41
120
248
3.35
10
50
171.17
125
257
2.92
15
59
135.14
130
266
2.58
20
68
107.44
135
275
2.28
25
77
86.00
140
284
2.02
30
86
69.28
145
293
1.80
35
95
56.16
150
302
1.59
40
104
45.81
155
311
1.39
45
113
37.58
160
320
1.25
50
122
30.99
165
329
1.12
55
131
25.68
170
338
1.01
60
140
21.40
175
347
0.92
65
149
17.91
180
356
0.83
70
158
15.07
47
Compressor Lockouts Some units include adjustable compressor lockouts. The
compressor lockout in the picture below can be set to any temperature between
-23.3°C and 21.1°C (-10°F and 70°F). The ambient temperature sensor hangs
right outside the unit with a cover.
Figure 15 – Adjustable compressor lockout Heat pump units include a non-
adjustable compressor lockout for the cooling mode set to 12.8°C (55°F), and
an adjustable compressor lockout for the heating mode that can be set between
-6.7°C (20°F) to 35°C (95°F). If a heat pump is selected with the compressor
lockout feature, the adjustable compressor lockout will change to the 23.3°C
and 21.1°C (-10°F and 70°F) range.
Figure 16 – Ambient sensor cover
48
Maintenance
General Qualified technicians must perform routine service checks and maintenance. This includes reading and recording the condensing and suction pressures and checking for normal sub-cooling and superheat.
Compressors The scroll compressors are fully hermetic and require no maintenance except keeping the shell clean.
Refrigerant Filter Driers Each refrigerant circuit contains a filter drier. Replace when there is excessive pressure drop across the assembly or moisture is indicated in a liquid line sight glass.
Table 20 – Max Filter Drier Pressure Drops
Circuit Loading
Max. Pressure Drop
100%
69 kPa (10 psig)
50%
34.5 kPa (5 psig)
Oil Level It is critical that the refrigerant line piping is designed to
maintain proper oil return to the compressors. Some systems may require oil to
be added in addition to what is provided in the compressors. The oil is a POE
type and is available from your AAON Representative under part number R63681.
Proper oil level must be observed under minimum load conditions. On units
equipped with tandem compressors, all oil is returned to the lead compressor
in each tandem pair. When only the lead compressor is running, the oil level
must be a minimum of from the bottom of the sight glass. With both compressors
running, the level in the lead compressor will drop to the bottom of the sight
glass and the level in the second compressor must be a minimum of , from the
bottom of its sight glass. Do not allow the oil level in the sight glass to
exceed ¾ full level.
49
Lubrication All original motors and bearings are furnished with an original
factory charge of lubrication. Certain applications require bearings be re-
lubricated periodically. The schedule will vary depending on operating duty,
temperature variations, or severe atmospheric conditions.
Bearings must be re-lubricated at normal operating temperatures, but not when
running.
Condenser Coil Inspection The coils are leak tested at 4482 kPa (650 psig),
before shipment. AAON will not be responsible for loss of refrigerant. It is
the responsibility of the installer to verify that the system is sealed before
charging with refrigerant.
Maintenance Requirements Fan Motor Maintenance Cleaning – Remove oil, dust,
water, and chemicals from exterior of motor. Keep motor air inlet and outlet
open. Blow out interior of open motors with clean compressed air at low
pressure.
Labeled Motors – It is imperative for repair of a motor with Underwriters’
Laboratories label that original clearances be held; that all plugs, screws,
other hardware be fastened securely, and that parts replacements be exact
duplicates or approved equals. Violation of any of the above invalidates
Underwriters’ Label.
Access Doors If scale deposits or water is found around the access doors,
adjust door for tightness. Adjust as necessary until leaking stops when door
is closed.
Propeller Fans and Motors The fans are directly mounted on the motor shafts
and the assemblies require minimal maintenance except to assure they are clear
of dirt or debris that would impede the airflow.
Required Annual Inspection In addition to the above maintenance activities, a
general inspection of the unit surface must be completed at least once a year.
Air-Cooled Condenser The air-cooled condenser section rejects heat by passing
outdoor air over the condenser coils for cooling of the hot refrigerant gas
from the compressors.
Inspect the condenser coils annually to ensure unrestricted airflow. If the
installation has a large amount of airborne dust or other material, clean the
condenser coils with a water spray in a direction opposite to airflow. Care
must be taken to prevent damage to the coils. Microchannel Coil Cleaning
Cleaning microchannel coils is necessary in all locations. In some locations
it may be necessary to clean the coils more or less often than recommended.
Condenser coil must be cleaned at a minimum of once a year. In locations where
there is commonly debris or a condition that causes dirt/grease build up it
may be necessary to clean the coils more often. Proper procedure must be
followed at every cleaning interval. Using improper cleaning technique or
incorrect chemicals will result in coil damage, system performance fall off,
and potentially leaks requiring coil replacement.
Documented routine cleaning of microchannel coils with factory provided e-
50
coating is required to maintain coating warranty coverage. Use the E-Coated
Coil Cleaning section for details on cleaning ecoated coils.
Field applied coil coatings are not recommended with microchannel coils.
Allowed Chemical Cleaners and Procedures AAON recommends certain chemicals
that can be used to remove buildup of grime and debris on the surface of
microchannel coils. These chemicals have been tested for performance and
safety and are the only chemicals that AAON will warrant as correct for
cleaning microchannel coils.
There are two procedures that are outlined below that will clean the coils
effectively without damage to the coils. Use of any other procedure or
chemical may void the warranty to the unit where the coil is installed. With
all procedures make sure the unit is off before starting.
WARNING
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
The water pressure used to clean must not exceed 689.5 kPa (100 psi), from no
closer than 15.25 centimeters (6 inches) from the coils, and with the water
aimed perpendicular to the coils.
1 Simple Green Simple Green is available from AAON Parts and Supply (Part
T10701) and is biodegradable with a neutral 6.5 pH A 4 to 1 solution is recommended. Use the following procedure.
1. Rinse the coil completely with water. Use a hard spray but be careful not
to bend or damage the fins. A spray that is too hard will bend the fins. Spray
from the fan side of the coil.
2. With a pump sprayer filled with a mix of 4 parts water to one part Simple
Green spray the air inlet face of the coil. Be sure to cover all areas of the
face of the coil.
3. Allow the coil to soak for 10-15 minutes.
4. Rinse the coil with water as in step one. 5. Repeat as necessary.
2 Water Flush This procedure can be used when the only material to cause the
coil to need cleaning is debris from plant material that has impinged the coil
face.
1. Rinse the coil completely with water. Use a hard spray but be careful not
to bend or damage the fins. A spray that is too hard will bend the fins. Spray
from the fan side of the coil.
2. Spray and rinse the coil from the face.
CAUTION
Use pressurized clean water, with pressure not to exceed 689.5 kPa (100 psi).
Nozzle must be 15.25 cm (6″) and perpendicular to the coil face. Failure to do
so could result in coil
Application Examples The two procedures can be used to clean microchannel
coils. They will fit with the application depending on the area. In some areas
where the spring/summer has a large cottonwood bloom #2 might work fine if the
unit is installed on an office building and no other environmental factors
apply.
51
Generally the best and broadest based procedure is #1. The grease cutting
effect of the Simple Green is good for restaurant applications.
Other Coil Cleaners There are many cleaners on the market for condenser coils.
Before using any cleaner that is not covered in this section you must get
written approval from the AAON warranty and service department. Use of
unapproved chemicals will void the warranty.
AAON testing has determined that unless a chemical has a neutral pH (6-8) it
must not be used.
Beware of any product that claims to be a foaming cleaner. The foam that is
generated is caused by a chemical reaction to the aluminum fin material on
tube and fin coils and with the fin, tube, and coating material on
microchannel coils.
Microchannel coils are robust in many ways, but like any component they must
be treated correctly. This includes cleaning the coils correctly to give
optimal performance over many years.
E-Coated Coil Cleaning Documented routine cleaning of e-coated coils is
required to maintain coating warranty coverage for condenser coils. E-Coated
Coil Maintenance Record sheet is provided in this document.
WARNING
ELECTRIC SHOCK
Electric shock hazard. Shut off all electrical power to the unit to avoid
shock hazard or injury from rotating parts.
52
Remove surface loaded fibers or dirt prior to water rinse to prevent
restriction of airflow. If unable to back wash the side of the coil opposite
of the coils entering air side, then remove surface loaded fibers or dirt with
a vacuum cleaner. If a vacuum cleaner is not available, a soft non-metallic
bristle brush may be used. In either case, the tool must be applied in the
direction of the fins. Coil surfaces can be easily damaged (fin edges bent
over) if the tool is applied across the fins.
Use of a water stream, such as a garden hose, against a surface loaded coil
will drive the fibers, dirt and salts into the coil. This will make cleaning
efforts more difficult. Surface loaded fibers must be completely removed prior
to using low velocity clean water rinse.
A monthly clean water rinse is recommended for coils that are applied in
coastal or industrial environments to help to remove chlorides, dirt, and
debris. It is very important when rinsing, that water temperature is less than
39.5°C (130°F) and pressure is less than 689.5 kPa (100 psi) to avoid damaging
the fin edges. An elevated water temperature (not to exceed 39.5°C [130°F])
will reduce surface tension, increasing the ability to remove chlorides and
dirt.
CAUTION
High velocity water from a pressure washer or compressed air must only be used
at a very low pressure to prevent fin and/or coil damages. The force of the
water or air jet may bend the fin edges and increase airside pressure drop.
Reduced unit performance or nuisance unit shutdowns may occur.
Quarterly cleaning is essential to extend the life of an e-coated coil and is
required to maintain coating warranty coverage. Coil cleaning must be part of
the unit’s regularly scheduled maintenance procedures. Failure to clean an
e-coated coil will void the warranty and may result in reduced efficiency and
durability.
CAUTION
Harsh chemicals, household bleach, or acid cleaners must not be used to clean
e-coated coils. These cleaners can be very difficult to rinse out of the coil
and can accelerate corrosion and attack the e-coating. If there is dirt below
the surface of the coil, use the recommended coil cleaners.
For routine quarterly cleaning, first clean the coil with the below approved
coil cleaner. After cleaning the coils with the approved cleaning agent, use
the approved chloride remover to remove soluble salts and revitalize the unit.
Recommended Coil Cleaner The following cleaning agent, when used in accordance
with the manufacturer’s directions on the container for proper mixing and
cleaning, has been approved for use on e-coated coils to remove mold, mildew,
dust, soot, greasy residue, lint, and other particulate:
Enviro-Coil Cleaner: AAON PN: V82540
GulfClean TM Coil Cleaner ; AAON PN: G074480
Recommended Chloride Remover GulfClean Salt ReducerTM ; AAON PN: G074490
GulfClean Salt ReducerTM is used to remove soluble salts from the e-coated
coil, follow the manufacturer’s instructions. This product is not intended for
use as a degreaser. Any grease or oil film must first be removed with
GulfClean TM Coil Cleaner.
Remove Barrier – First ensure the power to the unit is off and locked out.
Clean the area around the unit if needed to ensure leaves, grass or loose
debris will not be blown into the coil. Soluble salts adhere themselves to the
substrate. For the effective use of this product, the product must be able to
come in contact with the salts. These salts may be beneath any soils, grease
or dirt; therefore, these barriers must be removed prior to application of
this product. As in all surface preparation, the best work yields the best
results.
Application- Apply GulfClean TM Coil Cleaner directly onto the substrate.
Sufficient product must be applied uniformly across the substrate to
thoroughly wet out surface, with no areas missed. This may be accomplished by
use of a pump-up sprayer or conventional spray gun. Apply the cleaner to unit
interior air exiting side coil surfaces first. Work in sections/panels moving
side to side and from top to bottom. Allow the cleaning solution to soak for 5
to 10 minutes. Then move on to the exterior using the same method.
Rinse – Using pressurized potable water such as a garden hose, (< 689.5 kPa
[100 psi]), rinse the coils and continue to always work in sections/panels.
Continue until all coil areas on the inside of the unit have been rinsed.
Note: Coils must always be cleaned / back flushed, opposite of airflow to
prevent impacting the dirt into the coil.
53
Repeat these steps with GulfClean TM Salt Reducer. When finished replace all
panels and tops that were removed.
Service If the unit will not operate correctly and a service company is
required, only a company with service technicians qualified and experienced in
both refrigerant chillers and air conditioning are permitted to service the
systems to keep warranties in effect. If assistance is required, the service
technician must contact AAON.
Warranties Please refer to the limitation of warranties in effect at the time
of purchase.
Replacement Parts Parts for AAON equipment may be obtained by contacting your
local AAON representative. When ordering parts, reference the serial number
and part number located on the external or internal nameplate of the unit.
AAON Warranty, Service and Parts Department 203 Gum Springs Rd. Longview, TX
75602 Ph: 918-382-6450
techsupport@AAON.com www.AAON.com
Note: Before calling, technician must have model and serial number of the unit
available for the service department to help answer questions regarding the
unit.
Warranty: Refer to the Limited Warranty Certificate for the unit warranty
details. Contact your AAON representative for a unit specific copy of the
certificate for your serial number.
54
55
56
Split System Refrigerant Piping Diagrams
Figure 17 – A/C Split System Piping, Suction Down 57
Figure 18 – A/C Split System Piping, Suction Up 58
Figure 19 – A/C with LAC Split System Piping, Suction Down 59
Figure 20 – A/C with LAC Split System Piping, Suction Up 60
Figure 21 – A/C with Modulating Hot Gas Reheat Split System Piping, Suction Down 61
Figure 22 – A/C with Modulating Hot Gas Reheat Split System Piping, Suction Up 62
Figure 23 – A/C with Modulating Hot Gas Reheat Split + LAC System Piping, Suction Down 63
Figure 24 – A/C with Modulating Hot Gas Reheat Split + LAC System Piping, Suction Up 64
Figure 25 – A/C with Hot Gas Bypass Split System Piping, Suction Down 65
Figure 26 – A/C with Hot Gas Bypass Split System Piping, Suction Up 66
Figure 27 – A/C with Hot Gas Bypass + LAC Split System Piping, Suction Down 67
Figure 28 – A/C with Hot Gas Bypass + LAC Split System Piping, Suction Up 68
Figure 29 – A/C with Modulating Hot Gas Reheat and Hot Gas Bypass Split System
Piping, Suction Down
69
Figure 30 – A/C with Modulating Hot Gas Reheat and Hot Gas Bypass Split System
Piping, Suction Up
70
Figure 31 – A/C with Modulating Hot Gas Reheat and Hot Gas Bypass + LAC Split
System Piping, Suction Down
71
Figure 32 – A/C with Modulating Hot Gas Reheat and Hot Gas Bypass + LAC Split
System Piping, Suction Up
72
Figure 33 – Heat Pump Split System Piping, Suction Down 73
Figure 34 – Heat Pump Split System Piping, Suction Up 74
Figure 35 – Heat Pump with Modulating Hot Gas Reheat Split System Piping, Suction Down 75
Figure 36 – Heat Pump with Modulating Hot Gas Reheat Split System Piping, Suction Up 76
Figure 37 – Heat Pump with Hot Gas Bypass Split System Piping, Suction Down 77
Figure 38 – Heat Pump with Hot Gas Bypass Split System Piping, Suction Up 78
Figure 39 – Heat Pump with Modulating Hot Gas Reheat and Hot Gas Bypass Split
System Piping, Suction Down
79
Figure 40 – Heat Pump with Modulating Hot Gas Reheat and Hot Gas Bypass Split
System Piping, Suction Up
80
CF Series Startup Form
Job Name:____ Date:
Address:____
Model Number:____ Serial Number: Tag:__ Startup Contractor:____ Address:____ ___ Phone:_
Pre Startup Checklist Installing contractor must verify the following items.
- Is there any visible shipping damage? 2. Is the unit level? 3. Are the unit
clearances adequate for service and operation? 4. Do all access doors open
freely and are the handles operational? 5. Have all shipping braces been
removed? 6. Have all electrical connections been tested for tightness? 7. Does
the electrical service correspond to the unit nameplate? 8. On 208/230V units,
has transformer tap been checked? 9. Has overcurrent protection been installed
to match the unit nameplate
requirement? 10. Have all set screws on the fans been tightened? 11. Do all fans rotate freely?
Yes No Yes No Yes No Yes No Yes No Yes No Yes No Yes No
Yes No Yes No Yes No
Ambient Temperature Ambient Dry Bulb Temperature °C/°F Ambient Wet Bulb Temperature °C/°F
Voltage L1-L2
L2-L3
L1-L3
L1-Ground
L2-Ground
L3-Ground
Compressors/DX Cooling Check Rotation
Number
1 2 3 4
Model #
L1
L2
L3
Volts/Amps Volts/Amps Volts/Amps
Head Pressure
Suction Pressure
Crankcase Heater Amps
Refrigeration System 1 – Cooling Mode
Pressure
Saturated Temperature
Discharge
Suction
Liquid
Line Temperature
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 2 – Cooling Mode
Pressure
Saturated Temperature
Discharge
Suction
Liquid
Line Temperature
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 3 – Cooling Mode
Pressure
Saturated Temperature
Discharge
Suction
Liquid
Line Temperature
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 4 – Cooling Mode
Pressure
Saturated Temperature
Discharge
Suction
Liquid
Line Temperature
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 1 – Heating Mode (Heat Pump Only)
Pressure
Saturated
Line
Temperature Temperature
Discharge
Suction
Liquid
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 2 – Heating Mode (Heat Pump Only)
Pressure
Saturated
Line
Temperature Temperature
Discharge
Suction
Liquid
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 3 – Heating Mode (Heat Pump Only)
Pressure
Saturated
Line
Temperature Temperature
Discharge
Suction
Liquid
Sub-cooling
N/A N/A
Superheat N/A
N/A
Refrigeration System 4 – Heating Mode (Heat Pump Only)
Pressure
Saturated
Line
Temperature Temperature
Discharge
Suction
Liquid
Sub-cooling
N/A N/A
Superheat N/A
N/A
Condenser Fans
Alignment
Number
hp
1
2
3
4
Check Rotation
Nameplate Amps____
L1 Volts/Amps
L2 Volts/Amps
L3 Volts/Amps
Maintenance Log This log must be kept with the unit. It is the responsibility of the owner and/or maintenance/service contractor to document any service, repair or adjustments. AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts. The responsibility for proper start-up, maintenance and servicing of the equipment falls to the owner and qualified licensed technician.
Entry Date
Action Taken
Name/Tel.
Maintenance Log (E-Coated Coil)
Literature Change History
July 2015 Initial version
March 2016 Clarified forklift instructions and removed wording about curb
mounting.
June 2016 Updated CF Series Features and Options Introduction. Added Feature
17 Shipping Options in the Feature String Nomenclature. Added Storage
information. Added Table for Service Clearances. Clarified Low Ambient section
and added a picture of an adjustable fan cycle switch. Added guidelines for
variable capacity compressors and tandem compressors in the line sizing
section. Added double riser schematics and discussion for heat pump operation.
Added a section on compressor lockouts. Included heat pump charging guidelines
in the Acceptable Refrigeration Circuit Values Table. Added Special Low
Ambient Option Charging Instructions. Added A/C with LAC Piping to show low
ambient piping which is internal to the condensing unit.
March 2017 Updated Piping Diagrams because receivers are now factory installed
in CF 2-7 tons.
April 2017 Updated service clearances tables and added a table for coil pull.
Updated orientation of the CF 9-70 ton. Added a note that AAON does not allow
underground refrigerant lines. Added clarification to the liquid line solenoid
valve recommendation. Added a double suction risers figure. Removed solenoid
valve recommendation on the heat pump double risers and updated the figures.
Added a suction line traps section. Changed the suction flow minimum velocity
for variable compressors. Changed the caution note by removing the variable
capacity compressor wording. Added discharge line sizing guidelines. Removed
the hot gas bypass piping considerations for evaporator below condensing unit
since they are the same as for evaporator above condensing unit. Added a
figure for oil return line. Changed the maximum hot gas maximum velocity from
4,000 fpm to 3,500 fpm. Changed the sub-cooling values in the Acceptable
Refrigeration Circuit Values table. Updated heat pump piping diagrams to
include suction/discharge line traps in suction down diagrams. Added all the
LAC piping diagrams.
October 2017 Updated digital compressor discharge up minimum velocity. Updated
charge information. Updated phase imbalance example. Added Air Cooled
Condenser Option in A1 Compressor Style. Added No Cooling Option in A5
Staging. Added Orion VCCX.
March 2018 Added AAON Touchscreen Controller feature 8B. Updated Refrigerant
Piping section to match the DX Handbook. Added note about running variable
capacity compressors at 100% for 1 minute when starting. Updated Acceptable
Refrigeration Circuit Values Table and notes. Updated piping diagrams with
3-way reheat valve.
May 2018 Updated technical support contact information.
June 2018 Updated E-coated coil cleaning procedure. Added split system
evacuation procedure for low ambient and modulating hot gas reheat.
November 2018 Added Feature Options N = ECM Condenser Fan Head Pressure
Control + Low Sound Condenser Fan & S to Feature 13. Added Standard Evacuation
Instructions & Low Ambient & Modulating Reheat System Evacuation Instructions
to Installation section. Updated Special Low Ambient Option Charging
Instructions and the LAC Valve Piping Schematic figure.
February 2019 Changed WattMaster to Orion. Added Do Not Overcharge note to
Acceptable Refrigeration Circuit Values table.
May 2019 Added the minimum/maximum voltage range table in the Electrical
section.
July 2019 Removed most references to PVE oils except in the caution boxes.
October 2019 Updated mounting section to clarify spring isolation mounting
instructions.
April 2020 Minor changes to wording for print.
August 2020 Revised compressor cycling to 3 minute minimum off time. Revised
measurement of suction line temperature and pressure to be taken at the
evaporator. Revised wording for oil return line. Updated the Nameplate Voltage
Markings and Tolerance table. Updated phase imbalance example. Revised the
e-coated coil cleaning section. Added Voltage check to the startup form. Added
the AAON E-Coated Coil Maintenance Record.
August 2021 Added option J = AAON Refrigeration Systems Supervisory Controls
under Feature 8B. Updated the suction line & discharge line traps to include
wording for a trap at the bottom of the vertical run. Added Enviro-Coil
Cleaner.
December 2021 Added microchannel condenser coil option to Feature A2. Added
10kAIC option to Feature 16. Added Acceptable Microchannel Air-Cooled
Condenser Coil Liquid Sub-Cooling Values table. Added microchannel cleaning
section. Added Estimated R410A Refrigerant Charge per 5ft table to help with
initial charge estimates based on refrigerant line lengths. Updated values in
the Charge to Flood Condenser Coil for Ambient Above 70°F table and added a
table for microchannel condenser coils.
July 2022 Added the clarification that “ACR” rigid copper tubing must be used
for connecting copper.
December 2022 Added obsolete options in the feature string nomenclature for
historical reference. Added TwoStage Refrigeration system options M and N to
Model Option A5.
September 2023 Added all information pertaining to UL-60335 standard. Included
metric units with all imperial units. Added R-454b P.T. tables.
AAON 203 Gum Springs Rd. Longview, TX 75602-1721
www.AAON.com
CF Series Installation, Operation &
Maintenance V04410 Rev. A 230927
(ACP J000237)
Factory Technical Support: 918-382-6450
Note: Before calling Technical Support, please have the model and serial
number of the unit available.
Parts: For replacement parts, please contact your local AAON Representative.
It is the intent of AAON to provide accurate and current product information.
However, in the interest of product improvement, AAON reserves the right to
change pricing, specifications, and/or design of its product without notice,
obligation, or liability.
Copyright © AAON, all rights reserved throughout the world. AAON® and
AAONAIRE® are registered trademarks of AAON, Inc., Tulsa, OK.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>