HASWILL ELECTRONICS STC-9100 Thermostat Refrigeration or Defrosting and Alarm Output Controller User Manual

June 11, 2024
HASWILL ELECTRONICS

HASWILL Logo User Manual of STC-9100 Thermostat
Refrigeration & Defrosting & Alarm Output Controller
(Version 22.11.07GEN)

The STC-9100 temperature controller controls the power supply status of the connected Refrigeration device, defrosting unit, and the Alarm output, typically suited to ultra-low temperature walk-in freezer room;
It could wire an external alarm apparatus to remind users once error.

Package

Controller: 1PCS Sensor: 2PCS Clips: 2PCS Manual:1 PCS Waterproof Cover: 1PCS

Specification

Input Power 220V AC ± 10% 50/60HZ; (12/24/48/110V Option)
Maximum current 8A (Default) under 250V AC
Thermistor / Sensor NTC, 25°C /10 KΩ, the sensor cable 200cm
Protection Class IP65 to the front panel
Storage -10°C ~ 60°C, RH<90%, without condensation
Temperature Range Measurable: -50.0°C ~ +50.0°C; Controllable: -50.0°C ~

+50.0°C
Resolution| 0.1°C
Accuracy| ± 1°C from -40°C to +50°C; ± 2°C in other range
ower Consumption| ≤ 3W

Environmental Information

**** The package’s material is 100% recyclable. Just dispose of it through specialized recyclers.
The electro components can be recycled if it is disassembled for specialized companies.
Please do not burn or throw the controllers in domestic garbage; observe the respective law in your region concerning the environmentally responsible manner of disposing of its devices.

Appearance & Operation

4.1. Front Panel & Operation

Under normal status, the screen shows room sensor temp.HASWILL ELECTRONICS
STC-9100 Thermostat Refrigeration or Defrosting and Alarm Output
ControllerA. Hold the for 3s to enter/exit the user setting interface to check and modify the set-point and the hysteresis here.
B. Hold the and key at the same time for 10s to lock/unlock the admin menu:
OFF = unlock, editable
ON = locked, only can check the value, not editable.
C. Hold the and keys for 10s to enter admin interface; Press the to check current data, and press the or key to change the data; Press the again to save data and back to menu list; If without operated in 10s, the new data will be auto-saved.
The latest and easiest PDF instruction of STC-9100 temperature
D. Hold the for 3s to check the defrost sensor temperature.
E. Hold the for 3s to trigger the forced refrigeration mode manually (conditions in 5.3); do it again to quit.
F. Hold the for 3s to trigger the forced defrosting mode manually (conditions in 5.2); do it again to enter defrosting water dripping status.
4.2. Indicator / Character in Display

Indicator| | | |
---|---|---|---|---
Meaning| Compressor status| Setting Status| Alarm Status| Defrosting status
On| Working| Setting| Working| Working
Hide| Stop| Normal| Normal| Stop
Wink| Time Delay| N/A| N/A| Dripping Water
Fast Wink| Manually Refrigeration| N/A| N/A| Manually Defrosting

4.3. Dimensions & Installation

HASWILL ELECTRONICS STC-9100 Thermostat Refrigeration or Defrosting and
Alarm Output Controller - Dimensions

  1. Mount size: 712985 mm (WHD);
  2. Detach the slide fasteners, put the controller into the hole, and wire it.
  3. Install the fasteners and the waterproof cover.

4.4. Wiring Diagram

HASWILL ELECTRONICS STC-9100 Thermostat Refrigeration or Defrosting and
Alarm Output Controller - Dimensions 1

A. 10K NTC sensor, need not distinguish + or -.
B. The input voltage must be within the voltage value marked in the diagram ±10% value.
C. Suggest Load Power

4.5. Copykey (Optional)
A. Upload to Controller

  1. Insert the Copykey, Press the key, the display shows “UPL”;
  2. Now Press the key to upload data will show “END” once finished;
  3. Shut down the controller and pull out the Copykey.

B. Download from Controller

  1. Assure controller being shut down and insert the Copykey, then starting up
  2. The controller will scan the Copykey and download data automatically, shows “DOL” when downloading, and shows “END” once finished.
  3. Restart the controller; it will work according to the new data.

Attention:

  • Part of the parameters will be executed in the next cycle; please power off the controller and power back to start a new process for running by the new data without a wait.
  • If a parameter in Copykey exists error or is in the wrong format, the display shows ERR.

Configurations

5.1. Code and Function Menu
Hold the + keys at the same time for 10s to enter the Admin Interface The codes SET and HY (F01 and F02) are the user menu. Others are admin menu, ref 4.1 A & C

HASWILL ELECTRONICS STC-9100 Thermostat Refrigeration or Defrosting and
Alarm Output Controller - Dimensions2

The EN code menu and the F code menu are same, just for satisfy different clients.

HASWILL Icon 13

5.2. When will the Defrosting Starts / Stops?
STC-9100 temperature controller user manual from Haswill Electronics teaches you
A. Defrost relay will close/on when reaching all the below conditions

  • The time should later than: the compressor last stops moment + if the defrosting
    Mode was thermal air / Hot Gas ( ).

  • The defrost sensor temperature < Defrost stop temperature (in )

  • Time passed the defrosting cycle time ) or forced defrosting beginning
    B. Defrost relay will open/off when reaching any one of the below conditions

  • The defrost sensor temperature ≥ Defrost stop temperature (in )

  • Passed the defrosting Lasting Time (MDF/F07)

5.3. When will the Compressor Start / Stop?
The room temperature was supposed to keep at the range from “ ).”
The time should be later than the compressor last stops moment + AC/F05, and then
A. If TDF/F10 = EL/0 (like an electric heating wire wound around the evaporator)

Controller Status Start Condition Stop Condition
Forced defrosting Room Temp The dripping time is over (ref 41 F) Room Temp

or defrosting beginning ; or forced Refrigeration is over.
Not in defrosting| Room Temp

B. If (Hot Gas from the compressor Reverse Rotary), 1 more status than A

Code| Troublesome From|

Reason

---|---|---
| Room Sensor| Open or short
| Temperature not in the measurable range
| >Temp. < Max measurable limits 50°C
| Temp. > Min measurable limits -50°C
| Defrost Sensor| Open or short
| Temperature not in the measurable range
| Temp. < Max measurable limits 50°C
| Temp. > Min measurable limits -50°C

Video on YouTube
Haswill Electronics
https://www.thermo-hygro.com
Copyright Haswill-Haswell All Rights Reserved https://www.thermo- hygro.com/

Documents / Resources

| HASWILL ELECTRONICS STC-9100 Thermostat Refrigeration or Defrosting and Alarm Output Controller [pdf] User Manual
STC-9100, STC-9100 Thermostat Refrigeration or Defrosting and Alarm Output Controller, Thermostat Refrigeration or Defrosting and Alarm Output Controller
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

HASWILL ELECTRONICS User Manuals

Related Manuals