OLIMPIA SPLENDID Bi2 WALL High Wall Fan Coil Units Owner’s Manual
- June 9, 2024
- OLIMPIA SPLENDID
Table of Contents
OLIMPIA SPLENDID Bi2 WALL High Wall Fan Coil Units
FEATURES
- Heats, Cools, Dehumidifies, and Filters
- Brushless DC motor
- Equipped with a large motorized flap
- Total flat aesthetics
- Compact: Thickness min. 12.9 cm max 15 cm.
- A range consisting of 3 models of different power.
- Fan coil unit supplied with 2 or 3-way valve integrated with 4-wire electrothermic actuators.
- Monobloc body for comfortable working.
- Motorized steel air delivery flap.
- Extractable filters are placed on the air intake.
- Remote control supplied (only for TR control)
- Robust metal body
- Available in the colors: White RAL 9003
REVERSIBLE
By rotating the display, Bi2 Wall can be installed as a split unit or a
console machine.
FAMILY FEELING
Similar design as the Bi2 Air terminal to allow aesthetically coordinated
installations in the same environment.
MULTISET CONTROL
Integrated electronics allows touch operation, remote control and home
automation connection.
INTEGRATED CONTROLS AS STANDARD
TR (Touch Remote) CONTROL:
includes onboard touch control and remote control (supplied). Additionally,
through a combination of keys, it is possible to remotely* control with a
B0736 wall remote control or a home automation control (SiOS Control by
Olimpia Splendid or MyHome by Bticino), via the Modbus RS485 ASCII serial
protocol.
AR (Analog Remote) CONTROL:
allows remote control by interfacing with wall controls or home automation
control systems via 0-10V analog input or contacts (for radiant fan coil
units, use the contact mode). It has a 230Vac output for control of a solenoid
valve and a water probe inlet with the function of a minimum probe (only for
use in contact mode). AR models on request.
LAYOUT, DIMENSIONS, WEIGHT
TECHNICAL DATA
TECHNICAL DATA| | 400| | | 600| | | 800|
---|---|---|---|---|---|---|---|---|---
SLW inverter (with 2-way valve and TR command)| 01784| 01785| 01786
SLW inverter (with 2-way valve and AR command)| 01875| 01876| 01877
SLW inverter (with 3-way valve and TR command)
SLW inverter (with 3-way valve and AR command)
| 01787| 01788| 01789
01878| 01879| 01880
Fan speed| Lower| Middle| High| Lower| Middle| High| Lower| Middle| High
Total power output in cooling mode| a27/19 – w7/12| (a)| (E)| kW| 0.52| 0.71|
1.01| 0.69| 0.89| 1.23| 0.77| 1.09| 1.82
Sensitive power output in cooling mode| a27/19 – w7/12| (a)| (E)| kW| 0.42|
0.59| 0.91| 0.58| 0.80| 1.15| 0.65| 0.95| 1.47
Fluid flow rate| a27/19 – w7/12| (a)| | l/h| 90.6| 124.0| 177.0| 120.1|
155.1| 215.5| 134.0| 189.7| 317.7
Water side head loss| a27/19 – w7/12| (a)| (E)| kPa| 2.8| 5.2| 8.9| 4.9| 6|
7.9| 2.1| 4.8| 11
Total power output in heating mode| a20/15 – w50/-| (b)| (E)| kW| 0.67| 0.99|
1.55| 0.98| 1.37| 2.16| 1.14| 1.68| 2.85
Fluid flow rate| a20/15 – w50/-| (b)| | l/h| 90.6| 124.0| 177.0| 120.1|
155.1| 215.5| 134.0| 189.7| 317.7
Water side head loss| a20/15 – w50/-| (b)| (E)| kPa| 2.4| 4.5| 7.1| 1.9| 2.9|
2.5| 2.0| 4.6| 8.8
Total power output in heating mode| a20/15 – w45/40| (c)| (E)| kW| 0.58| 0.86|
1.40| 0.86| 1.20| 1.90| 0.99| 1.45| 2.50
Fluid flow rate| a20/15 – w45/40| (c)| | l/h| 99.1| 146.3| 237.5| 146.5|
204.6| 322.8| 168.1| 247.8| 425.4
Water side head loss| a20/15 – w45/40| (c)| (E)| kPa| 3.4| 6.7| 11.6| 6.7|
11.9| 5.4| 8.5| 16.4| 15.3
Absorbed power| | | (E)| W| 7| 11| 19| 8| 12| 23| 9| 13| 27
Sound Power Lw (A)| | | (E)| dB(A)| 43| 49| 57| 43| 50| 58| 43| 50| 58
Sound pressure Lp (A)| | (d)| | dB(A)| 34| 40| 48| 34| 41| 49| 34| 41| 49
Air flow rate| | (f)| | m3/h| 140| 190| 290| 190| 260| 400| 200| 280| 430
Battery water content| | | | l| 0.3| 0.4| 0.5
Maximum operating pressure| | | | bar| 8| 8| 8
Hydraulic fittings| | | | inch| Eurocone 3/4| Eurocone 3/4| Eurocone 3/4
Electrical power supply| | | | V/ph/Hz| 230/1/50| 230/1/50| 230/1/50
Max static heating efficiency (50°C)| | | | kW| –| –| –
Max static heating efficiency (70°C)| | | | kW| –| –| –
The water content of the radiant panel| | | | l| –| –| –
The above services refer to the following operating conditions:
- (a) Cooling mode at standard conditions: air temperature 27°C b.s. 19°C b.u., water inlet temperature 7°C, water outlet temperature 12°C
- (b) Heating mode conditions of use 1: air temperature 20°C b.s., 15°C b.u. max, water inlet temperature 50°C, water flow equal to the cooling water standard condition
- (c) Heating mode standard conditions: air temperature 20°C b.s., 15°C b.u. max, water inlet temperature 45°C, water outlet temperature 40°C
- (d) Sound pressure level valid for closed rooms with a volume of 100 m3 with a reverberation time of 0.5 s and installation on the floor/ceiling, sound emission on 1/4 sphere at 3 m distance
- (E) Eurovent-certified data
- (f) Air flow rate measured with clean filters
ACCESSORIES
COMMANDS | B0736 | Wall-mounted Modbus chrono-thermostat kit | TR |
---|---|---|---|
B0921 | Contact touch wall-mounted thermostat kit | AR | |
INDRZ | Addressing of the Modbus control kit | TR | |
BMS00 | Configuration for management with BMS systems – AR controls | AR |
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>