COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector Instruction Manual

June 10, 2024
COOPER Lighting

PORTFOLIO
IB520115ML
Installation Instructions – LDSQ4B/LDSQ6B Commercial
Recessed LED Rough-In
COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector
-

LDSQ4B LED Housing LED Reflector Downlight Reflector

IMPORTANT: Read carefully before installing fixture.
Retain for future reference.

WARNING
Risk Of Electrical Shock! Disconnect power at fuse or circuit breaker before installing or servicing.
WARNING
Risk Of Fire! Do not install insulation within 3 inches (76 mm) of any part of the luminaire fixture or in a way that may entrap heat.
WARNING
Installation and servicing to be performed only by qualified personnel. If not qualified, consult an electrician.
WARNING
Do not energize the LED Engine until the protective covering has been removed and the lower trim properly installed. Do not touch the yellow surface of the LED as it may damage the light engine.
Note: This fixture should be supported by main runners or other structure that is capable of supporting fixture weight of 30 Ibs.
SAFETY: When using electrical equipment, basic safety precautions should always be followed, including the following:

  1. This unit is for recessed mounting only. Do not use in hazardous locations nor near gas or electric heaters.
  2. Do not use this equipment for other than the intended use.
  3. Install only in accordance with National Electrical Code and local regulatory agencies’ requirements.

| Aperture| Ceiling Cutout
---|---|---
LDSQ4| 4-1/2″ x 4-1/2″| 5-1/4″ x 5-1/4″
LDSQ6| 6” x 6”| 6-3/4″ x 6-3/4″

INSTALLATION

Rough-In Section

  1. Install fixture into ceiling cavity using 1/2˝ electrical conduit. Use 3/4˝ channel, 1-1/2˝ channel, 1/8˝ x 1/2˝ bar stock, or T-bar fasteners as mounting rails (furnished by others) by inserting the through hanger brackets at both sides.
  2. Adjust hanger adjustment screws (Figure 1.) so bottom of square neck is flush with finished ceiling line. (Figure 2.) Hanger bracket is reversible for total adjustment of 5˝.
  3. (Height): Square neck can also be adjusted by loosening the 3 thumbscrews and adjusting such that the neck is flush with the ceiling. Once desired height is achieved, tighten thumb screws (Figure 1.).
  4. (Rotation): If rotation of the square neck is required, loosen 2 thumbscrews. Rotate the square neck to the desired position. Tighten thumbscrews upon completion (Figure 1.).
  5. Remove one of the junction box covers. Connect supply lead wires to lead wires of driver as per Wiring Diagram and in accordance with your local electrical code(s) or
    N.E.C. (Figure 14.)

Trim Installation

  1. Place end of flexible conduit through frame opening in ceiling exposing upper portion of quick disconnect (Figure 2.).

  2. Remove LED engine from protective packaging.COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 1

  3. Remove trim assembly from protective packaging and rotate side clips (3) outwards. (Figure 4.).COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 2

  4. Insert LED engine on to trim assembly. Align post on LED engine with slot on trim assembly (Figure 5.)COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 5

  5. Rotate side clips (3) into place to securely attach trim assembly to LED engine (Figure 6.).

  6. Trim ring (optional) should be placed between the ceiling and lower trim.
    COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector -
Figure 6

  7. Properly align the connector as shown in (Figure 7.).
    Plug in the luminaire quick disconnect on the module.

  8. Ensure the connector is properly engaged. (Figure 8.).
    COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector -
Figure 7

  9. Install the LED engine and trim assembly by inserting the torsion springs into the spring receivers located inside the housing (Figure 9.).

Cleaning
To Clean Trims:

  1. Press in on white plastic latch to remove upper reflector and clean lens. (Figure 10 & 11.)COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 10
  2. Gently wipe with soft, clean, dry lint-free cloth to remove dust.
  3. Wipe with mild detergent solution on a soft, clean cloth to remove fingerprints and stains.
  4. Rinse with clean water and dry with soft, clean, dry lint-free cloth.

Electrical Connection

CAUTION
Make certain no bare wires are exposed outside of lever nut connectors.

  1. Provide electrical service according to the “National Electrical Code” or your local electrical code to the junction box (located on the plasterframe). Supply wire insulation must be rated for at least 90°C. The junction box is rated for a maximum of 8 No. 12 AWG Branch Circuit conductors and is also suitable for at least 90°C.
  2. Remove junction box cover (Figure 12.).COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 12
  3. Remove appropriate round pryout and connect conduit to junction box with proper connector (not included).
  4. Connect supply lead wires to junction box lead wires (line, neutral and ground) in the fixture using the provided lever nut connectors. (Figure 14). Be careful not to leave any bare conductors outside of the lever nut connectors.
  5. Lift the orange tab on the lever nut to disengage the wire and close to secure the wire in place. (Figure 14).COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 14
  6. Connect white to white, black to black, and green (from electrical service) on the supply side to the bare copper wire in the junction box. Place all excess wiring and connections into the junction box and replace the cover. Place all connections and excess wiring into the junction box and replace cover.

Driver Replacement
CAUTION
To avoid possible electrical shock, be sure that the power is turned off before installing or servicing this fixture.

  • The driver should be replaced by a qualified electrician.
  • The driver may be replaced either from below or above the ceiling.
  1. Remove trim assembly from the housing (Figure 9.).
  2. Remove the driver and junction box cover assembly. (Figure 13.).COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 13
  3. Disconnect the wiring to the driver by undoing the lever nut connectors then cut the red and blue wires.
  4. Discard the old driver and junction box cover assembly.
  5. Connect the new driver leads with the lever nut connectors.
  6. Reattach the new driver and junction box cover assembly.

Wiring Diagrams

  1. For D010COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - Figure 15
  2. For D010TRCOOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For D010TR
  3. For D010TECOOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For D010TE
  4. For DL2COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For DL2
  5. For DL3COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For DL3
  6. For DLECOOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For DLE
  7. For DE010COOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For DE010
  8. For D5LTCOOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For D5LT
  9. For DMXCOOPER Lighting LDSQ4B LED Housing LED Reflector Downlight Reflector - For DMX
  • Constructions built before Jan 2022 may have gray wire for 0-10 dimming control present. In these cases, the installer will label the gray building wire as a 0-10 dimming wire and connect to our product’s pink 0-10V dimming control wire. Reference NFPA70 (2020 NEC), section 410.69.

Dimming
The Portfolio LDSQ4D010/LDSQ6D010 Series can be dimmed with many standard 0-10V DC dimming controls. The Portfolio LDSQ4DL3/LDSQ6DL3 Series can be dimmed with Lutron 3-wire fluorescent and EcoSystem® digital controls.
The Portfolio LDSQ4DL2/LDSQ6DL2 Series can be dimmed with Lutron 2-wire forward phase controls. The Portfolio LDSQ4D010TR/LDSQ6D010TR Series can be dimmed with many standard 120V incandescent dimmers, electronic low voltage dimmers and 0-10V DC dimming controls. The Portfolio LDSQ4D5LT/LDSQ6D5LT Series can be dimmed with Fifth Light and DALI compatible controls. The Portfolio LDSQ4DMX/LDSQ6DMX Series can be dimmed with DMX compatible controls. The Portfolio LDSQ4DE010/ LDSQ6DE010 Series can be dimmed with 0-10V DC dimming controls but are NOT to be dimmed using line voltage dimmers. To be assured of the latest information regarding luminaire and dimmer compatibility, please reference the Portfolio LED website: www.portfolio- lighting.com.

Installation Instructions – LDSQ4B/LDSQ6B Commercial Recessed LED Rough-In
IB520115ML www.cooperlighting.com

Warranties and Limitation of Liability
Please refer to www.cooperlighting.com/legal for our terms and conditions.

FCC Statement
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

  • Reorient or relocate the receiving antenna.

  • Increase the separation between the equipment and receiver.

  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

  • Consult the dealer or an experienced radio/TV technician for help.

  • This device complies with Part 15 of the FCC Rules.
    Operation is subject to the following two conditions:
    (1) this device may not cause harmful interference, and
    (2) this device must accept any interference received, including interference that may cause undesired operation.

  •  This device complies with ISED ICES Standard Canada ICES-005 (A) / NMB-005 (A) or ICES-005 (B) / NMB-005 (B) depending on driver selected.
    Any changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2021 Cooper Lighting Solutions
All Rights Reserved
Printed in USA
Publication No. IB520115ML
October 26, 2021
Cooper Lighting Solutions is a registered trademark.
All trademarks are property of their respective owners.
Product availability, specifications, and compliances are subject to change without notice.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

COOPER Lighting User Manuals

Related Manuals