Features

  • Universal AC input / Full range
  • Built-in active PFC function
  • High efficiency up to 92%
  • Forced air cooling by built-in DC fan
  • Output voltage and constant current level programmable
  • Built-in remote ON-OFF control/ remote sense auxiliary power/ DC OK signal
  • Protections: Short circuit/Overload/Over voltage/Over temperature
  • Optional conformal coating
  • 5 years warranty

Dimension

Applications

  • Factory control or automation apparatus
  • Test and measurement instrument
  • Laser related machine
  • Burn-in facility
  • RF application

GTIN CODE

MW Search : https://www.meanwell.comiserviceGTIN.aspx

Description

RSP-750 is a 750W single output enclosed type AC/DC power supply. This series operates for 90-264 VAC nput voltage and offers the models with the DC output mostly demanded from the industry. Each model is cooled by the built-in fan with fan speed control, working for the temperature up to 70C. Moreover, RSP-750 provides vast design flexibility by equipping various built-in functions such as the output programming, remote ON-OFF control, auxiliary power, etc.

Model Encoding/ Order InformationMEAN-WELL RSP-750-Series-750W-Power-
Supply-with-Single-Output-FIG- \(4\)

SPECIFICATION

MODEL| RSP-750-5| RSP-750-12| RSP-750-15| RSP-750-24| RSP-750-27| RSP-750-48
---|---|---|---|---|---|---








OUTPUT

| DC VOLTAGE| 5V| 12V| 15V| 24V| 27V| 48V
RATED CURRENT| 100A| 62.5A| 50A| 31.3A| 27.8A| 15.7A
CURRENT RANGE| 0 ~ 100A| 0 ~ 62.5A| 0 ~ 50A| 0 ~ 31.3A| 0 ~ 27.8A| 0 ~ 15.7A
RATED POWER| 500W| 750W| 750W| 751.2W| 750.6W| 753.6W
RIPPLE & NOISE (max.) **Note.2| 150mVp-p| 150mVp-p| 150mVp-p| 150mVp-p| 150mVp-p| 150mVp-p
VOLTAGE ADJ. RANGE| 4.75 ~ 5.5V| 10 ~ 13.5V| 13.5 ~ 16.5V| 20 ~ 26.4V| 24 ~ 30V| 43 ~ 55V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION| ±2.0%| ±0.5%| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 1000ms, 50ms at full load
HOLD UP TIME (Typ.)**| 16ms/230VAC           16ms/115VAC at full load





INPUT

| VOLTAGE RANGE Note.4| 90 ~ 264VAC           127 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| 0.97/230VAC           0.98/115VAC at full load
EFFICIENCY (Typ.)| 82%| 87%| 89%| 90.5%| 90.5%| 92%
AC CURRENT (Typ.)| 5V : 5.6A/115VAC           2.8A/230VAC 12V~48V : 8.2A/115VAC           3.9A/230VAC
INRUSH CURRENT (Typ.)| 25A/115VAC           40A/230VAC
LEAKAGE CURRENT| <2.0mA / 240VAC




PROTECTION

| ****

OVERLOAD

| 105 ~ 125% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed


OVER VOLTAGE (OVP)

| 5.75 ~ 6.75V| 13.8 ~ 16.8V| 17 ~ 20.5V| 27.6 ~ 32.4V| 31 ~ 36.5V| 56.6 ~ 66.2V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after temperature goes down




FUNCTION

| OUTPUT VOLTAGE PROGRAMMABLE(PV)| Adjustment of output voltage is allowable to 40 ~ 110% of nominal output voltage. Please refer to the Function Manual.
CONSTANT CURRENT LEVEL PROGRAMMABLE(PC)| Adjustment of constant current level is allowable to 40 ~ 110% of rated current. Please refer to the Function Manual.
AUXILIARY POWER| 12V @ 0.1A ; tolerance : ±10%
REMOTE ON-OFF CONTROL| Power on : short between Remote ON-OFF(pin13) & 12V-AUX(pin14) on CN50 Power off : open between Remote ON-OFF(pin13) & 12-AUX(pin14) on CN50
DC OK SIGNAL| The TTL signal out, power supply turn on = 0 ~ 1V ; power supply turn off = 3.3 ~ 5.6V




ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes











SAFETY & EMC

(Note 7)

| SAFETY STANDARDS| UL62368-1, CSA C22.2 No. 62368-1, TUV BS EN/EN62368-1, CCC GB4943.1, BSMI CNS14336-1, AS/NZS62368.1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032 (CISPR32)| Class B
Radiated| BS EN/EN55032 (CISPR32)| Class B
Harmonic Current| BS EN/EN61000-3-2| —–
Voltage Flicker| BS EN/EN61000-3-3| —–







EMC IMMUNITY

| BS EN/EN55035, BS EN/EN61000-6-2, CCC GB17625.1,GB/T9254, BSMI CNS13438
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 3
EFT / Burst| BS EN/EN61000-4-4| Level 3
Surge| BS EN/EN61000-4-5| Level 4, 4KV/Line-Earth ; Level 3, 2KV/Line-Line
Conducted| BS EN/EN61000-4-6| Level 3
Magnetic Field| BS EN/EN61000-4-8| Level 4
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,

95% interruptions 250 periods


OTHERS

| MTBF| 1036.8K hrs min.       Telcordia SR-332 (Bellcore) ; 109.2K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 25012741mm (LWH)
PACKING| 1.64Kg; 6pcs/10.8Kg/1.1CUFT
NOTE| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  Derating may be needed under low input voltages. Please check the derating curve for more details.

5.  There is high possibility to trigger the floating over voltage protection when PV voltage is trimmed from a high voltage level to a lower voltage level at light    load or no load condition. It is suggested that turn off the power supply and set PV voltage to the lowest level, then adjust output voltage to a desired value.

6.  Strongly recommended that external output capacitance should not exceed 5000uF. (Only for: RSP-750-5)

7.  The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on a 720mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

8.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-
Output-FIG- \(5\)

Static Characteristics

MODEL

INPUT

| 5V| 12V| 15V
---|---|---|---
__

100~264VAC

| 500W

100A

| 750W

62.5A

| 750W

50A

__

90VAC

| 450W

90A

| 675W

56.25A

| 675W

45A

MODEL

INPUT

| 24V| 27V| 48V
__

100~264VAC

| 751.2W

31.3A

| 750.6W

27.8A

| 753.6W

15.7A

__

90VAC

| 676.08W

28.17A

| 675.54W

25.02A

| 678.24W

14.13A

Derating CurveMEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-
Output-FIG- \(7\)

Efficiency vs Load (48V Model)MEAN-WELL RSP-750-Series-750W-Power-Supply-
with-Single-Output-FIG- \(8\)

Function Manual

Remote Sense
The remote sensing compensates voltage drop on the load wiring up to 0.5V .MEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-Output-FIG-
\(9\)

The +S signal should be connected to the positive terminal of the load whereas-S signal to the negative terminal.
By factory default, on CN50, Remote ON-OFF (pin13) and 12V-AUX (pin14), PV(pin5) and PS (pin6), and PC (pin7) and PO (pin8, respectively, are shorted when shipped. The power supply wll have no output if the shorting connector is not assembled unless certain functin needs to be activated.

Remote ON-OFF

The power supply can be turned ON/OFF by using the “Remote ON-OFF” function .MEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-Output-FIG-
\(10\)

Between Remote ON-OFF(pin13) and 12V-AUX(pin14) Power Supply Status
SW close (Short) ON
SW open (Open) OFF

When multiple power supplies need to turn ON/OFF simultaneously by Remote ON- OFF control, -S & -V on CN50, as well as +S & +V, on each power supply should be connected

Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)

In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 40~110% of the nominal voltage by applying EXTERNAL VOLTAGEMEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-Output-FIG-
\(11\)

If EXTERNAL VOLTAGE (VDC) <0.5V,the power supply may enter under voltage protection; it needs to be restarted to work.
Caution : By factory default, the Output Voltage Programming is not activated, and PV (pin5) and PS(pin6) are shorted by connector. Whenever this function is not needed to activate, as assumed in other sections’ diagrams, please keep PV (pin5) and PS(pin6) shorted ; other wise, the power supply will have no output.

Constant Current Level Programming (or, PC / remote current programming / dynamic current trim)
The constant current level can be trimmed to 40~110% of the rated current by applying EXTERNAL VOLTAGE.MEAN-WELL RSP-750-Series-750W-Power-Supply-with-
Single-Output-FIG- \(12\)

Caution : By factory default, the Output Current Programming is not activated, and PC(pin7) and PO(pin8) are shorted by connector. Whenever this function is not needed to activate, as assumed in other sections’ diagrams, please keep PC(pin7) and PO(pin8) shorted ; otherwise, the power supply will have no output.MEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-
Output-FIG- \(13\)

DC_OK signal
“DC_OK” is an open collector signal. It indicates the output ※ status of the power supply. It can operate in two ways : One is sinking current from external TTL signal ; the other is sending out a TTL voltage signal.

  • Sinking current from external TTL signal: The maximum sink current is 10mA and the maximum external voltage is 5.6V.
  • Sending out TTL voltage signal
    Between DC- OK(pin9) and GND(pin10 &11)| Output Status
    ---|---
    0 ~ 1V| Power supply ON
    3.3 ~ 5.6V| Power supply OFF

MEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-Output-FIG-
\(14\)

Mechanical Specification

MEAN-WELL RSP-750-Series-750W-Power-Supply-
with-Single-Output-FIG- \(15\)

Mounting Instruction

Hole No.| Recommended Screw Size| MAX. Penetration Depth L| Recommended mounting torque
---|---|---|---
1| M4| 6mm| 7~11Kgf-cm
2| M4| 4mm| 7~11Kgf-cm

MEAN-WELL RSP-750-Series-750W-Power-Supply-with-Single-Output-FIG-
\(16\)

Control Pin No. Assignment (CN50) : HRS DF11-14DP-2DS or equivalent

Mating Housing HRS DF11-14DS or equivalent
Terminal HRS DF11-**SC or equivalent
Pin No. Function
--- ---
1 +S
2 +VS

when “output voltage programming” function is in use.
3| -S| Negative sensing for remote sense.
4| -VS| -V Signal. The -VS should be connected to the -S to reduce the noise when “output voltage programming” function is in use.
5| PV| Connect to external DC voltage source for output voltage programming, referenced to pin 10,11 (GND).
6| PS| Reference pin regarding output voltage programming. Please refer to the Function Manual.
7| PC| Connect to external DC voltage source for output current programming.
8| PO| Reference pin regarding output current programming. Please refer to the Function Manual.
9| DC_OK| Open collector signal, referenced to pin10,11(GND). Low when PSU turns on. The maximum sink current is 10mA and the maximum external voltage is 5.6V.
10,11| GND| These pins connect to the negative terminal (-V). Return for DC_OK Signal output.
12| G-AUX| Auxiliary voltage output ground.

The signal return is isolated from the output terminals (+V & -V).

13| REMOTE ON-OFF| Turns the output on and off by electrical or dry contact between pin 13 ( ON/OFF) and pin 14 (12V-AUX). Short: Power ON, Open: Power OFF.
14| 12V-AUX| Auxiliary voltage output, 10.8~13.2V, referenced to pin 12(G-AUX).

The maximum load current is 0.1A. This output is not controlled by the “remote ON/OFF control”.

AC Input Terminal Pin No. AssignmentMEAN-WELL RSP-750-Series-750W-Power-
Supply-with-Single-Output-FIG- \(18\)

DC Output Terminal Pin No. AssignmentMEAN-WELL RSP-750-Series-750W-Power-
Supply-with-Single-Output-FIG- \(19\)

Installation Manual