POTTER PAD100-ZM Conventional Zone Module Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PAD100-ZM Conventional Zone Module
Features
- Compatible with conventional 2-wire smoke detectors
- IDC can be wired One (1) Class A or Two (2) Class B
- Monitors presence of 24VDC Aux Power
- SLC Class A, Class X & Class B
- Mounts in a standard 4” or double gang box
- Wiring terminals accessible when mounted in box
- All wiring terminals accept 22 to 12AWG
- Product includes a 5 year warranty
- UUKL Listed for Smoke Control
Description
The PAD100-ZM module uses one (1) address on an SLC Loop when monitoring two (2) Class B or one (1) Class A circuit. The module requires and supervises a 24VDC auxiliary power connection. The 24VDC power source must be either a Potter IPA series addressable panel, or a Potter PSN series power supply. The IDC may be wired Class B or Class A which is selectable by an on board DIP switch. The PA D100-ZM employs one red LED to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel. When a device is activated, the LED will flash at a fast rate.
Application
The PAD100-ZM is compatible with Potter’s IPA and AFC/ARC series addressable fire alarm control panels. The PAD100-ZM is used to supervise a zone of conventional 2-wire smoke detectors on an Initiating Device Circuit (IDC). The PA D100-ZM is capable of monitoring two (2) separate Class B or one (1) Class A circuits.
Setting the Address
Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the PA D100-ZM. When the PAD100-ZM is used to monitor two individual Class B circuits a single device address is assigned, each input is then identified as a sub-point of the module address. For example, if the address number is assigned as “8”, the B1 input will be “8.1” and the B2 input will be “8.2”.
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:
- Power to the device is removed.
- Field wiring is correctly installed.
- Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage | 24.0V |
---|---|
Max SLC Standby Current | 240μA |
Max SLC alarm Current | 240μA |
aux power Required | 19 – 28V |
Max Detector Standby Current of IDC at 24 VDC | 1ma |
Max Module alarm Current of IDC at 24 VDC | 50ma |
Max Wiring Resistance of IDC | 100Ω |
Max Wiring Capacitance of IDC | 1μF |
eOL Resistor | 5.1K Ω |
Operating Temperature Range | 32 to 120ºF (0 to 49ºC) |
Operating Humidity Range | 0 to 93% (non-condensing) |
Max no. of Module per Loop | 127 units |
Dimensions | 4.17” (106mm)L × 4.17” (106mm)W × 1.14” (29mm)D |
Mounting Options | Standard 4” Square or Double gang Box |
Shipping Weight | 0.6 lbs |
Installation Using Compatible Electrical Box
Wiring Diagrams
Typical Class B Wiring Diagram
Typical Class A Wiring Diagram
Ordering Information
Model | Description | Stock No. |
---|---|---|
paD100-ZM | Conventional Zone Module | 3992706 |
Compatible 2-Wire Smoke Detectors & Bases
Detector Model | Identifier | Base Model | Identifier |
---|
SYSTEM SENSOR (Brk) (Max. No. Of Detectors Per Zone is 10)
1400| a| N/a| N/a
2400| a| N/a| N/a
2400TH| a| N/a| N/a
2W-B| a| N/a| N/a
2WT-B| a| N/a| N/a
DETECTION SYSTEM (Max. No. Of Detectors Per Zone is 11)
DS250| a| MB2W/MB2WL| a
DS250TH| a| MB2W/MB2WL| a
ESL (Max. No. Of Detectors Per Zone is 20)
611U| S10| 601U| S00
611UD| S10| 601U| S00
611UT| S10| 601U| S00
612U| S10| 601U| S00
612UD| S10| 601U| S00
613U5| S10| 601U| S00
611UD| S10| 609U10| S00
612UD| S10| 609U10| S00
425C| S10| N/a| N/a
425CT| S10| N/a| N/a
HOCHIKI (Max. No. Of Detectors Per Zone is 20)
SLR-24| HD-3| HSC-221R| HB-71
| | HSB-221| HB-54
| | HSB-221N| HB-54
| | NS6-221|
| | NS4-221|
| | NS6-220| HB-3
SLR-24H| HD-3| HSC-221R| HB-71
| | HSB-221| HB-54
| | HSB-221N| HB-54
| | NS6-221|
| | NS4-221|
SIJ-24| HD-3| HSC-221R| HB-71
| | HSB-221| HB-54
| | HSB-221N| HB-54
| | NS6-221|
| | NS4-221|
Detector Model| Identifier| Base Model| Identifier
---|---|---|---
FENWAL (Max. No. Of Detectors Per Zone is 14)
CpD-7051| I51Fe1| 2-WIRe| Fe51a
pSD-7155| p55Fe1| 2WRLT| Fe52a
pSD-7156| p56Fe1| 2WRB| Fe55a
all of the above Fenwal detectors and bases can be used in any combination.
Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000
Bases, Models -001, -002, -003, and -005). Duct Housing with Detector Base
DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).
POTTER (Max. No. Of Detectors Per Zone is 25)
pS-24| HD-3 (HOCHIKI)| SB-46| HB-71(HOCHIKI)
| | | HB-54 (HOCHIKI)
| | SB-93| HB-3 (HOCHIKI)
pS-24H| HD-3 (HOCHIKI)| SB-46| HB-71 (HOCHIKI)
| | | HB-54 (HOCHIKI)
IS-24| HD-3 (HOCHIKI)| SB-46| HB-71 (HOCHIKI)
| | | HB-54 (HOCHIKI)
NOTE: If using a mix of System Sensor and other smoke detectors, a
maximum of 20 detectors shall be permitted.