SensoIRIS T110 Intelligent Analogue Addressable Sounder Installation Guide
- August 13, 2024
- SensoIRIS
Table of Contents
T110 Intelligent Analogue Addressable Sounder
Installation Guide
Installation Instruction
ATTENTION: Read carefully this installation Instructions before
installing the device!
This manual is subject to change without notice!
SensoIRIS CSOU is аn addressable sounder with base, compatible for mounting on
all models standard bases for SensoIRIS devices. The sounder is designed for
installing in addressable fire alarm systems which support operation via TTE
communication protocol. The device is powered on from the panel and can be
controlled via the communication protocol.
SensoIRIS CSOU supports 32 different tone types at two sound levels. The tone
type and sound level are0 programmed from the control panel.
The SensoIRIS CSOU is compatible for operation with SensoIRIS addressable
detectors series: T110 (IS), S130 (IS) and M140 (IS).
The sounder is compatible for mounting on the following bases:
- SensoIRIS B124 – Standard low profile base for addressable detectors and sounders.
- SensoIRIS B124-HP – Standard high profile base for addressable detectors and sounders.
- SensoIRIS VAD RST* – Standard base with built-in red LED flash beacons.
- SensoIRIS VAD WST* – Standard base with built-in white LED flash beacons.
-
The base SensoIRIS VAD RST/WST is specially designed for use with SensoIRIS CSOU sounders, as expands their application in fire alarm installations providing additional lighting indication in case of fire alarm events.
Installation Instructions
Attention: Power off the loop circuit before installing the SensoIRIS CSOU addressable sounder!-
Choose the proper place for installation of the device.
-
Set the device address using SensoIRIS Programmer or directly from addressable fire panel. The address must be in the range from 1 to 250.
-
Mount the standard base (SensoIRIS B124/B124-HP or SensoIRIS VAD RST/WST), choosing the type according the requirement of the installation. If you want to “lock” the sounder to the standard base, remove the little “tooth” on the top of the locking mechanism of the base.
-
Connect the standard base to the fire panel using the wiring diagrams.
-
Insert the SensoIRIS CSOU sounder into the standard base and rotate it clockwise until it drops into place – the short mark on the standard base fits with the long mark on the sounder body. Continue to rotate the sounder until the short and the long marks coincides with those on the base – a click is heard.
-
Insert a detector – SensoIRIS T110 (IS)/ S130 (IS)/ M140 (IS) – into the sounder base and rotate clockwise until it drops into place – the short mark on the sounder fits with that on the detector. Continue to rotate the detector until its mark coincides with the long mark on the sounder – a click is heard. If you want to “lock” the detector to the sounder before installation, remove the little “tooth” on the top of the locking mechanism of the sounder. Note: The mounted detector on the SensoIRIS CSOU sounder is assigned at different address to the control panel!
-
Program the sounder parameters. Choose in consecutiveness from the IRIS/SIMPO control panel: System – Programming – Devices – Loop. Find the installed sounder, as enter address, loop and zone number – the panel automatically will recognize its type. Choose the button MORE to enter in the additional settings menu and to review the SW version and ID number of the sounder.
When the sounder is mounted on B124 or B124-HP base, it is recognized from the panel as “CSOU”. When the sounder in mounted on VAD RST or VAD WST base, it is recognized from the panel as “CSOU / VAD”. -
Test the sounder for proper operation.
-
If the sounder has been locked to the base, to remove it for a service schedule maintenance and cleaning, you have to use the special tool available in all SensoIRIS standard bases. Light press with the tool into the base opening and at the same time rotate the sounder body counter-clockwise. The same way is used for unlocking a detector from the SensoIRIS CSOU addressable sounder.
-
Warranty
All devices carry on a warranty valid from the date of manufacture. The date
of manufacture can be checked on the device. The first two numbers represent
the year and the last two – the month. For example: The date code “21 07”,
means the sounder is manufactured in July, 2021.
To return goods for warranty service, please contact with your local
distributer for details.
TECHNICAL SPECIFICATIONS
- SensoIRIS CSOU
Operating Voltage Range | 16 – 32VDC |
---|---|
Maximal consumption at communication | 470 μА @ 27VDC |
Maximal consumption: | |
main tone type 27, low volume level | 3 mА @ 27VDC |
main tone type 27, high volume level | 10 mА @ 27VDC |
Power volume (main tone type 27): | |
low volume (up to 100 pcs sounders* to the loop) | ~ 81dB (A) ± 3dB @ 1m |
high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
Power volume (other tone types): | |
low volume (up to 100 pcs sounders* to the loop) | ~ 81dB (A) ± 3dB @ 1m |
high volume (up to 30 pcs sounders* to the loop) | ~ 87dB (A) ± 3dB @ 1m |
Number of tone types | 32 |
Supported communication protocol | ТТЕ |
Relative humidity resistance | (93 ± 3)% @ +40°C |
Color | White/ бял |
Material | ABS |
Dimensions | 105 х 22 mm |
Connection Diagram
Attention: DO NOT CONNECT the Earth terminal ( ) of B124 and B124-HP
bases to the loop line! Legend
RI – Remote Indicator
+Loop – Positive loop wire
-Loop – Negative loop wire
Mounting of T110 IS, S130 IS and M140 IS to the CSOU sounder and using the
built-in isolator in the detector.
Mounting of T110, S130 and M140 to the CSOU sounder; Mounting of T110 IS, S130
IS and M140 IS to the CSOU sounder and not using the built-in isolator in the
detector.
Installation At the end of installation, the long marks of the standard
base and CSOU sounder must coincide with the single mark of the mounted
detector.
Tone types and description
Tone | Tone Type | Tone Description / Application |
---|---|---|
1 | 970Hz | |
2 | 800Hz/970Hz @ 2Hz | |
3 | 800Hz – 970Hz @ 1Hz | |
4 | 970Hz 1s OFF/1s ON | |
5 | 970Hz, 0.5s/ 630Hz, 0.5s | |
6 | 554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001) | |
7 | 500 – 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000) | |
8 | 420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone) | |
9 | 500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF (AS1670 Evacuation) | |
10 | 550Hz/440Hz @ 0.5Hz | |
11 | 970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201) | |
12 | 2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201) | |
13 | 1200Hz – 500Hz @ 1Hz (DIN 33 404) | |
14 | 400Hz | |
15 | 550Hz, 0.7s/1000Hz, 0.33s | |
16 | 1500Hz – 2700Hz @ 3Hz | |
17 | 750Hz | |
18 | 2400Hz | |
19 | 660Hz | |
20 | 660Hz 1.8s ON/1.8s OFF | |
21 | 660Hz 0.15s ON/0.15s OFF | |
22 | 510Hz, 0.25s/ 610Hz, 0.25s | |
23 | 800/1000Hz 0.5s each (1Hz) | |
24 | 250Hz – 1200Hz @ 12Hz | |
25 | 500Hz – 1200Hz @ 0.33Hz | |
26 | 2400Hz – 2900Hz @ 9Hz | |
27 | 2400Hz – 2900Hz @ 3Hz (2500Hz – main sound frequency | |
28 | 800Hz – 970Hz @ 100Hz | |
29 | 800Hz – 970Hz @ 9Hz | |
30 | 800Hz – 970Hz @ 3Hz | |
31 | 800Hz, 0.25s ON/1s OFF | |
32 | 600Hz – 1100Hz, 2.6s/0.4s OFF |
1293
DoP No: 188
Tested by EVPU
Teletek Electronics JSC
Address: 2 Iliyansko shose Str,
1220 Sofia, Bulgaria
54-3:2001
54-3:2001/A1:2002
54-3:2001/A2:2006
Sounder Type: A