MEAN WELL EDR-120 DIN Rail Switching Power Supply Instruction Manual

June 9, 2024
MEAN WELL

EDR-120 DIN Rail Switching Power Supply
Instruction Manual

MEAN WELL EDR-120 DIN Rail Switching Power Supply 120W Single Output Industrial DIN RAIL

EDR-120 DIN Rail Switching Power Supply

https://www.meanwell.com/Upload/PDF/EDR%20DIN%20rail.pdf

Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508 (industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • 2 years warranty

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search hms “Ay, noanwoll tarn cooncaGTIN

Description

EDR-120 is one economical slim 120W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 40mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
EDR-120 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20t and 60t under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-120 a very competitive power supply solution for industrial applications.

Model Encoding

MEAN WELL EDR-120 DIN Rail Switching Power Supply - fig
1

SPECIFICATION

MODEL EDR-120-12 EDR-120.24 EDR-120.48
OUTPUT DC VOLTAGE 12V 24V
RATED CURRENT 10A 5A 2.5A
CURRENT RANGE 0 – 10A 0 – 5A 0 – 2.5A
RATED POWER 120W 120W 120W
RIPPLE & NOISE (max.) Note.2 100mVp-p 120mVp-p 150mVp-p
VOLTAGE ADJ. RANGE 12 – 14V 24 – 28V 48 – 55V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0%
LINE REGULATION ± 0.5% ± 0.5% ±0.5%
LOAD REGULATION ± 1.0% ± 1.0% ±1.0%
SETUP, RISE TIME 1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.) 16ms/230VAC 10ms/115VAC at full load
INPUT VOLTAGE RANGE Note.6 90 – 264VAC 127 – 370VDC [DC input operation

possible by connecting AC/L(+), AC1N(-)]
FREQUENCY RANGE| 47 – 63Hz
EFFICIENCY (Typ.)| 85%| 88.%| 8&5%
AC CURRENT (Typ.)| 2.25A/115VAC 1.3A/230VAC
INRUSH CURRENT (Typ.)| 20A/115VAC 35A/230VAC
LEAKAGE CURRENT| <1mA/ 240VAC
PROTECTION| OVERLOAD| 105 -130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE| 14 -17V| 29 – 33V| 56- 65V
Protection type: Shut down o/p voltage, re power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -20 – +60°C (Refer to ‘Derating Curve’
WORKING HUMIDITY| 20 – 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 – +85°C , 10 – 95% RH
TEMP. COEFFICIENT| ±0.03%/°C (0 – 50°C )
VIBRATION| Component:10 – 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY &
EMC (Note 4)| SAFETY STANDARDS| UL508,TUV BS EN/EN62368-1,EACTP TC004,BSMI CNS14336-1,IS13252(Part1)/IEC60950-1 approved; (meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-0/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-0/P, I/P-FG, 0/P-FG:>100M Ohms /500VDC / 25°C/70% RH
EMC EMISSION| Compliance to BS EN1EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN1EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, criteria A, EAC TP TC 020
OTHERS| MTBF| 2718.3K hrs min. Telcordia SR-332 (Bellcore) ; 474.7K hrs min. MI L-HD BK-217F (25°C)
DIMENSION| 40-125.2-113.5mm (WHD)
PACKING| 0.6Kg; 20pcs/13Kg/1.16CUFT
NOTE| 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3.Tolerance : includes set up tolerance, line regulation and bad regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5.Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
6.Derating may be needed under low input voltage. Please check the derating curve for more details.
7.The ambient temperature derating of 3.5t/1000m with fanless models and of 5°C/1000m with fan models for operating altitude higher than 2000m(6500ft). Product Liability Disdaimer : For detailed information, please refer to https://vwvw.meanwell.com/serviceDisdaimeraspx

Block Diagram

MEAN WELL EDR-120 DIN Rail Switching Power Supply - fig
5 Derating Curve
MEAN WELL EDR-120 DIN Rail Switching Power Supply - fig
2 Static Characteristics
MEAN WELL EDR-120 DIN Rail Switching Power Supply - fig
6

Mechanical Specification

MEAN WELL EDR-120 DIN Rail Switching Power Supply - fig
3

Installation Instruction

MEAN WELL EDR-120 DIN Rail Switching Power Supply - fig
4ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Downloaded from Arrow.com.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>