RAB RTLED1X4-19NW/HC/D10 RTLED Troffer Retrofit Luminaires Instructions
- June 9, 2024
- RAB
Table of Contents
INSTRUCTIONS
RTLED 1×4/2×2/2×4 TROFFER RETROFIT INSTALLATION
RTLED1X4-19NW/HC/D10 RTLED Troffer Retrofit Luminaires
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE
REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside.
WARNING: Risk of fire or electric shock. Luminaire wiring and electrical
parts may be damaged when drilling for installation of LED retrofit kit. Check
for enclosed wiring and components.
WARNING – Risk of fire or electric shock. Install this kit only in
luminaires that have the construction features and dimensions shown in the
photographs and/or drawings and where the input rating of the retrofit kit
does not exceed the input rating of the luminaire.
WARNING – To prevent wiring damage or abrasion, do not expose wiring to
edges of sheet metal or other sharp objects to lampholder lead wires by
employing applicable connectors.
WARNING – Risk of fire or electric shock. LED Retrofit Kit installation
requires knowledge of luminaires electrical systems. If not qualified, do not
attempt installation. Contact a qualified electrician.
RECESSED CEILING MOUNTING
The fixture is suitable only for INDOOR RECESSED CEILING application. To mount in an insulated or non-insulated ceiling exposed Flat Tee Grid Ceiling follow the steps below.
-
Remove existing lamps, door frame (if applicable), reflector and cover. Depending on clearance space, ballast may need to be removed.
-
Gently lift the original luminaire housing and slide in both side brackets between the housing and the T-grid. Lower the housing to rest on the brackets, securing them in place. (fig. 1 & 2)
-
Hang the retrofit kit body by hooking the T-hinges into the respective on one mounting brackets. (fig. 3)
-
Attach the safety cables to the original luminaire housing using the self-tapping hex screws provided.
-
Connect the retrofit kit power to the AC power. Insert the black wire (line) from the power into the provided LED quick connector marked with a black circle. Insert the white wire (neutral) into the unmarked port. Connect the power supply to the retrofit kit.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. 0-10V control wires must be rated for 300V minimum. For 0-10V Dimming, follow the wiring directions shown below (fig. 4).
-
Connect the black fixture lead to the LINE supply lead.
-
Connect the white fixture lead to the COMMON supply lead.
-
Connect the GROUND wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to the output. -
Connect the purple fixture lead to the (V+) DIM lead.
-
Connect the pink (or gray) fixture lead to the (V-) DIM lead.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.
- Clean polycarbonate lens & fixture with non-abrasive cleaning solution.
- Do not open fixture to clean the LEDs. Do not touch the LEDs.
TROUBLESHOOTING
- Check that the line voltage at fixture is correct. Refer to wiring directions.
- Be sure the fixture is grounded properly.
Note: These instructions do not cover all details or variations in
equipment nor do they provide for every possible situation during
installation, operation or maintenance.
BATTERY BACKUP MODELS
WIRING
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be presentin BATTERY. To
prevent high voltage from being present on output leads, Inverter connector
must be open. Do not join
BATTERY connector until installation is complete and AC power is supplied to
the emergency driver (fig. 5).
NOTE: Make sure that the necessary branch circuit wiring is available. An
UNSWITCHED AC source of power is required.
The emergency driver must be fed from the same branch circuit as the LED
driver.
CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
-
Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
-
If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
-
If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external SWITCHED.
-
Connect the NEUTRAL fixture lead to the NEUTRAL supply line.
-
For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply DIM(+) and DIM(-).
-
All unused leads must be capped and insulated.
-
Connect GROUND lead from the fixture to the supply GROUND.
Do not connect GROUND to the output leads. -
After installation is complete, supply AC power to the fixture and connect the BATTERY.
-
When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
-
Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the test button.
-
After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
OPERATION
- When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
- When power fails, the standby power automatically switches to emergency power (internal battery), operating at reduced illumination. The emergency driver will operate in stand by power for a minimum of 90 minutes.
- When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Is the fixture grounded properly?
- If the charging indicator light does not illuminate after pressing the test button, check if battery is connected properly.
© 2022 RAB LIGHTING Inc
RTLED-IN-0322
73520-RAB
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request
RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found
at rablighting.com/warranty
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>