RAB RTLED1X4-19NW/HC/D10 RTLED Troffer Retrofit Luminaires Instructions

June 9, 2024
RAB

INSTRUCTIONS
RTLED 1×4/2×2/2×4 TROFFER RETROFIT INSTALLATIONRAB RTLED1X4-19NW HC D10
RTLED Troffer Retrofit Luminaires

RTLED1X4-19NW/HC/D10 RTLED Troffer Retrofit Luminaires

RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: marketing@rablighting.com

IMPORTANT

READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining fixture. No user serviceable parts inside.
WARNING: Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of LED retrofit kit. Check for enclosed wiring and components.
WARNING – Risk of fire or electric shock. Install this kit only in luminaires that have the construction features and dimensions shown in the photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of the luminaire.
WARNING – To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects to lampholder lead wires by employing applicable connectors.
WARNING – Risk of fire or electric shock. LED Retrofit Kit installation requires knowledge of luminaires electrical systems. If not qualified, do not attempt installation. Contact a qualified electrician.

RECESSED CEILING MOUNTING

The fixture is suitable only for INDOOR RECESSED CEILING application. To mount in an insulated or non-insulated ceiling exposed Flat Tee Grid Ceiling follow the steps below.

  1. Remove existing lamps, door frame (if applicable), reflector and cover. Depending on clearance space, ballast may need to be removed.

  2. Gently lift the original luminaire housing and slide in both side brackets between the housing and the T-grid. Lower the housing to rest on the brackets, securing them in place. (fig. 1 & 2)

  3. Hang the retrofit kit body by hooking the T-hinges into the respective on one mounting brackets. (fig. 3)

  4. Attach the safety cables to the original luminaire housing using the self-tapping hex screws provided.

  5. Connect the retrofit kit power to the AC power. Insert the black wire (line) from the power into the provided LED quick connector marked with a black circle. Insert the white wire (neutral) into the unmarked port. Connect the power supply to the retrofit kit.

0-10V DIMMABLE WIRING

Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. 0-10V control wires must be rated for 300V minimum. For 0-10V Dimming, follow the wiring directions shown below (fig. 4).

  1. Connect the black fixture lead to the LINE supply lead.

  2. Connect the white fixture lead to the COMMON supply lead.

  3. Connect the GROUND wire from fixture to supply ground.
    Do NOT connect the GROUND of the dimming fixture to the output.

  4. Connect the purple fixture lead to the (V+) DIM lead.

  5. Connect the pink (or gray) fixture lead to the (V-) DIM lead.

CLEANING & MAINTENANCE

CAUTION: Be sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.

  1. Clean polycarbonate lens & fixture with non-abrasive cleaning solution.
  2. Do not open fixture to clean the LEDs. Do not touch the LEDs.

TROUBLESHOOTING

  1. Check that the line voltage at fixture is correct. Refer to wiring directions.
  2. Be sure the fixture is grounded properly.

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
BATTERY BACKUP MODELS

WIRING

CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be presentin BATTERY. To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join
BATTERY connector until installation is complete and AC power is supplied to the emergency driver (fig. 5).
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required.
The emergency driver must be fed from the same branch circuit as the LED driver.
CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.

  1. Connect UNSWITCHED HOT fixture lead to HOT AC supply line.

  2. If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.

  3. If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external SWITCHED.

  4. Connect the NEUTRAL fixture lead to the NEUTRAL supply line.

  5. For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply DIM(+) and DIM(-).

  6. All unused leads must be capped and insulated.

  7. Connect GROUND lead from the fixture to the supply GROUND.
    Do not connect GROUND to the output leads.

  8. After installation is complete, supply AC power to the fixture and connect the BATTERY.

  9. When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.

  10. Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the test button.

  11. After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.

Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.

OPERATION

  1. When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
  2. When power fails, the standby power automatically switches to emergency power (internal battery), operating at reduced illumination. The emergency driver will operate in stand by power for a minimum of 90 minutes.
  3. When AC power is restored, the emergency driver automatically returns to charging mode.

MAINTENANCE

Although no routine maintenance is required to keep the emergency driver functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:

  1. Visually inspect the charging indicator light monthly. It should be illuminated.
  2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
  3. Conduct a 90-minute discharge test once a year. Fixture would operate at reduced illumination for a minimum of 90 minutes.

TROUBLESHOOTING

  1. Is the fixture grounded properly?
  2. If the charging indicator light does not illuminate after pressing the test button, check if battery is connected properly.

RAB RTLED1X4-19NW HC D10 RTLED Troffer Retrofit Luminaires - FIG
6

© 2022 RAB LIGHTING Inc
RTLED-IN-0322
73520-RAB
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request
RAB WARRANTY: RAB’s warranty is subject to all terms and conditions found at rablighting.com/warranty

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals