MW HDR-30 series 30W Ultra Slim Step Shape DIN Rail User Guide

June 9, 2024
MW

HDR-30 series 30W Ultra Slim
Step Shape DIN Rail
User GuideMW HDR 30 series 30W Ultra Slim Step Shape DIN
Rail

HDR-30 series 30W Ultra Slim Step Shape DIN Rail

MW HDR 30 series 30W Ultra Slim Step Shape DIN Rail - qr
codehttps://www.meanwell.com/Upload/PDF/HDR%20DIN%20rail%20power%20supply.pdfMW
HDR 30 series 30W Ultra Slim Step Shape DIN Rail - icon
1

Features

  • Ultra slim design with 35mm(2SU) width
  • Universal input 85′-264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections : Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature:-30-4-70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • Over voltage category 111
  • LED indicator for power on
  • 3 years warranty

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

Description

HDR-30 is one economical ultra slim 30W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 35mm(2SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC(277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-30 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 90%, the entire series can operate at the ambient temperature between -30 ℃ and 70℃ under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1, UL508,UL62368-1, BS EN/EN61558-2-16) make HDR-30 a very competitive power supply solution for household and industrial applications.
Model EncodingMW HDR 30 series 30W Ultra Slim Step Shape - DIN
Rail

SPECIFICATION

MODEL| HDR-30-5| HDR-30-12| HDR-30-15| HDR-30-24| HDR-30-48
---|---|---|---|---|---
OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 3A| 2A| 2A| 1.5A| 0.75A
CURRENT RANGE| 0 ~ 3A| 0 ~ 2A| 0 ~ 2A| 0 ~ 1.5A| 0 ~ 0.75A
RATED POWER| 15W| 24W| 30W| 36W| 36W
RIPPLE & NOISE (max.) Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 4.5 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 50ms/230VAC  500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC  12ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )  120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 82%| 88%| 89%| 89%| 90%
AC CURRENT (Typ.)| 0.88A/115VAC         0.48A/230VAC
INRUSH CURRENT (Typ.)| COLD START 25A/115VAC          45A/230VAC
PROTECTION| OVERLOAD| 105 ~ 160% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed
Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed
OVER VOLTAGE| 5.75 ~ 7.5V| 15 ~ 18V| 18.8 ~ 22.5V| 30 ~ 36V| 57.6~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover





ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters










SAFETY & **EMC
(Note 4)**

| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1,IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved; Design refer to TUV BS EN/EN62368-1
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —-







EMC IMMUNITY

| BS EN/EN55024, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods


OTHERS

| MTBF| 968.1K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 359054.5mm (WHD)
PACKING| 0.12Kg;96pcs/12.5Kg/1.1CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMl testing of component power supplies.”
(as available on http://www.meanwell.com)
5.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MW HDR 30 series 30W Ultra Slim Step Shape DIN Rail - Block
Diagram Derating Curve

MW HDR 30 series 30W Ultra Slim Step Shape DIN Rail - Derating
Curve Output Derating VS Input VoltageMW HDR 30 series 30W Ultra Slim Step Shape DIN Rail - Input
Voltage

Mechanical Specification

(Unit: mm , tolerance ± 0.5mm)MW HDR 30 series 30W Ultra Slim Step Shape DIN
Rail - Figure 1MW HDR 30 series 30W
Ultra Slim Step Shape DIN Rail - Figure 2ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Terminal Pin No. Assignment

Pin No. Assignment Pin No. Assignment
1 +V 3 AC/L
2 -V 4 AC/N

Installation Manual

Please refer to: http://www.meanwell.com/manual.html

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MW User Manuals