STUDER xtender xth Inverter Charger Perma-Batteries User Guide
- June 9, 2024
- STUDER
Table of Contents
STUDER extender xth Inverter Charger Perma-Batteries
Introduction
Congratulations ! You are about to install and use high-end equipment that will play a central role in the energy management of your battery-based system. The tender is a smart battery inverter/charger with advanced functions. This extender has been designed, manufactured, assembled, and tested in our factory in Switzerland. It has a 5-year warranty and is eligible for an extension of 5+5.
General Information
Exclusion of liability
Studer disclaims all responsibility and liability for damage, costs, or losses
resulting from an installation that does not comply with the instructions, a
faulty operation, or inadequate maintenance. The use of studio equipment is in
any case under the responsibility of the customer.
Read carefully the safety and operation instructions / Installation must be
entrusted to qualified personnel / Check the user manual online / Need help
?
Compatible with
Mounting and installation
Storage and content
Mounting place
The batteries should only be installed by qualified personnel.
Fixing and dimensions
Wiring
AC out connection
- 3x10mm2 cable, 1.6Nm
- 3x25mm2 cable, 1.6Nm (xth 8000)
- Protection device to protect cables
- Up to 56Aac (80Aac xth 8000), circuit breaker type B Protection device to protect people
- Up to 56Aac (80Aac xth 8000),
- RCCB/RCD, check earth scheme
- Overvoltage protection, SPD
AC in connection
- 3x10mm2 cable, 1.6Nm
- 3x25mm2 cable, 1.6Nm (xth 8000)
- Protection device AC
- 50Aac, circuit breaker type B
- Overvoltage protection, SPD
- The device must be installed in accordance with local standards and regulations in force.
Multi-units and power up
Up to 9 Xtenders in the same communication bus
Display
Display system
Configuring the extender
Multi-units
A 3-phase and parallel combination
Technical data
xth xth xth xth 3000-12 5000-12 6000-24 8000-48|
|
---|---|---
Batt norminal voltage| 12Vdc 24Vdc 48Vdc 48Vdc|
Batt charge current| 160Adc 140Adc 100Adc
120Adc|
Batt min-max voltage| 9.5-17Vdc 19-34Vdc 38-68Vdc
38-68Vdc|
| AC input voltage| 230V (150-265V)
*120V (50-140V)
|
AC input max current| 50A|
Continuos Power| 2500VA 4500VA 5000VA 7000VA| |
Power 30min| 3000VA 5000VA 6000VA 8000VA| |
Power 5sec| 7.5kVA 12kVA 15kVA 21kVA| |
AC output voltage| 230V (150-245V) / *120V
(50-140V)| |
AC output frequency| 45-65Hz (configurable)| ****
- Version – 01
|
AC output max current| 56A 56A 56A
80A|
120Vac/60Hz version|
Maintenance and recycling
- Except for the periodic check of the connections (tightening, general condition), the xtender does not require any particular maintenance.
- To dispose of this product, please use the service for the collection of electrical waste and observe all obligations in force in the place of purchase.
- Serial Number:—————————-
- Installed by:———————————–
- Date:—————————–
- Signature:——————————-
- Call our specialists at +41 27 205 60 80
- or visitStuder-innotec.com/support
- Studer Innotec SA
- rue des Casernes 57
- 1950 Sion, Switzerland
- info@studer-innotec.com
- © All rights reserved Studer Innnotec SA – V1.0