STUDER bsp Battery Status Processor Instruction Manual

June 9, 2024
STUDER

quick guide bsp
Battery Status Processor
Instruction Manual

swiss made power

designed and assembled by studer in Switzerland

Introduction

Congratulations !
You are about to install and use a high-end equipment that will play a central role in the energy management of your battery-based system. The bsp is a battery status processor for advanced monitoring of lead-acid batteries within an xtender system. This device has been designed, manufactured, assembled and tested in our factory in Switzerland. It has a 5-year warranty.

General Information

Exclusion of liability
Studer disclaims all responsibility and liability for damage, costs or losses resulting from an installation that does not comply with the instructions, a faulty operation  or inadequate maintenance. The use of studer equipment is in any case under the responsibility of the customer.
Read carefully the safety and operation instructions
Installation must be entrusted to qualified personnel
Check the user manual online

Need help ?STUDER bsp Battery Status Processor - qr
codehttps://eqrcode.co/a/Ecznzt

Compatible with :

STUDER bsp Battery Status Processor - Compatible

Mounting and installation

Storage and content

STUDER bsp Battery Status Processor - Storage

Mounting place
The bsp should only be installed by qualified personnel.

STUDER bsp Battery Status Processor - icon5

Fixing and dimensions

STUDER bsp Battery Status Processor - dimensions

Wiring

STUDER bsp Battery Status Processor - Wiring

The device must be installed in accordance with local standards and regulations in force.

Measurement cables

Cables included :

  • black&yellow (b) to shunt, confirm orientation
  • blue (c) to shunt, confirm orientation
  • red (d) to bat +, fuse included (500mA)

Multi units and power up

  1. bsp per system

STUDER bsp Battery Status Processor - system

Display

Display system

Configuring the xtender

STUDER bsp Battery Status Processor - xtender

Technical data

IP 20

Supply voltage range 7 … 85Vdc
Supply current 9 mA @ 12V

5 mA @ 24V
3 mA @ 48V
Input voltage range| 7 … 85Vdc
Shunt measurement input range| ± 195 mV
RMS continuous current @ 25°C| ± 500 A (bsp 500)
± 1200 A (bsp 1200)
Maximum measurable peak current| ± 1950 A (bsp 500)
± 4680 A (bsp 1200)
Voltage measurement accuracy| 0.30%
Current measurement accuracy| 0.50%
Battery capacity| 20 … 20000 Ah
Operating temperature range| -20 … 55°C

Maintenance and recycling

Maintenance and recycling
Except for the periodic check of the connections (tightening, general condition), the bsp does not require any particular maintenance. To dispose of this product, please use the service for the collection of electrical waste and observe all obligations in force in the place of purchase.
Serial Number :…………………………..
Installed by :………………………………..
Date :………………………………………
Signature :…………………………………..

Call our specialists +41 27 205 60 80
or visit studer-innotec.com/support
Studer Innotec SA
rue des Casernes 57
1950 Sion, Switzerland
info@studer-innotec.com
© All rights reserved
Studer Innnotec SA – V1.0

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals