STUDER bsp Battery Status Processor Instruction Manual
- June 9, 2024
- STUDER
Table of Contents
quick guide bsp
Battery Status Processor
Instruction Manual
swiss made power
designed and assembled by studer in Switzerland
Introduction
Congratulations !
You are about to install and use a high-end equipment that will play a central
role in the energy management of your battery-based system. The bsp is a
battery status processor for advanced monitoring of lead-acid batteries within
an xtender system. This device has been designed, manufactured, assembled and
tested in our factory in Switzerland. It has a 5-year warranty.
General Information
Exclusion of liability
Studer disclaims all responsibility and liability for damage, costs or losses
resulting from an installation that does not comply with the instructions, a
faulty operation or inadequate maintenance. The use of studer equipment is in
any case under the responsibility of the customer.
Read carefully the safety and operation instructions
Installation must be entrusted to qualified personnel
Check the user manual online
Need help ?https://eqrcode.co/a/Ecznzt
Compatible with :
Mounting and installation
Storage and content
Mounting place
The bsp should only be installed by qualified personnel.
Fixing and dimensions
Wiring
The device must be installed in accordance with local standards and regulations in force.
Measurement cables
Cables included :
- black&yellow (b) to shunt, confirm orientation
- blue (c) to shunt, confirm orientation
- red (d) to bat +, fuse included (500mA)
Multi units and power up
- bsp per system
Display
Display system
Configuring the xtender
Technical data
IP 20
Supply voltage range | 7 … 85Vdc |
---|---|
Supply current | 9 mA @ 12V |
5 mA @ 24V
3 mA @ 48V
Input voltage range| 7 … 85Vdc
Shunt measurement input range| ± 195 mV
RMS continuous current @ 25°C| ± 500 A (bsp 500)
± 1200 A (bsp 1200)
Maximum measurable peak current| ± 1950 A (bsp 500)
± 4680 A (bsp 1200)
Voltage measurement accuracy| 0.30%
Current measurement accuracy| 0.50%
Battery capacity| 20 … 20000 Ah
Operating temperature range| -20 … 55°C
Maintenance and recycling
Maintenance and recycling
Except for the periodic check of the connections (tightening, general
condition), the bsp does not require any particular maintenance. To dispose of
this product, please use the service for the collection of electrical waste
and observe all obligations in force in the place of purchase.
Serial Number :…………………………..
Installed by :………………………………..
Date :………………………………………
Signature :…………………………………..
Call our specialists +41 27 205 60 80
or visit studer-innotec.com/support
Studer Innotec SA
rue des Casernes 57
1950 Sion, Switzerland
info@studer-innotec.com
© All rights reserved
Studer Innnotec SA – V1.0
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>