ELKO EKO01825 Smart Tag Instruction Manual

June 9, 2024
ELKO

ELKO EKO01825 Smart Tag

Model

  • Smart Tag Flex 1P+N 230V

  • Smart Tag 3P 230V

  • Smart Tag Flex 3P+N 400V

www.elko.no

Refer to the ELKO Smart user guide to configure your system.

Wireless-communication energy sensor for ELKO Energy modular devices for final distribution.

This instruction sheet must be kept for future use.
Visit our web site www.elko.no to download the technical documents for
ELKO Energy products.
PLEASE NOTE

  • Smart Tag devices must only be installed and maintained by qualified professionals.

  • Smart Tag devices should not be installed if, while unpacking, any damage is observed.

  • The Smart Tag devices must be installed inside electrical panels or switchboards,
    behind a door or plate, so that they are inaccessible for unauthorised persons.
    The electric panels must meet the requirements of the applicable standards
    (IEC/EN 60670-24) and installed in compliance with current installation and safety rules.

  • All relevant local, regional, and national regulations must be respected while installing and using Smart Tag devices.

  • Smart Tag shall be used by ELKO RCBO and circuit breaker or utility circuit breaker.

  • ELKO AS declines any responsibility in the event that Smart Tag equipment is associated with another equipment.

  • ELKO AS is not liable in case the instructions mentioned in this document and other referred documents are not respected.

DANGER / FARE

HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Turn off all power supply sources before installing and during maintenance of this equipment.
  • Do not use a Smart Tag product for voltage testing purposes. A Voltage Tester must be used instead.
    Failure to follow these instructions will result in death or serious injury.

Description

A Current measurement module.
B Product label.

The detachable adhesive part carries an unique product identifier RF-Id, useable during commissioning on certain concentrators.
C| Conductor feedthroughs for current measurement.
D| Comply with all safety instructions associated with this symbol to avoid any potential risk of injury or death.
E| Smart Tag communication status indicator light.
F| Power-supply and voltage measurement terminal.
Neutral = Blue wire
G| Connection cable between the power-supply terminal and the current- measurement module.

Before proceeding with pairing, ensure that the ELKO SmartHUB has the latest available software version. Refer to the user manual of the concerned ELKO SmartHUB .

Communication indicator light

Smart Tag status


| Smart Tag switched off.
| Smart Tag is searching a ELKO SmartHUB.
| Smart Tag in identification mode
| Smart Tag is in network. Normal communication with the ELKO SmartHUB.
| Occasional loss of communication
| Loss of communication with the ELKO SmartHUB.
| Internal error detected

Installation And Connection

FIRE HAZARD

  • For the reference EKO01825 use 18 mm cable end or strip over 18 mm to avoid tightening against the insulating material.
  • The Smart Tag must be associated with an easily accessible upstream protection and circuit-breaker system, marked with callout A in the schematic below. This upstream protection and disconnection device must be clearly identified and labeled. The electrical diagram is shown below. Failure to follow these instructions can result in death, serious injury, or equipment damage.

NOTICE

RISK OF DAMAGING THE SMART TAG

  • Disconnect the Smart Tag before performing the dielectric withstand test.
  • Limit the insulation measurements up to 500 V c.
    The input impedance of the Smart Tag between phases or between phases and the neutral is equal to 1.8 MΩ.
    Failure to follow these instructions can result in equipment damage.
Installation
  • EKO01951 – 1P+N (IT network) Unit ∼ 200-240 V

  • EKO01825 – 3P Unit ∼ 3 200-240 V

  • EKO01952 – 3P+N Un: 3N ∼ 220-240 / 380-415 V

Connection

Technical Data

  • Nominal voltage Un: ∿ 200-240 V, 3 ∿ 200-240 V, or 3N ∿ 220-240 / 380-415 V
  • Operating range (power supply and voltage measurement inputs): Un ± 20 %
  • Frequency: 50 Hz
  • Maximum power consumption: y 1 VA (1P+N) ; y 2 VA (3P/3P+N)
  • Maximum current: 63 A
  • Basic current (Ib): 10A
  • Operating temperature: -25°C to +60°C / -13°F to +140°F
  • Overvoltage and measurement category: III
  • Supports temporary surges relative to the ground
  • Pollution degree: 3
  • Altitude: y 2000 m / 6500 ft
  • Relative humidity: Maximum 93 % without condensation
  • Impact resistance index: IK05
  • For indoor use only
  • Radio communication:
    • 2.4 GHz ISM band (2400MHz to 2483.5MHz)
    • Channels 11 to 26 (IEEE 802.15.4)
    • Equivalent isotropics Radiated Power (EIRP): 0 dBm
    • Max. transmitted RF power: y 10 mW (EIRP)
  • Accuracy:
    • Voltage: Class 0.5
    • Current, Power and Active Energy: Class 1

Hereby, ELKO AS declares that the wireless-communication energy sensors Smart Tag are in compliance with the essential requirements and other relevant provisions of RED-DIRECTIVE 2014/53/EU n°FD19022803. Declaration of conformity can be download on: www.elko.no

Symbols Printed On The Product

| Comply with all safety instructions accompanying this symbol to avoid any potential risk of injury or death.
---|---

| Alternating current.
| Radio communication.
| CE marking on product(s) or its (their) packaging indicates that ELKO makes available to the EU authorities the reference technical file(s).
| This product is an electrical and electronic device. It falls within the scope of the WEEE 2012/19/EU directive. On the EU market, it must be disposed of using a specific waste collection system and never be disposed of in a household waste bin.

Customer Support