EPH CONTROLS UFH10 Wiring Centre Installation Guide
- June 9, 2024
 - EPH CONTROLS
 
Table of Contents
EPH CONTROLS UFH10 Wiring Centre

Specifications
- Power supply: 230Vac 50-60Hz
 - Number of Zones: 10
 - Power Supply Indication: Yes
 - Heat Enable Indication: Yes
 - UFH Valve Indication: Yes
 - Zone 1 to Zone 10 Indication: Yes
 - Ambient temperature: 0…45°C
 - Admissible ambient humidity: 5-95%RH
 - Dimensions: 380 x 140 x 50 mm
 - Heat Enable contact rating: 3A
 - UFH Pump contact rating: 3A
 - IP rating: IP20
 - Max. No. of actuators per zone 4
 - Max. Permissible Load 5A Resistive
 
Mounting and Installation
- Remove the UFH10 from its packaging.
 - The UFH10 can be directly mounted on a wall using the fixing holes on the base of the unit or it can be directly mounted on DIN rail.
 
DIMENSION

Wiring Centre Terminals
Power Supply
- L 230Vac Live
 - E Earth
 - N Neutral
 
Programmer
- L 230Vac to the programmer.
 - E Earth to the programmer.
 - N Neutral to the programmer.
 - 1 Zone 1 output from programmer to the wiring centre. 2 Zone 2 output from programmer to the wiring centre. 3 Zone 3 output from programmer to the wiring centre. 4
 - Zone 4 output from programmer to the wiring centre.
 
Thermostats (Zone 1 to Zone 8)
- L Live supply to the thermostat.
 - 1 Timed switch live to room stat from programmer zone 1. 2 Timed switch live to room stat from programmer zone 2. E Earth.
 - N Neutral supply to the thermostat.
 - S/L Switch live from the thermostat to the wiring centre.
 - Note: With thermostats 1 to 8, you have an option of; one of two time inputs.
 
Thermostats (Zone 9 and Zone 10)
- L Live supply to the thermostat.
 - 1 Timed switch live to room stat from programmer zone 1 2 Timed switch live to room stat from programmer zone 2 3 Timed switch live to room stat from programmer
 - zone 3 4 Timed switch live to room stat from programmer zone 4 E Earth.
 - N Neutral supply to the thermostat.
 - S/L Switch live from the thermostat to the wiring centre.
 
Note: With thermostats 9 & 10, you have an option of; one of four time inputs.
Heat Enable (Boiler / Heat Pump On)
- LS Live supply
 - E Earth
 - LR Live return
 
This is a volt free relay which is switched on when there is a call for heat If 230V is applied to terminal LS and there is a call for heat, 230V will come back on terminal LR.
UFH Pump (Underfloor Heating Pump)
- L 230Vac Live
 - E Earth
 - N Neutral
 
When an underfloor heating zone calls for heat, 230V is sent to the underfloor heating manifold pump. Best practice is to wire the underfloor heating manifold pump through a high limit thermostat which is mounted on the manifold.
UFH Valve (Underfloor Heating Valve)
- GR Grey Switch Live
 - OR Orange Permanent Live
 - L Live
 - E Earth
 - N Neutral
 
When an underfloor heating zone calls for heat, 230V is sent to the Underfloor
heating valve. The valves auxiliary contacts are wired to the GR and OR
terminals.
Note: Please refer to factory default settings on page 1.
Actuators (Zone 1 to Zone 8)
- L 230V Live supply to the actuator.
 - N Neutral supply to the actuator.
 
There are two terminals marked L & N for each zone.
Actuators (Zone 9 and Zone 10)
- L Live supply to the actuator.
 - N Neutral supply to the actuator.
 
There are two terminals marked L and two terminals marked N for each zone. Both zones 9 and 10 have a switch associated with each zone. This allows the installer to use these zones as underfloor heating zones or radiator / hot water zones.
Operation of Zone 9 & 10 UFH – RAD / HW switches
If set to UFH – When the thermostat calls for heat, the actuator, boiler and pump / valve outputs are enabled. If set to RAD / HW – When the thermostat calls for heat, the actuator is enabled. To enable the boiler output, the actuator auxiliary contacts (Grey and Orange wires) must be connected to the LS & LR terminals of the Heat Enable.
| UFH | On | On | On | On | 
|---|---|---|---|---|
| RAD | Off | Off | Off | On | 
UFH10 – 10 x Underfloor Heating Zones
c/w Mains Operated Programmable Thermostats. Options:
Note: Please refer to individual thermostat wiring diagrams.
| UFH Pump | Yes | 
|---|---|
| UFH Valve | Yes | 
| UFH Actuators | Yes | 
| Programmer | – | 
| RAD Valve | – | 
| HW Valve | – | 

c/w Mains Operated Non- Programmable Thermostats.

Note: Please refer to individual thermostat wiring diagrams.
| UFH Pump | Yes | 
|---|---|
| UFH Valve | Yes | 
| UFH Actuators | Yes | 
| Programmer | R47 | 
| RAD Valve | – | 
| HW Valve | – | 
Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
Zone 3 on the programmer is controlling thermostat 9
Zone 4 on the programmer is controlling thermostat 10  

c/w Mains Operated Non- Programmable Setback Thermostats.
Options:

Note: Please refer to individual thermostat wiring diagrams.
| UFH Pump | Yes | 
|---|---|
| UFH Valve | Yes | 
| UFH Actuators | Yes | 
| Programmer | R47 | 
| RAD Valve | – | 
| HW Valve | – | 
Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
Zone 3 on the programmer is controlling thermostat 9
Zone 4 on the programmer is controlling thermostat 10  

c/w Mains Operated Non- Programmable Thermostats. Options:

Note: Please refer to individual thermostat wiring diagrams.
| UFH Pump | Yes | 
|---|---|
| UFH Valve | Yes | 
| UFH Actuators | Yes | 
| Programmer | R47 | 
| RAD Valve | V22_P | 
| HW Valve | V22_P | 
Zone 1 on the programmer is controlling thermostats 1, 2, 3 & 4
Zone 2 on the programmer is controlling thermostats 5, 6, 7 & 8
Zone 3 on the programmer is controlling thermostat 9
Zone 4 on the programmer is controlling thermostat 10  

UFH10 is compatible with the following EPH thermostats
Electro – Mechanical Thermostats