WATTS LFM116 Pressure Relief, Sustaining, or Backpressure Control Valve User Manual

June 8, 2024
WATTS

WATTS logo LFM116 Pressure Relief, Sustaining, or Backpressure Control Valve
User ManualWATTS LFM116 Pressure Relief Sustaining or Backpressure
Control Valve

LFM116
Series LFM116 / LFM6116
Sizes: 11/4″ to 24″

WARNING
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in death, serious personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.

WARNING
Local building or plumbing codes may require modifications to the information provided. You are required to consult the local building and plumbing codes prior to installation. If the information provided here is not consistent with local building or plumbing codes, the local codes should be followed. This product must be installed by a licensed contractor in accordance with local codes and ordinances.

WARNING
Need for Periodic Inspection/Maintenance: This product must be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. All products must be retested once maintenance has been performed. Corrosive water conditions and/or unauthorized adjustments or repair could render the product ineffective for the service intended. Regular checking and cleaning of the product’s internal and external components helps assure maximum life and proper product function. !

NOTICE
For Australia and New Zealand: Pipeline strainers should be installed between the upstream shutoff valve and the inlet of the backflow preventer.
It’s important that this device be tested periodically in compliance with local codes, but at least once per year or more as service conditions warrant. If installed on a fire  sprinkler system, all mechanical checks, such as alarm checks and backflow preventers, should be flow tested and inspected internally in accordance with NFPA 13 and NFPA 25.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts  Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any  obligation to make such changes and modifications on Watts products previously or subsequently sold.

Engineering Specification

**LEAD FREE*
Series LFM116**
Pressure Relief, Sustaining or Backpressure Control Valve
Full Port Ductile Iron Single Chamber Valve

Features

  • Opens when upstream pressure is above setpoint
  • Closes when upstream pressure is below setpoint
  • Adjustable Closing Speed
  • When installed on branch of tee, acts as Pressure Relief Valve
  • When installed between two pressure zones, acts as Pressure Sustaining Valve
  • When installed on discharge of a pump, acts as Backpressure Control Valve
  • Setpoint is adjustable

Standard Components
1 – Main Valve (M100 – Single Chamber)
2 – Relief / Sustaining Control
3 – Adjustable Closing Speed
X – Isolation Cocks

Options and Accessories

  • FC – Flo-Clean Strainer (Standard 1¼” – 4″)
  • Y – Y-Strainer (Replaces Flo-Clean)
  • AOS – Adjustable Opening Speed (Standard 1¼” – 4″)
  • P – Position Indicator
  • L – Limit Switch

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve -
fig

Operation

The Pressure Relief, Sustaining or Backpressure Automatic Control Valve (ACV) is designed to permit flow when upstream pressure is above the adjustable setpoint of the control pilot, and throttle toward closed when upstream pressure falls below the adjustable setpoint. It is controlled by a normally closed control pilot designed to: 1) Open (allowing fluid out of the main valve cover chamber) when upstream pressure is above the adjustable setpoint, and, 2) Close (allowing fluid to fill the main valve cover chamber) when upstream pressure is below the adjustable setpoint. An increase in upstream pressure causes the valve to modulate toward an open position. A decrease in upstream pressure causes the valve to modulate toward a closed position.
When the valve is installed “off the main line” on the branch of a tee, it serves as a Pressure Relief Control Valve. The valve is normally closed, and quickly opens when upstream pressure exceeds the pilot setting, relieving pressure, commonly discharging to a storage reservoir, pump suction, or atmosphere. When upstream pressure is lowered below the pilot setting, the valve closes at a controlled, adjustable rate.
When the valve is located “in line” connecting two distribution zones, the valve acts as a Pressure Sustaining Control Valve. When pressure in the upstream zone falls below the pilot setting, the valve modulates toward a closed position, sustaining pressure in the upstream zone. The valve will close, if necessary, until upstream pressure is above the pilot setting. The valve should be specified to include the optional opening speed control and position indicator when used for Pressure Sustaining applications.
When the valve is installed “in line” on the discharge of a pump, it acts as Backpressure Control Valve. When pump discharge pressure falls below the pilot setting, the valve modulates toward a closed position, increasing backpressure against the pump. The valve should be specified to include the optional opening speed control when used for Backpressure applications.

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.
    NOTICE
    The information contained herein is not intended to replace the full product installation and safety information available or the experience of a trained product installer.
    You are required to thoroughly read all installation instructions and product safety information before beginning the installation of this product.

M Series Basic Valves
Pressure Relief, Sustaining or Backpressure Control Valve
Full Port Ductile Iron Single Chamber Basic Valve

This Watts Automatic Control Valve (ACV) is a full port, single chamber basic valve that incorporates a one-piece disc and diaphragm assembly. This assembly is the only moving part within the valve allowing it to open, close, or modulate as commanded by the pilot control system. Watts ACV Main Valves are Lead Free. The Watts ACV piloting system contains Lead Free* components, ensuring all of our configurations are Lead Free compliant. Globe Pattern Single Chamber Basic Valve (M100) Angle Pattern Single Chamber Basic Valve (M1100)

Basic Valve Body Options

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
1

Standard Materials

Body and Cover: – Ductile Iron ASTM A536
Coating: NSF Listed Fusion Bonded Epoxy Lined and Coated
Trim: 316 Stainless Steel
Elastomers: Buna-N (standard) EPDM (optional) VitonTM (optional)
Nut, Spring and Stem: Stainless Steel.
Anti-Scale (Optional): Xylan Coated Stem and Seat

VitonTM is a trademark of The Chemours Company FC, LLC

Operating Pressure
Threaded = 400psi (27.6 bar)
150# Flanged = 250psi (17.2 bar)
300# Flanged = 400psi (27.6 bar)
Grooved End = 400psi (27.6 bar)
Operating Temperature
Buna-N: 160°F (71°C) Maximum
EPDM: 300°F (140°C) Maximum
Viton™: 250°F (121°C) Maximum
Epoxy Coating: 225°F (107°C) Maximum
Valves can be provided without internal epoxy coating consult factory

Flow Data

  • Maximum continuous flow based on velocity of 20 ft. per second.

  • Maximum intermittent flow based on velocity of 25 ft. per second.

  • Minimum flow rates based on a 20-40 psi pressure drop.

  • The Cv Factor of a value is the flow rate in US GPM at 60°F that will cause a 1psi drop in pressure.

  • Cv factor can be used in the following equations to determine Flow
    (Q) and Pressure Drop (∆P):
    Q (Flow) = Cv²√∆P ∆P (Pressure Drop) = (Q/Cv)

  • The Cv factors stated are based upon a fully open valve.

  • Many factors should be considered in sizing control valves including inlet pressure, outlet pressure and flow rates.

  • For sizing questions including cavitation analysis consult Watts with system details.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
3

Basic Valve

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
4

Item Description Material
1 Pipe Plug Lead Free Brass
2 Cover ASTM A536 65-45-12 Epoxy Coated Ductile Iron
3 Cover Bearing ASTM A276 304 Stainless Steel
4 Stud with Cover Nut and Washer ASTM A570 Gr.33 Zinc Plated Steel
5 Body ASTM A536 65-45-12 Epoxy Coated Ductile Iron
6 Spring ASTM A276 302 Stainless Steel
7 Stem Nut ASTM A276 304 Stainless Steel
8 Lock Washer ASTM A276 304 Stainless Steel
9 Stem Washer ASTM A276 304 Stainless Steel
10 Diaphragm Washer ASTM A536 65-45-12 Epoxy Coated Ductile Iron
11 Diaphragm’ Buna-N (Nitrile)
12 Disc Retainer ASTM A536 65-45-12 Epoxy Coated Ductile Iron
13 Seat Disc’ Buna-N (Nitrile)
14 Spacer Washer x5 NY300 Fiber
15 Disc Guide ASTM A743 CF8M (316) Stainless Steel
16 Shaft ASTM A276 304 Stainless Steel
17 Seat Ring” ASTM A743 CF8M (316) Stainless Steel
17A Seat Screw” (8″ and Larger) ASTM A276 304 Stainless Steel
18 Seat Gasket’ Buna-N (Nitrile)
  • Contained in Main Valve Repair Kit
    **Note: 6 inch and Smaller Valves, Seat Ring is threaded
    NOTICE
    Installation: If unit is installed in any orientation other than horizontal (cover up) OR extreme space constraints exist, consult customer service prior to or at the time of order.

Dimensions

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
5

Flanged and Threaded Dimensions

*LEAD FREE
Model LFPV20C
Pressure Relief, Sustaining or Backpressure Pilot**

Size: 1/2″ NPT

The Model LFPV20C is a remote sensed direct acting, diaphragm actuated Pilot that is used on various configurations of Automatic Control Valves. It is normally held closed by the force of the adjustable spring setting above the diaphragm. It modulates toward an open position when control pressure, exerting force below the diaphragm, exceeds the spring setpoint, and modulates toward a closed position when the control pressure falls below the spring setpoint.
The LFPV20C senses control pressure through a tapped port below the diaphragm. The large diaphragm-to-seat ratio allows it to open and close within tight pressure tolerances, accurately positioning the Main Valve.
Turning the adjustment screw clockwise raises the control setpoint.
Turning the adjustment screw counterclockwise lowers the control setpoint.
The LFPV20C is equipped with one 1/2″ NPT inlet and outlet port and a 1/4″ NPT side sensing port located on the power chamber. The 1/4″ side sensing port is used to monitor upstream or downstream pressure as required by specific valve function.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
6

Specifications

Body Material: Lead Free Copper Silicon Alloy
*Seat: 316 Stainless Steel
Elastomers: Buna-N (standard) Viton TM (optional)

EPDM (optional)
| 400psi (27.6 bar) maximum
Inlet Pressure Rating:
.
Adjustment Rating:| 20-200psi (1.4 – 13.8 bar) (standard) 0-30psi (0 – 2.1 bar) (optional)
100-300psi (6.9 – 20.7 bar) (optional) 200-450psi (13.8 – 31.0 bar) (optional)

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
7

Item Description
1 Adjusting Screw
2 Jam Nut
3 Spring Housing
4 Spring Guide
5 Spring
6 Cap Screw
7 Power Chamber
8 0-Ring’
9 Body
10 Seat
11 0-Ring`
Item Description
--- ---
12 Nut
13 Lockwasher
14 Diaphragm Washer
15 Diaphragm*
16 Diaphragm Washer
17 0-RIng’
18 Stem
19 Retainer
20 Rubber Disc’
21 Screw

**LEAD FREE *
Model LFFC
Flow Control
Size: ½” NPT**
A Flow Control is an adjustable device used for tuning valve performance. It can be installed to either control the opening or closing the speed of the automatic control main valve. When the flow is in the direction of the needle the flow control is an adjustable restriction. In the free flow direction the seat moves out of the flow path to all unrestricted flow.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
8

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
9

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

*LEAD FREE
Model BV
Ball Valve
Size: ¼” – 1″ NPT **

Model BV Ball Valves are used in pilot lines to provide a positive shutoff in any override or maintenance situation for simple trouble shooting. This 2-piece, full port valve features: bottom loaded stems, PTFE seats and packing.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
11

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

**LEAD FREE *
Model LF60
Flo-Clean Strainer
Size: 1/4″ – 3/4″ NPT**

Model LF60 Flo-Clean Strainers are used to filter the fluid passing through the pilot circuit, and provide protection to pilot circuit speed controls and pilots. It is installed in the inlet body port of the Main Valve, exposing the strainer element to main line flow. The currents and flow across the screen create a self-scouring effect, cleaning the filter element.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
12

Valve inlet with Filter installed

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
13

Body Material: Lead Free Brass (standard) Stainless Steel (optional)
Pressure Rating: 400psi (27.6 bar)
Filter Element: Monel
Screen Mesh: 40 Mesh (standard)

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

**LEAD FREE*
Model LF60-1
Y-Pattern Strainer
Size: 1/4″ – 3/4″ NPT**

Model LF60-1 Y-Pattern Strainers are used to filter the fluid passing through the pilot circuit, and provide protection to pilot circuit speed controls and pilots. The filter element can be accessed for cleaning by removing the clean- out cap, or may be cleaned by installing an optional “blow-down” ball valve.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
15

Dimensions

Body Material: Lead Free Copper Silicon Alloy CF8M (316) Stainless Steel (optional)
Retainer Cap: Lead Free Copper Silicon Alloy
Cap Gasket: EPDM
Pressure Rating: 400psi (27.6 bar)
Filter Element: 304 Stainless Steel
Mesh Options: 60 Mesh (standard) 100 Mesh (optional,

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

LEAD FREE
Model 50
Position Indicator 

When specified as an option on a Control Valve, the Model 50 Position Indicator is installed in the topmost cover port of the Main Valve and allows for visual indication of valve position. The Model 50 is also very useful during valve start-up and troubleshooting procedures.
A stainless steel indicating rod threads into the tapped portion of the Main Valve stem and moves inside of a cylindrical Pyrex sight tube. The indicating rod travels up and down, following Main Valve stem movement. The housing protects the sight tube and indicating rod, and allows visibility on two sides. The screw driver operated test cock installed on the top of the Model 50 housing provides a controlled method of removal of air from the cover chamber during start-up or troubleshooting of the Main Valve.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
17

Item Description
1 Test Cock
2 Housing
3 Gasket
4 Pyrex Sight Tube
5 Body
6 Indicating Rod
7 Stem Adaptor (8″ or Larger)

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
16

Standard Material: Stainless Steel Housing and Body Stainless Steel Indicating Rod
Lead Free Test Cock
Pyrex Sight Tube
Optional Material: Stainless Steel Test Cock
Pressure Rating: 400psi (27.6 bar)

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

Dimensions

Valve Size
(in)| Dimension
(in)
---|---
11/4 – 11/2| 7 ⅜
2| 4 ⅞
2
1/2| 4⅞
3| 4 ⅞
4| 5
6| 5
8| 5 ⅞
10| 5 ⅞
12| 7¼
14| 7¼
16| 7¼
18| 7¼
20
| 7¼
24*| 7¼

**LEAD FREE *
Model 51
Single Limit Switch**
The Model 51 Single Limit Switch provides visual indication of valve position, as well as remote electrical indication of “valve open” or “valve closed”. The single pole double throw MicroSwitch can be connected to open or close an electrical circuit when the valve opens or closes. The adjustable collar is normally set to contact the trip arm when
the main valve is closed. The collar can be positioned on the stem by loosening the set-screw to actuate the switch at the desired point of valve travel.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
19

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
18

Body Material: Stainless Steel
Elastomers: Buna-N (standard)
EPDM (optional) Viton™ (optional)
Enclosure: NEMA 1, 3, 4 and 13 General Purpose (standard)
NEMA 1,7 and 9 Explosion Proof (optional)
Electrical: Form C SPDT Switch
15 amp. 125, 250 or 480 VAC
½ amp. 125 VDC
¼ amp. 250 VDC
½” Conduit Connection

Viton™ is a trademark of The Chemours Company FC, LLC

  • The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

Parts List

Item Description
1 Limit Switch
2 Bracket
3 Stem
4 Trip collar
5 Set Screw
6 Cap
7 Wiper Ring*
8 O-Ring*
9 Guide
10 O-Ring*
11 Polypak*
12 Locknut
13 Body
14 Pin
15 Coupling

*Included in Repair Kit

Installation

Start-up of an automatic control valve requires that proper procedures be followed. Time must be allowed for the valve to react to adjustments and the system to stabilize. The objective is to bring the valve into service in a controlled manner to protect the system from damaging over-pressure.

  1. Clear the line free of slag and other debris.
  2. Install the valve so that the FLOW ARROW marked on the valve body/tag corresponds to flow through the line.
  3. Close upstream and downstream isolation valves.
  4. Open the isolation ball valves in the control tubing if so equipped. Failure to open these will prevent the valve from functioning properly.
  5. Install pressure gauges at locations upstream and downstream of the valve.

Valve Servicing Dimensions

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
20

The following tables detail the recommended minimum valve servicing dimensions.

Setting the Pressure Controls

STEP 1
Pre-set pilots as noted:
Pressure Sustaining –Turn Sustaining Control adjustment screw OUT, counterclockwise, backing pressure off the spring, to allow it to stay open while adjusting the other controls.
Pressure Reducing – Adjust OUT, counterclockwise, backing pressure off the spring, preventing possible over-pressuring of the system.
Opening and Closing Speed – Turn the adjustment screws on the Closing Speed and Opening Speed Controls, if the main valve is so equipped, OUT, counterclockwise, 11/2 to 21/2 turns from full closed position.
STEP 2
To ensure proper operation, any trapped air will need to be bled off the valve cover during startup. If your ACV includes a bleed valve, as shown to the right, use a flat head screwdriver to slowly open the valve (See Figure 1).
If your valve does not include a bleed valve, bleed air by loosening a fitting on the valve or a plug, at the highest point of the valve assembly.
STEP 3
Pressure the line, by opening the upstream isolation valve slowly Air is vented through the air bleed valve or loosened fitting. Tighten the fitting when liquid begins to vent (See Figure 1).
Repeat the process until no air is trapped in the system.

STEP 4
Slowly open downstream isolation valve to establish flow through the system.
STEP 5
Setting the Sustaining Control requires lowering the upstream pressure to the desired minimum sustained pressure.
STEP 6
Leave the downstream isolation valve fully open and close the upstream isolation valve until the inlet pressure drops to the desired setting.
STEP 7
Adjust the Sustaining Control screw IN, clockwise, until the inlet pressure begins to increase, or OUT, counterclockwise to decrease, stopping at the desired pressure (See Figure 2).

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
22

STEP 8
Allow pressure to stabilize.
STEP 9
Fine-tune the sustaining setting as required as detailed in STEP 7.
STEP 10
Open the upstream isolation valve to return to normal operation.
STEP 11
Closing Speed Needle Valve Adjustment: The closing speed needle valve regulates fluid pressure into the main valve cover chamber, controlling the valve closing speed. If the downstream pressure fluctuates slightly above the desired set point, turn the adjustment screw OUT, counterclockwise, increasing the rate of closing.
(IF INSTALLED) Opening Speed Flow Control Adjustment: The Opening speed flow control allows free flow into the cover and restricted flow out of the cover of the main valve. If recovery of pressure is slow upon increased downstream demand, turn the adjustment screw OUT, counterclockwise, increasing the rate of opening. IF recovery of downstream pressure is too quick, as indicated in a rapid increase in pressure, possibly higher than the desired set-point, turn the adjustment screw IN, clockwise,
decreasing the rate of opening (See Figure 3).

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
23

Automatic Control Valve Maintenance Schedule

To ensure peak performance and longevity of your automatic control valve, Watts/Ames recommends following the below standard maintenance schedule.

  •  Monthly Maintenance
    – Visual inspection of valve(s) for leaks
    – Inspect for proper operation(s); exercise valve.

  • Quarterly Maintenance
    – Conduct monthly inspection.
    – Validate/Re-establish necessary setpoints of controls/pilots.

  • Annual Maintenance
    – Conduct monthly & quarterly inspections.
    – Inspect & clean all strainers.
    – Inspect valve coating, touch up as required.

  • 3-5 Year Maintenance
    – Conduct monthly, quarterly, & annual maintenance.
    – Inspect & replace valve elastomers (diaphragm, O-rings,
    valve/pilot seats)
    – Re-establish necessary set points of controls/pilots.

Troubleshooting Guide

WARNING
Warning: The valve cannot be serviced under pressure.
Upstream and downstream Isolation Valves must be installed to protect system piping. Accurate diagnosis and troubleshooting requires the valve to open fully, and may subject downstream piping and equipment to high pressure and/or flow rates. The downstream Isolation Valve should be kept closed while diagnosing the valve.
Extreme caution should be used while performing the troubleshooting techniques listed below.
Recommended tools for diagnosis: (3) PRESSURE GAUGES, installed to monitor the inlet pressure, outlet pressure, and coverchamber pressure. If included, a POSITION INDICATOR shouldbe installed to visually assess the position of the disc & diaphragm assembly.

Test 1: Diaphragm Seal Test

  1. Close upstream & downstream isolation valves. Close pilot isolation valves or remove pilot control tubing to isolate valve cover from incoming fluid & pressure. Remove uppermost cover plug, test cock, or limit switch.
  2. With the valve cover chamber vented to atmosphere, partially open the upstream isolation valve, allowing incoming pressure to lift the disc & diaphragm assembly. A volume of water will be displaced from the cover chamber as the valve opens; consult valve specification sheets for approximate cover capacity. A continuous flow of water from the open port indicates a damaged diaphragm or loose disc & diaphragm assembly. Disassemble valve and replace diaphragm or tightendisc & diaphragm assembly.

Test 2: Seat Seal Test

  1. Close downstream isolation valve and install pressure gauges on an open inlet and outlet port of main valve.
  2. Open upstream isolation valve to allow pressure on to the valve cover. Allow valve to fully close.
  3. Monitor downstream pressure gauge; reading should hold steady below incoming pressure. If pressure on downstream side rises to match upstream pressure, leakage is occurring through the seat of the main valve. Disassemble valve, inspect and repair/replace any required parts. a. If gauge pressure rises to match outlet pressure (downstream of closed isolation valve) yet remains below inlet pressure, the isolation valve may be leaking as opposed to main valve seat.

Test 3: Freedom of Movement/Valve Travel Test

  1. Close upstream and downstream isolation valves. Install valve position indicator.

  2. Partially open upstream isolation valve and allow cover to fill with fluid & pressure, closing the valve fully. Mark the position indicator’s full closed position.

  3. Isolate cover chamber from receiving fluid and pressure by closing isolation valves or removing control tubing.

  4. Carefully vent cover chamber to atmosphere by opening test cock or removing a cover plug. Observe the valve position indicator as the valve travels to the full-open position. The disc & diaphragm assembly should move freely from fully closed to fully open position without binding or “grabbing” at any point during its movement.
    a. The disc & diaphragm assembly may momentarily “hesitate” while travelling from fully closed to fully open position – this is a normal characteristic of diaphragm operated control valves, and does not indicate mechanical binding or improper valve operation.
    b. A continuous discharge of water from the cover chamber after venting to atmosphere indicates leakage past the diaphragm.

  5. If necessary, disassemble valve and inspect/repair disc & diaphragm assembly.

Issue Possible Cause Corrective Action Notes
Main Valve will not open Closed isolation valves in pilot system. Check
isolation valves, ensure open.
Insufficient supply pressure. Check upstream pressure. Depending on water

source, supply pressure may not be controlled by valve operator.
Main valve stem assembly corroded/ damaged.| Inspect stem assembly, clean/ replace if necessary.|
Blockage in pilot system.| Inspect & clean any installed pilot system strainers, check orifice/speed controls for blockages.|
Missing fixed orifice assembly.| Verify installation of orifice; replace if required/missing.| Pilot valve inlet isolation valve can be used as a makeshift orifice assembly by partially opening from full closed position.
Improperly configured opening speed control (if equipped).| Adjust opening speed control to verify functionality, adjust as required.| Standard setting for opening speed control is 11/2 – 21/2 turns open from full closed position. Can be adjusted in field.
Main Valve will not close| Closed isolation valves in pilot system| Check isolation valves, ensure open.|
Diaphragm is damaged| Conduct diaphragm seal test repair and replace if necessary.|
Main valve stem assembly corroded/ damaged.| Inspect stem assembly, clean/ replace if necessary.|
Blockage in main valve.| Perform freedom of movement test; if valve does not close, disassemble and remove blockage.|
Worn/damaged valve seat.| Perform seat sealing check; disassemble and inspect/repair seat if required.|

Valve Disassembly Instructions

Before undertaking valve disassembly, it is recommended to gather the following tools to aid you during the process:

  • Small & large adjustable wrenches
  • Screwdriver set
  • Machinist fine metal file
  • Fine wire brush
  • Bench vise
  • Basic valve IO&M manual
  • Hammer & dull cold chisel
  • Heavy-duty ratchet & socket set
  • Hexagonal wrench set
  • 320 grit/fine Emery cloth
  • Appropriate technical bulletins for valve start-up procedures.

WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
24

  1. Isolate the valve from line pressure and depressurize it to ensure safe working conditions. Disconnect any electrical connections if so equipped.

  2. Carefully remove Position Indicator or Limit Switches if equipped. Remove all tubing, fittings, and Control Pilots necessary to easily access and remove the cover. Remove cover nuts and washers.

  3. Remove the cover. If cover is not free to be removed, loosen it by tapping upward along its outside edge with a dull cold chisel, pictured above.
    a. Large valves may require the installation of lifting “eye” bolts in order to facilitate cover removal; installation ports are provided on the cover for this purpose.

  4. Remove the Disc and Diaphragm Assembly from the valve body by lifting straight up.
    a. Large diameter valves may require a lifting “eye” bolt to be installed in the valve stem accessory threads located on the very top of the valve stem.

  5. Before removing Stem Nut, examine stem threads for mineral build-up. Remove deposits with a fine wire brush. Extreme care should be taken not to damage the finish on stem guiding surfaces when disassembling. Avoid applying pipe wrenches to top or bottom stem guide surfaces.

  6. After removing the Stem Nut, the remainder of the Disc & Diaphragm Assembly should disassemble easily. Polish stem guide surfaces with fine emery cloth to remove any mineral deposits and inspect for excessive wear. Remove any mineral build-up from other components with wire brush or by using a Mineral Dissolving Solution. Inspect parts for wear and replace if necessary.

  7. Inspect valve seat. If seat is not damaged, removal is not necessary. Valve seats 6″ and smaller are threaded into the body of the valve and require a seat removal tool (Figure 4) (Table 1 details the tool dimensions for seat removal). Valve seats 8″ and larger are held in the valve body with stainless steel cap screws. Remove seat retaining screws and lift seat straight up (Figure 5).
    WATTS LFM116 Pressure Relief Sustaining or Backpressure Control Valve - fig
25
    Table 1: Seat Removal Tool Dimension
    **** Size| A| B| C| D| E (Dia.)|
    ---|---|---|---|---|---|---
    in| Pipe Size (in)| Min. Length (in)| in| in| in| in
    11/4| 1| 3.| 0.38| 0.25| 0.44| 0.55
    11/2| 1| 3.| 0.38| 0.25| 0.44| 0.50
    2| 11/4| 3.| 0.38| 0.25| 0.44| 0.50
    21/2| 2| 4.0| 0.38| 0.38| 0.56| 0.62
    3| 21/2| 5.| 0.50| 0.38| 0.56| 0.62
    4| 3| 5.0| 0.50| 0.44| 0.56| 0.62
    6| 5| 6.50| 0.62| 0.44| 0.56| 0.62

*Schedule 40 steel pipe

  1. Replace Seat Disc, Diaphragm and Spacer Washers provided in Main Valve repair kit (refer to Table 2 or 3 for correct repair kit part number). Re-assemble in the reverse order of disassembly.
    Table 2: Full Port Valve (M100/M1100) Repair Kits
    **** Size (in)| 1 1/4| 1 1/2| 2| 21/2| 3| 4| 6| 8| 10| 12| 14| 16
    ---|---|---|---|---|---|---|---|---|---|---|---|---
    P/N| 0677-01| 0677-01| 0677-02| 0677-03| 0677-04| 0677-05| 0677-06| 0677-07| 0677-08| 0677-09| 0677-10| 0677-11

Table 3: Reduced Port Valve (M6100 / M61100) Repair Kits


Size (in) 3 4 6 8 10 12 16 20 & 24
P/N 0677-02 0677-04 0677-05 0677-06 0677-07 0677-08 0677-09 0677-11
  1. Re-Install Disc and Diaphragm Assembly in the valve, taking care not to damage the lower guide area in the center of the valve seat.
  2. Re-install Cover Spring. Replace Valve Cover and tighten Cover Nuts in a crossing pattern to ensure even distribution. Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section.
  3.  Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section.
  4. Return valve to service by following instructions in the Setting the Pressure Controls section matching the valve function.

Limited Warranty : Watts Regulator Co. (the “Company”) warrants each product to be free from defects in material and workmanship under normal usage for a period of one year from the date of original shipment. In the event of such defects within the warranty period, the Company will, at its option, replace or recondition the product without charge. THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT. THE COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. The remedy described in the first paragraph of this warranty shall constitute the sole and exclusive remedy for breach of warranty, and the Company shall not be responsible for any incidental, special or consequential damages, including without limitation, lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling caused by foreign material, damage from adverse water conditions, chemical, or any other circumstances over which the Company has no control. This warranty shall be invalidated by any abuse, misuse, misapplication, improper installation or improper maintenance or alteration of the product. Some States do not allow limitations on how long an implied warranty lasts, and some States do not allow the exclusion or limitation of incidental or consequential damages. Therefore the above limitations may not apply to you. This Limited Warranty gives you specific legal rights, and you may have other rights that vary from State to State. You should consult applicable state laws to determine your rights. SO FAR AS IS CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE YEAR FROM THE DATE OF ORIGINAL SHIPMENT.

WATTS logo               USA: T: 978-689-6066 • F: 978-975-8350Watts.com
Canada: T: 888-208-8927 • F: 905-481-2316Watts.ca
Latin America: T: (52) 55-4122-0138 • Watts.com
ES-ACV-LFM116 2115
© 2021 Watts

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

WATTS User Manuals

Related Manuals