WARNING

The wiring should be done only when the panel and the communicator are disconnected from the power line!

  • Connect the antenna and place it outside of the alarm panel’s box.
  • Connect + and – of the communicator to a max of 12V – 29V DC power supply.

LED Indicator

(+) 12-29 VDC Power Supply
(-) Ground
IN1 Digital Input 1 (pull-up to VDC)
IN2 Digital Input 2 (pull-up to VDC)
IN3 Digital Input 3 (pull-up to VDC)
IN4 Digital Input 4 (pull-up to VDC)
OUT1 Latched/Pulse Output (transistor, open collector, 100mA)
OUT2 Pulse Output (transistor, open collector, 100mA)

LED in dicator

  • Slow flashing – trying to establish connection
  • Constantly On – connection established at good signal level
  • Constantly On, blinking every 5 sec. – connection established at low signal level
  • Fast flashing – sending cellular traffic

Default configuration of the digital inputs and outputs

IN1 General Alarm – Zone 251 OUT1 Preconfigured as Pulse Output
IN2 General Alarm – Zone 252 OUT2 Preconfigured as Pulse Output
IN3 General Alarm – Zone 253
IN4 General Alarm – Zone 254

The inputs are tripped by applying a negative (GND) signal and must share the same common ground.
All inputs can be connected to bell output and will recognize a pulsed voltage
as Fire Alarm and steady voltage as General Alarm. Always use the active
output of the bell and wire it to the alarm panel according to the bell supervision
requirements – refer to the alarm panel installation manual.

Changing the configuration of the digital inputs and outputs (Optional) Note: The device should be powered up and connected to the network.

Changing the configuration from the Uplink Dealers Portal:

  • Open the “Device Dashboard” and navigate to “Advanced Settings”
  • Check the “Enable Online Settings” checkbox and press “Get Current Settings”
  • Change the settings of the digital inputs and outputs under the “Pins” section Changing the configuration from the RControl Admin App:
  • Go to the “Settings” tab and navigate to “Advanced Settings”
  • Enable “Editing”
  • Change the settings of the digital inputs under the “Inputs” section

Register your company at www.uplinkdealers.com or use your existing account to login.

Adding preferred monitoring station

Contact your monitoring station and request your Uplink Dealer Code.

  • Specify your preferred monitoring station during your initial registration in the list found in section “Additional Information” > “Preferred Monitoring Station.” Provide your Dealer code in the corresponding field, OR
  • Add preferred monitoring station/s after registration from My Devices > Monitoring Stations > Add CMS.

Add a new device and choose cellular service monthly billing method

Use the device Serial Number and the Config Key provided with this manual.

  • Go to My Devices > Devices > Add New Device.
  • Select monitoring station (optional)
  • Select preferred cellular service monthly billing method.
  • From Monitoring Station – You will be billed for cellular service by the monitoring station.
  • From Uplink – You will be billed for cellular service by Uplink.

Uplink end-user app credentials

Download the Uplink mobile application on your Android or iOS device by scanning the QR codes.



Remote Arming/Disarming via Keyswitch (Optional)

  • Configure one of the outputs of the unit as a Keyswitch from “Advanced Settings” menu.
  • Configure a zone on the panel as a momentary keyswitch (refer to the panel’s installation manual).
  • Configure a PGM output of the panel to activate (switch to ground), when the panel is armed, and to deactivate, when disarmed (refer to the panel’s installation manual).
  • Wire the device to the panel according to the Key switch wiring diagram below.
    Remote Arming

Initial pairing procedure for Remote Arming/Disarming via Keyswitch

  • Log in to the Uplink App and press Sync with Panel.
  • Ask the end user to enter a Remote PIN code of his/her choice.
  • Disarm (or Arm) from the keypad within 2 minutes to complete the pairing.

IMPORTANT NOTE

Do not power the device before registering it in the Uplink Dealers Portal because the cellular service will be deactivated.