TRANE CO2 Sensing Kit 6 to 25 Ton Packaged Units with Symbio 700 Controls Instruction Manual
- June 9, 2024
- Trane
Table of Contents
- TRANE CO2 Sensing Kit 6 to 25 Ton Packaged Units with Symbio 700 Controls
- SAFETY WARNING
- Important Environmental Concerns
- Important Responsible Refrigerant Practices
- General
- Inspection
- Parts List
- Installation
- CO2 Sensor Operation for Symbio™ 700 with Economizer
- DCV Setup, Damper Position, and CO2 Setpoint
- Overview
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TRANE CO2 Sensing Kit 6 to 25 Ton Packaged Units with Symbio 700 Controls
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up and servicing of heating, ventilating, and air- conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted, or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
Warnings, Cautions, and Notices
Read this manual thoroughly before operating or servicing this unit. Safety
advisories appear throughout this manual as required. Your personal safety and
the proper operation of this machine depend upon the strict observance of
these precautions.
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation that, if not avoided, could result
in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not avoided, could result
in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released into the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine, and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine, and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact on the environment. Trane advocates the responsible handling of all refrigerants including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering, and recycling certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for the responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding are Required!
Failure to follow the code could result in death or serious injury. All field
wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring installation and
grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) is Required!
Failure to wear proper PPE for the job being undertaken could result in death
or serious injury. Technicians, in order to protect themselves from potential
electrical, mechanical, and chemical hazards, MUST follow precautions in this
manual and on the tags, stickers, and labels, as well as the instructions
below:
- Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut-resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE, and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
- When working with or around hazardous chemicals, ALWAYS refer to the appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection, and handling instructions.
- If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR THE INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow the instructions below could result in death or serious
injury.
- All Trane personnel must follow the company’s Environmental, Health, and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
- Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not
be used or reproduced in whole or in part without written permission. Trane
reserves the right to revise this publication at any time and to make changes
to its content without obligation to notify any person of such revision or
change.
Trademarks
All trademarks referenced in this document are the trademarks of their
respective owners.
General
Note:
An economizer must be installed and functional before attempting to install a
CO2 sensing kit.
These sensors detect and control the carbon dioxide level in the conditioned space by measuring CO2 concentration, comparing it with a user-adjustable set point and sending a corresponding control signal to the economizer module. This causes the economizer damper to be positioned so that sufficient fresh air is introduced into the conditioned space to reduce and maintain the CO2 concentration to a minimum level as selected by the user.
Inspection
- Unpack all components of the kit.
- Check carefully for shipping damage. If any damage is found, report it immediately, and file a claim against the transportation company.
- Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
- If the concealed damage is discovered, stop unpacking the shipment.
- Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
- Notify the carrier’s terminal of the damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Note:
Do not attempt to repair any damaged parts until the parts are inspected by
the carrier’s representative.
Parts List
CO2 Sensor:
FIACO2K001
- One (1) CO2 Demand-Controlled Ventilation Wall-Sensor (4190 4100) with instructions and mounting hardware.
FIACO2K002
- One (1) CO2 Demand-Controlled Ventilation Duct -Sensor (4190 4101) with instructions and mounting hardware.
- One (1) “CO2 Kit Has Been Installed” Label
Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could
result in death or serious injury. Disconnect all electric power, including
remote disconnects, and discharge all motor start/run capacitors before
servicing. Follow proper lockout/Tagout procedures to ensure the power cannot
be inadvertently energized. Verify with a CAT III or IV voltmeter rated per
NFPA 70E that all capacitors have discharged.
- Apply provided CO2 and ventilation override wiring diagram label next to the main unit wiring diagram label, located on the compressor access panel.
- Apply the “CO2 kit Has Been Installed” label next to the main unit wiring diagram label.
- Install the CO2 sensor in the conditioned space or return the air duct according to the instructions packed with the sensor.
- Make field wiring connections to Symbio™ 700 UC J22 pins 1-3. Refer to main unit schematic sheet 3 and in this guide.
- Route low voltage external field wiring along with and secure to existing low voltage zone sensor or thermostat wiring.
- Replace any access panels removed for kit installation.
CO2 Sensor Operation for Symbio™ 700 with Economizer
Demand Control Ventilation (DCV)
DCV eliminates over-ventilating the space by allowing the fresh air damper to
close further than non-CO2 sensing systems, which reduces power consumption.
DCV
adjusts the fresh air damper between a DCV Minimum Position and Design Minimum
Position. DCV Minimum Position equals non-CO2 sensing systems minimum
damper position – 10%, or more, down to 0% open.
When the CO2 level is greater than or equal to the DCV Minimum CO2 setpoint
the supply fan is energized and the fresh air damper modulates between the DCV
Minimum Position Setpoint and the Design Minimum Setpoint, increasing the
amount of outdoor airflow and reducing the CO2 level in the space. The damper
will only
open up to the Design Minimum Position Setpoint. If the CO2 level drops below
the DCV Minimum CO2 Setpoint – 50ppm the fresh air damper will drive to the
DCV
Minimum Position. If the CO2 level rises above the Building CO2 setpoint the
fresh air damper will open to the Design Minimum Position setpoint.
DCV Setup, Damper Position, and CO2 Setpoint
Before beginning, turn the fan ON and conduct the Minimum Position Setpoint
procedure used WITHOUT CO2 to obtain and record visually the Minimum Position
Setpoint
setting and/or the corresponding DC voltage settings for the min and max
required to meet ASHRAE standards.
Overview
- TO SHUT DOWN THE UNIT FOR AN EMERGENCY STOP, CONNECT FIELD SUPPLIED CONTROL DEVICE ACROSS PINS 1 & 2. THE UNIT STOPS WHEN THE SWITCH CLOSES.
- DISCHARGE AIR TEMPERATURE SENSOR (DAT) STANDARD ON UNITS WITH SZVAV & MZVAV.
- EXTENSION HARNESS NOT PRESENT ON 15-25T UNITS.
CONDUCTOR NAME | CONDUCTOR BASE COLOR | CONDUCTOR TRACER COLOR |
---|---|---|
1 | BLACK | |
2 | RED | |
3 | BLUE | |
4 | ORANGE | |
5 | YELLOW | |
6 | BROWN | |
7 | RED | BLACK |
8 | BLUE | BLACK |
9 | ORANGE | BLACK |
10 | YELLOW | BLACK |
11 | BROWN | BLACK |
12 | BLACK | RED |
13 | BLUE | RED |
14 | ORANGE | RED |
15 | YELLOW | RED |
16 | BROWN | RED |
17 | BLACK | BLUE |
18 | RED | BLUE |
19 | ORANGE | BLUE |
20 | YELLOW | BLUE |
21 | BROWN | BLUE |
22 | BLACK | ORANGE |
23 | RED | ORANGE |
24 | BLUE | ORANGE |
25 | YELLOW | ORANGE |
26 | BROWN | ORANGE |
Trane and American Standard create comfortable, energy-efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or americanstandardair.com.
Trane and American Standard have a policy of continuous product and product data improvement and reserve the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>