RAB 73613-ESPANHA 1X4 2X2 2X4 Instructions
- June 2, 2024
- RAB
Table of Contents
RAB 73613-ESPANHA 1X4 2X2 2X4
INSTRUCTIONS
EZPAN® HE INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed
and energy-efficient LED lighting and controls that make it easy for
electricians to install and end users to save energy. We’d love to hear your
comments. Please call the Marketing Department at 888-RAB-1000 or
email: marketing@rablighting.com
IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR
FUTURE REFERENCE.
RAB fixtures must be wired in accordance with the National Electrical Code and
all applicable local codes. Proper grounding is required for safety. THIS
PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE
BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND
THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF before installing or maintaining
fixture. No user serviceable parts inside.
CAUTION: For proper weatherproof function all gaskets must be seated
properly and all screws inserted and tightened firmly. Apply weatherproof
silicone sealant around the edge of the ceiling mounting box and/or junction
box. This is especially important with an uneven ceiling surface. Silicone all
plugs and unused conduit entries.
RECESSED CEILING MOUNTING
The fixture is suitable only for INDOOR RECESSED CEILING application. Above
ceiling access required.
To mount in an insulated or non-insulated ceiling – 9/16” or 15/16” exposed
Flat Tee Grid Ceiling follow the steps below.
-
Firmly bend the pre-installed Grid Clips (up and out as shown) Fig. 1.
-
Rotate and slide the Fixture as required to fi t through the Tee-Grid Bar and place it as indicated by the directional arrow as shown in Fig. 2. Secure the Fixture to the Tee-Grid Bar.
-
Support wires are required by Installation Codes. Support the Fixture to the building structure by Support Wires (supplied by others) through the Grid Clip Hole as shown in Fig. 3.
-
Make sure that the orientation of the Splice Box and Access Plate faces an accessible tile to make electrical splices.
-
Loosen Access Plate Screw and remove the Access Plate. Knock out appropriate Conduit Knockouts on the Access Plate to route input conduit. Use appropriate conduit connectors as required by code as shown in Fig. 4.
-
Connect wires as shown in wiring diagram. Push all wires back into the Splice Box. Use appropriate UL approved wire connectors as required by code to complete wiring. Be careful not to pinch wires.
WARNING: To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects. -
Replace Access Plate and tighten Access Plate Screw.
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V, 50 or 60 Hz. For
0-10V Dimming, follow the wiring directions as shown
(Fig. 5).
- Connect the black fixture lead to the LINE supply lead.
- Connect the white fixture lead to the COMMON supply lead.
- Connect the GROUND wire from fixture to supply GROUND.
- Connect the purple fixture lead to the (V+) DIM lead.
- Connect the pink (or gray) fixture lead to the (V-) DIM lead.
NOTE: Do not connect DIM V+ (purple)/ DIM V- (pink/gray) to line voltage
SAFETY INSTRUCTIONS
-
WARNING: Risk of fi re or electric shock. Suitable for damp locations.
-
WARNING: Suitable for 9/16” or 15/16” Flat Tee Grid in bothinsulated ceilings and non-insulated ceilings.
Access above ceiling required. -
WARNING: Do not handle energized fixture when hands are wet, when standing on wet or damp surfaces, or in water.
-
WARNING: Vapor barrier must be suitable for 90°C.
-
WARNING: Fixture to be independently supported to
TROUBLESHOOTING
- Check that the line voltage at the fixture is correct. Refer to wiring directions.
- Be sure the fixture is grounded properly.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch. Do not clean or maintain while fixture is energized.
- Clean polycarbonate lens with non-abrasive cleaning solution.
- Do not open the fixture to clean the LEDs. Do not touch the LEDs.
Note: These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
BATTERY BACKUP MODELS
WIRING
-
CAUTION: FOR BATTERY BACKUP FIXTURE. Voltage can be present in BATTERY.
To prevent high voltage from being present on output leads, Inverter connector must be open. Do not join -
BATTERY connector until installation is complete and AC power is supplied to the emergency driver.(Fig. 6)
-
NOTE: Make sure that the necessary branch circuit wiring is available. An UNSWITCHED AC source of power is required.
The emergency driver must be fed from the same branch circuit as the LED driver. -
CAUTION: Do not use any supply voltage other than 120-277V 50/60 HZ.
- Connect UNSWITCHED HOT fixture lead to HOT AC supply line.
- If using an UNSWITCHED circuit, connect UNSWITCHED and SWITCHED lines together.
- If using a SWITCHED circuit, connect SWITCHED HOT AC fixture lead to the external.
- Connect the pink (or gray) fixture lead to the (V-) DIM lead.
- For 0-10V Dimming, connect DIM (+) and DIM (-) to the supply ground. Do not connect GROUND to the output leads.
- All unused leads must be capped and insulated.
- After installation is complete, supply AC power to the fixture and connect the BATTERY.
- When power is on, the fixture should be on and the Charging Indicator Light should illuminate to indicate the battery is charging.
- Once the BATTERY has charged for at least one hour, a short duration test may be performed by pressing the test button.
- After the battery has charged for 24 hours, a long duration test can be performed by shutting power to the fixture.
OPERATION
- When AC power is applied, the charging indicator light is illuminated, indicating that the BATTERY is being charged.
- When power fails, the standby power automatically switches to emergency power (internal battery), operating at reduced illumination. The emergency driver supplies power in standby power for a minimum of 90 minutes.
- When AC power is restored, the emergency driver automatically returns to charging mode.
MAINTENANCE
Although no routine maintenance is required to keep the emergency driver
functional, it should be checked periodically to ensure that it is working.
The following schedule is recommended:
- Visually inspect the charging indicator light monthly. It should be illuminated.
- Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
- Conduct a 90-minute discharge test once a year. Fixture will operate at reduced illumination for a minimum of 90 minutes.
TROUBLESHOOTING
- Is the fixture grounded properly?
- If the charging indicator light does not illuminate after pressing the test button, check if battery is connected properly.
- Is the Battery Backup Dip Switch Position set to the correct position?
Battery Backup Setting
PRODUCT| WATTAGE| DIP SWITCH POSITION (12W)
EZPANHE 1X4| 12| 1 = Off
2 = On
EZPANHE 1X4| 23, 30
EZPANHE 2X2| 12
EZPANHE 2X2| 23, 30
EZPANHE 2X4| 23, 30, 46
© 2022 RAB LIGHTING Inc.
EZPAN HE – IN – 0522
73613-RAB
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
e-mail
Answered promptly – sales@rablighting.com
Free Lighting Layouts
Answered online or by request